ABB - Installation Products J4-2226-15-R - 4 Point Junction, with three 200 Amp Bushing Well Interfaces and one 600 Amp Bushing interface, 15kV, Right Parking Stand.
ABB - Installation Products

J4-2226-15-R

UPC: 075114402705


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Overview

The ABB J4-2226-15-R is a 4-point junction designed for 15kV electrical distribution systems. This unit features three 200 Amp bushing well interfaces and one 600 Amp bushing well interface, providing versatile connection options for various load requirements. The junction is equipped with a right parking stand for convenient and secure mounting. This configuration allows for efficient power distribution and management in substations, industrial facilities, and utility applications where reliable connections are paramount. Engineered by ABB Installation Products, this junction box facilitates the termination and branching of medium-voltage power cables. The bushing well interfaces ensure a secure and insulated connection, crucial for maintaining system integrity and preventing electrical hazards. The distinct current ratings (200A and 600A) allow for flexible system design, accommodating both smaller and larger load demands from a single junction point. The 15kV voltage rating signifies its suitability for medium-voltage networks. Key Specifications: * **Manufacturer:** ABB - Installation Products * **SKU:** J4-2226-15-R * **Voltage Rating:** 15 kV * **Current Ratings:** 3 x 200 Amp, 1 x 600 Amp * **Poles:** 4 (3x 200A + 1x 600A) * **Connection Type:** Bushing Well Interfaces * **Mounting:** Right Parking Stand This junction unit is essential for applications requiring robust and reliable power distribution infrastructure. Its design prioritizes safety and operational efficiency, making it a practical choice for electrical engineers and system designers working with medium-voltage power systems.
  • 15kV voltage rating for medium-voltage applications
  • Three 200 Amp bushing well interfaces
  • One 600 Amp bushing well interface
  • 4-point junction configuration
  • Right parking stand for secure mounting

Specifications

Application
Suited for Subsurface, Vault or Padmount Applications and can be used for Sectionalizing, Looping, Tapping and Equipment Bypass
Connection
Push-In
Material
EPDM-Rubber and Stainless Steel Mounting Brackets
Mounting
Right Parking Stand
Size
Overall Length 20.5 inches, Width 6.75 inches
Special Features
4 inch Center Spacing. Right Parking Stand
Standard
ANSI/IEEE Standard 386
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Multi-Point Junction - 4 Points
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
4 Point Junction, with one 200 Amp Bushing Well Interface, two 600 Amp Bushing interfaces and one 200 Amp Bushing Well Interface, 15kV, No Tilt Mounting.

J4-6226-15

4 Point Junction, with one 200 Amp Bushing Well Interface, two 600 Amp Bushing interfaces and one 200 Amp Bushing Well Interface, 15kV, No Tilt Mounting.
25kV, 600 Amp, Deadbreak, Elbow with Test Point, (includes Insulated Plug, Cap, Stud, Lug and Cable Adapter), No Sealing Kit, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000. Any Customer Specific Modifications CS871 - CSA Die Compatibility.

K656LR-N0410-CS871

25kV, 600 Amp, Deadbreak, Elbow with Test Point, (includes Insulated Plug, Cap, Stud, Lug and Cable Adapter), No Sealing Kit, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000. Any Customer Specific Modifications CS871 - CSA Die Compatibility.
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size Compressed/Stranded 500, No Sealing Kit

K656LR-N0330

15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size Compressed/Stranded 500, No Sealing Kit
15/25kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 900 /Compacted Solid 1000 /mmSquared Compact 500. Any Customer Specific Modifications - CS471 - CSA Die Compatibility.

K656LRN0400-CS871

15/25kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 900 /Compacted Solid 1000 /mmSquared Compact 500. Any Customer Specific Modifications - CS471 - CSA Die Compatibility.
6 Point Junction, with three 200 Amp Bushing Well Interfaces and three 600 Amp Bushing Interfaces, 15kV, No Parking Stand. Standard 4 inch spacing.

J6-222666-15-N

6 Point Junction, with three 200 Amp Bushing Well Interfaces and three 600 Amp Bushing Interfaces, 15kV, No Parking Stand. Standard 4 inch spacing.
5 Point Junction, with two 200 Amp Bushing Well Interfaces and three 600 Amp Bushing Interfaces, alternating Interfaces starting with the 600 Amp. 15kV, No Parking Stand. Standard 4 inch spacing.

J5-62626-15-N

5 Point Junction, with two 200 Amp Bushing Well Interfaces and three 600 Amp Bushing Interfaces, alternating Interfaces starting with the 600 Amp. 15kV, No Parking Stand. Standard 4 inch spacing.
15/25kV 600 Series Deadbreak Bushing Extender (without Stud)

K655BEN

15/25kV 600 Series Deadbreak Bushing Extender (without Stud)
15/25kV 600 Series Deadbreak Bushing Extender (with Stud), Pack of 20.

K655BE-20 PACK

15/25kV 600 Series Deadbreak Bushing Extender (with Stud), Pack of 20.

Frequently Asked Questions

What are the available voltage classes?

The junctions are available in 15kV, 25kV, and 35kV voltage classes.

Is the junction housing submersible?

Yes, the molded rubber housing is fully shielded and fully submersible.

How many points can a junction have?

The junctions are available with 2, 3, 4, 5, or 6 points.

What is the 35kV class maximum operating voltage?

For the 35kV voltage class, the maximum phase-to-ground operating voltage is 21.1kV.

What is the 25kV class maximum operating voltage?

For the 25kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV.

What is the 15kV class maximum operating voltage?

For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV.

What types of connectors are compatible?

The junctions provide mating for Elastimold Elbow connectors, both 600 Amp and 200 Amp.

What are the available interface spacing options?

Units are available with standard 4 inch spacing or optional 6.5 inch spacing.

What types of interfaces are available?

The junctions offer 200 Amp deepwell or 600 Amp bushing interfaces.

What standards do these junctions meet?

These junctions meet ANSI/IEEE Standard 386, Latest Revision.

How to Install a J4 Deadbreak Junction with Universal Mount

This guide provides step-by-step instructions for installing a J4 deadbreak junction using the universal mounting method, including assembly and grounding procedures. Ensure all apparatus are de-energized before beginning installation.

Estimated time: 1h

Tools needed:

Wrench, Socket Set, Marking Tool, Measuring Tape, Wire Strippers

Supplies needed:

Suitable Fasteners (for mounting brackets to surface), Grounding Wire (No. 2 solid to 1/0 stranded)

  1. Determine Mounting Location

    DANGER: All apparatus must be de-energized during installation. Determine the desired location for the junction assembly. Use the base plate as a template, place it on the mounting surface, and mark the slot locations for fastener placement.

  2. Mount First Pair of Universal Brackets

    Attach two universal brackets to the marked flat surface using suitable fasteners. Tighten these fasteners securely to ensure no movement during operation.

  3. Assemble Remaining Universal Brackets

    Attach the remaining two universal brackets to the two brackets already mounted on the surface. Position them at the desired angle using the supplied 3/8” hex head cap screw, external tooth lock washer, and 3/8” hex nut. Tighten securely.

  4. Assemble Deadbreak Junction to Base

    Assemble the deadbreak junction to the base bracket assembly and base plate. Use two supplied 1/2” hex head cap screws, two 1/2” split lock washers, and two 1/2” hex nuts, attaching them to the center mounting holes on the bracket assembly. Tighten all components securely.

  5. Mount Junction Assembly to Brackets

    Attach the assembled deadbreak junction to the universal brackets using the supplied 1/2” hex head cap screws, 1/2” split lock washers, and 1/2” hex nuts. Ensure the parking stand is in the upright position before tightening all hardware securely.

  6. Ground the Junction Assembly

    Ground the base bracket assembly and the junction’s black conductive jacket. Connect a grounding wire (No. 2 solid to 1/0 stranded) to the grounding lug provided on the base bracket for this purpose.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.