ABB Installation Products K655LR-L2330 15/25kV, 600 Amp, Deadbreak Elbow without Test Point. Cable Insulation Diameter Range…
UPC: 075114331807
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV voltage class with 600 Amp continuous current rating
- Supports cable insulation diameters from 1.180 to 1.465 inches
- Accommodates conductor sizes: 500 kcmil (compressed/stranded), 600 kcmil (compact/solid), 250/300 mm² (compact)
- Fully shielded, fully submersible molded rubber housing with peroxide-cured EPDM construction
- Deadbreak operation for safe connection/disconnection under de-energized conditions
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | 500 kcmil , 600 kcmil |
Connection Type | Deadbreak Elbow |
Connection Type | Deadbreak |
Current Rating | 600 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Copper |
Material | Copper Lug |
Material | Housing - EPDM-Rubber |
Series | K655LR |
Size | 1.180-1.465 inches (cable insulation diameter) |
Size | Cable Insulation Diameter Range 1.180 to 1.465 inch, Conductor Size kcmil Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300 |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps, surge arrestors, and fault current indicators |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K656LR-L2330
Elbow Connector with Test Point, 600 Amp, Dead Break, 15/25 KV, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Compression Lug. Conductor Size AWG Compressed/Stranded 500 or Solid 600 or mm2 250/300.
K151SR-A0220-S
15/25kV, 200 Amp, Deadbreak Straight Receptacle without Test Point, Cable Insulation Diameter 0.575 to 0.740 inches, Aluminum, Conductor Size 220 - #2 Stranded/Compressed or #1 Solid/Compact. S - Cold-Shrinkable Jacket Seal
K151SR-B0250-S
15/25kV, 200 Amp, Deadbreak Straight Receptacle without Test Point, Cable Insulation Diameter 0.635 to 0.905 inches, Aluminum, Conductor Size 250 - 2/0 Stranded/Compressed or 3/0 Solid/Compact. S - Cold-Shrinkable Jacket Seal
K656LR-J0240-SG3
25 kV, 600 Amp, Deadbreak, Elbow Kit, with Test Point, Insulated Plug, Cap, Stud, Aluminum Lug, and Cable Adapter. Cable Insulation Diameter .980-1.180. Conductor Size 1/0 Stranded/Compressed or 2/0 Compact/Solid, with Sealing Kit - Cold-Shrinkable Seal with Copper Braid and Constant Spring Force.
K655LR-J5300-SG3
15/25kV, 600 Amp, Deadbreak Elbow without Test Point, with Sealing Kit. Cable Insulation Diameter Range 0.980 to 1.180 inch, Conductor Size kcmil Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185. Bi-Metal Lug.
K675LR-N2420
900 Amp, 15/25kV, 600 Series Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.515 inch to 1.780 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compact/Solid 1250.Frequently Asked Questions
What is the maximum operating voltage for the K655LR-W0X?
For the 15kV voltage class, the maximum operating voltage is 8.3kV phase-to-ground. For the 28kV voltage class, it is 16.2kV phase-to-ground.
What conductor sizes can the K655LR-W0X accommodate?
It can be used with conductor ranges from #2 AWG to 1250 kcmil for both aluminum and copper conductors.
What is the continuous current rating for this deadbreak elbow?
The K655LR-W0X has a continuous current rating of 600 Amps.
What is the impulse withstand rating for the 28kV voltage class?
The impulse withstand rating for the 28kV voltage class is 140kV BIL (1.2 x 50 microsecond wave).
What is the insulation diameter range for the K655LR-W0X?
The product accommodates insulation diameters ranging from 0.640 inches to 1.935 inches.
What standards does the K655LR-W0X meet?
It meets ANSI/IEEE Standard 386, Latest Revision.
Can this elbow connector be used underwater?
Yes, the K655LR-W0X features a fully shielded, fully submersible molded rubber housing.
What is required for metallic tape shield or drain wire cable?
When used on metallic tape shield or drain wire cable, an ECS cable seal grounding device is recommended.
How to Install K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe installation and setup of 600-ampere and 900-ampere K655/K675LR deadbreak elbow connectors on 15kV and 25kV class systems. Ensure all apparatus are de-energized before beginning.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Wire brush, Hotstick, Suitable sensing device, Torque wrench
Supplies needed:
Lubricant, Compression Lug, Cable Adapter, Insulating Plug, Threaded Stud, No. 14 AWG Copper wire (or equivalent), Suitable grounding connector, Tape marker
- De-energize Apparatus and Inspect Parts
Ensure all apparatus are de-energized before installation or removal. Do not touch or move energized products. Inspect all parts for damage, correct rating, and compatibility. Remove any protective shipping covers and replace with appropriate HV insulated caps or connectors before submerging or energizing.
- Prepare Cable for Installation
Assemble the cable in its final position with enough slack to remove elbows. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4” (45mm) from the centerline of the mating product. Clean the outer surface of the cable for 24” (610mm) or up to the bent back concentric neutral wires.
- Perform Cable Preparation (Specific to Cable Type)
Follow the specific instructions for your cable type (e.g., 20MA/21MA grounding device, UNISHIELD, Jacketed/Non-Jacketed). Remove the outer jacket (if applicable) and prepare the cable dimensions as shown in the diagrams, ensuring correct lengths for insulation, semi-con shield, and tape marker.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare and Measure Conductor
Remove protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or conductor. Verify the exposed conductor length is between 4-1/4” – 4-9/16” (108mm-116mm). If not, redo the assembly.
- Install and Crimp Compression Lug
For copper, fully insert conductor into lug. For aluminum, wire brush and immediately insert. Measure 'Check Dimension' before crimping (must be < 6-3/8”). Crimp lug per instructions, starting at indicated end. Wipe excess inhibitor. Verify post-crimp distance from lug end to adapter is 6-3/8” to 7-1/8” (162mm-181mm). Redo if dimensions are incorrect.
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter is still flush with the tape marker. If not, reposition the cable adapter. Remove the tape marker.
- Prepare and Connect Mating Products
Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and mating part. If the mating part lacks a stud, hand tighten the supplied threaded stud into it. Clean and lubricate both the elbow and mating part with supplied lubricant, keeping surfaces clean.
- Push Elbow onto Mating Part
Push the elbow onto the mating part, aligning the hole in the compression lug with the stud on the mating part.
- Connect Opposite Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert the mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to its supplied instructions.
- Install Insulating Plug and Voltage Detection Cap (if used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps into place.
- Ground the Cable Shield
Insert a wire (min. No. 14 AWG Copper equivalent) through the grounding eye, twist to form a loop, and connect to ground using a suitable connector. Ground the cable shield per grounding device instructions or an alternate method. Waterproof the cable jacket to prevent moisture entry. For 600-amp L-Kits, ensure all components are torqued to specifications.
- Perform Voltage Test (Capacitive Test Point)
The voltage test point is a capacitance device; do not use conventional voltage measuring equipment. Remove the test point cap with a hotstick, peeling at an angle. Test with a suitable sensing device to determine if energized. Treat as energized until 'no voltage' is confirmed by other means to prevent injury. Clean, lubricate, and replace the cap after testing.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.