Authorized ABB Distributor (Installation Products)
ABB - Installation Products K655ETP-J5270 - 600 Amp, 25KV, DeadBreak, Elbow Connector, Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.

ABB Installation Products K655ETP-J5270 600 Amp, 25KV, DeadBreak, Elbow Connector, Cable Insulation Diameter 0.980 inch to 1.180…

UPC: 783786522798


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB K655ETP-J5270 DeadBreak Elbow Connector is a high-performance medium-voltage cable termination solution engineered for utility and industrial power distribution systems. This 600 Amp, 25 kV-rated connector delivers reliable, fully insulated connections in space-constrained environments such as pad-mounted transformers and underground vaults. The deadbreak design enables safe, energized cable system maintenance and expansion without requiring a complete power shutdown, minimizing downtime and operational disruptions. The connector accommodates cable insulation diameters from 0.980 inches to 1.180 inches and supports conductor sizes ranging from 4/0 AWG compressed stranded to 250 mm² solid (126.67 mm² equivalent for compressed stranded). Its integrated bi-metal compression lug ensures robust mechanical strength and electrical continuity while preventing galvanic corrosion between copper and aluminum conductors. The elbow configuration optimizes installation and maintenance workflows in tight spaces, with a fully shielded, submersible molded rubber housing for long-term reliability. Designed for compatibility with industry-standard medium-voltage cables, the K655ETP-J5270 meets ANSI/IEEE Standard 386 requirements. The compression lug provides secure, permanent connections that minimize the risk of loose terminations and associated power quality issues.
  • 600 Amp continuous current rating, 25 kV voltage class
  • Accommodates cable insulation diameters from 0.980" to 1.180"
  • Bi-metal compression lug for copper and aluminum conductors (4/0 AWG to 250 mm²)
  • Deadbreak design enables safe, energized maintenance without power shutdown
  • Fully shielded, submersible molded rubber housing for long-term reliability

Specifications

Amperage Rating
600 A
Application
600 Amps, 25kV
Color
Black
Conductor Range
4/0 STR/COMPR AWG , 250 SOL/COMPT kcmil
Connection
Compression
Connection Type
Compression Lug
Current Rating
600 A
Insulation
EPDM Rubber
Material
Housing - EPDM-Rubber
Material
Bi-Metal
Size
Cable Insulation Diameter 0.980 inch to 1.180 inch
Size
0.980 to 1.180 inches
Standard
ANSI/IEEE Standard 386
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Window-Op Connector
Voltage Rating
25 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
600 Amp, 25KV, DeadBreak, Elbow Connector, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.

K655ETP-J0270

600 Amp, 25KV, DeadBreak, Elbow Connector, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
600 Amp Dead Break Elbow Connector, Test and Ground Connector Kit, 15 KV, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 350 /Solid 400 /mmSquared 185.

655ETP-J0300-DRG

600 Amp Dead Break Elbow Connector, Test and Ground Connector Kit, 15 KV, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 350 /Solid 400 /mmSquared 185.
15kV 600 Series Deadbreak Elbow TAP PLUG Connector, Test and Ground Connector Kit, Test and Ground kit includes - Insulated Cap, Test and Ground reducing tap plug, 600 series Elbow housing, cable adapter and 0370 style compression lug. Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000.

655ETP-P0410-DRG

15kV 600 Series Deadbreak Elbow TAP PLUG Connector, Test and Ground Connector Kit, Test and Ground kit includes - Insulated Cap, Test and Ground reducing tap plug, 600 series Elbow housing, cable adapter and 0370 style compression lug. Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000.
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Test and Ground Connector Kit, Insulated Cap. 200ECS Cold-Shrinkable Jacket Seal Included. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550.

656ETP-K0320-DRG-S

600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Test and Ground Connector Kit, Insulated Cap. 200ECS Cold-Shrinkable Jacket Seal Included. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550.
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Window-Op Connector Kit. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400.

656ETP-K0360

600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Window-Op Connector Kit. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400.
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Test and Ground Connector Kit, Insulated Cap. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0. 200ECS Cold-Shrinkable Jacket Seal Included.

656ETP-G0240-DRG-S

600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Test and Ground Connector Kit, Insulated Cap. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0. 200ECS Cold-Shrinkable Jacket Seal Included.
15kV 600 Series Deadbreak Elbow TAP PLUG Connector, Test and Ground Connector Kit, Test and Ground kit includes - Insulated Cap, Test and Ground reducing tap plug, 600 series Elbow housing, cable adapter and 0370 style compression lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. 200ECS Cold-Shrinkable Jacket Seal Included.

655ETP-M0380-DRG-S

15kV 600 Series Deadbreak Elbow TAP PLUG Connector, Test and Ground Connector Kit, Test and Ground kit includes - Insulated Cap, Test and Ground reducing tap plug, 600 series Elbow housing, cable adapter and 0370 style compression lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. 200ECS Cold-Shrinkable Jacket Seal Included.
15kV 600 Series Deadbreak Elbow TAP PLUG Connector, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. 200ECS Cold-Shrinkable Jacket Seal Included.

655ETP-N0380-S

15kV 600 Series Deadbreak Elbow TAP PLUG Connector, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. 200ECS Cold-Shrinkable Jacket Seal Included.

Frequently Asked Questions

How do I select the correct WINDOW-OP connector kit?

Select the kit by determining the cable insulation diameter (W code), choosing the connector material type, and selecting the proper compression lug code (X code) based on conductor size.

What is the continuous current rating of the connector?

The WINDOW-OP connector has a continuous current rating of 600 Amps.

What is the maximum operating voltage for this connector?

The maximum phase-to-ground operating voltage is 16.2kV, and the maximum phase-to-phase voltage is 28kV.

What is the maximum operating voltage for this connector?

The maximum phase-to-ground operating voltage is 16.2kV, and the maximum phase-to-phase voltage is 28kV.

What is the continuous current rating of the connector?

The WINDOW-OP connector has a continuous current rating of 600 Amps.

How do I select the correct WINDOW-OP connector kit?

Select the kit by determining the cable insulation diameter (W code), choosing the connector material type, and selecting the proper compression lug code (X code) based on conductor size.

What conductor sizes are supported by the '270' X code?

The '270' X code supports 4/0 AWG or 250 kcmil (125 mm2) conductor sizes.

What cable insulation diameter range does the 'J' W code cover?

The 'J' W code covers a cable insulation diameter range of 0.980 inches to 1.180 inches.

What components are included in the K655ETP-W0X-DRG kit?

The kit includes a 600 Series Elbow Housing, WINDOW-OP LB Elbow Tap Plug, Insulated Cap, Cable Size Adapter, Compression Lug, Stud, Silicone Lubricant, Crimp Chart, and Instruction Sheets.

What AC and DC withstand voltages does the connector support?

The connector can withstand 45kV AC for one minute and 84kV DC for 15 minutes.

How to Install the 160DRG/167DRG Insulated Cap with Ground Lead

This guide provides instructions for the safe installation of the 160DRG and 167DRG Insulated Cap with Ground Lead onto ELASTIMOLD 15kV class loadbreak bushing interfaces for insulation, shielding, and watersealing.

Estimated time: 15m

Tools needed:

Full insulated hotstick

Supplies needed:

ELASTIMOLD approved lubricant

  1. Ensure Safety and Inspect Components

    Before beginning, ensure all apparatus is de-energized. This product must only be installed by competent personnel trained in high-voltage electrical safety practices. Inspect the contents of the package for completeness and damage. Verify all components, including the insulated cap and mating products, for proper fit and compatibility.

  2. Connect Electrostatic Grounding Wire

    Connect the free end of the electrostatic grounding wire from the insulated cap to the system ground. Leave enough slack in the wire to allow for hot-stick operation of the insulated cap. CAUTION: Ensure the grounding wire is positioned so it will not contact the bushing interface during operation.

  3. Prepare the Insulated Cap

    Remove the protective cover from the insulated cap. Apply the supplied or ELASTIMOLD approved lubricant generously to the cap's internal mating surface. DO NOT substitute lubricants, as unapproved types may damage the product. Keep the internal mating surface clean and free from dirt or grime.

  4. Install Insulated Cap

    Firmly attach a full insulated hotstick to the pulling eye of the insulated cap. Carefully align the male contact of the insulated cap with the loadbreak bushing interface. Using a fast, firm, and straight motion, push the cap fully onto the bushing until it is completely mated and the locking ring is securely seated. Detach the hotstick from the insulated cap.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.