Authorized ABB Distributor (Installation Products)
ABB - Installation Products 776LR-Q2410-S - 900 Amp, 35KV, DeadBreak Elbow, with Test Point, Cable Insulation Diameter 1.900 inch to 2.120 inch. Copper Compression Lug. Conductor Size Compressed Stranded 1000 kcmil. Cold-Shrinkable Jacket Seal Included.

ABB Installation Products 776LR-Q2410-S 900 Amp, 35KV, DeadBreak Elbow, with Test Point, Cable Insulation Diameter 1.900 inch to…

UPC: 075114261203


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB 776LR-Q2410-S is a 900A, 35kV deadbreak elbow connector engineered for medium-voltage cable terminations in underground distribution networks, switchgear, and pad-mounted transformers. This deadbreak design enables hot-line maintenance without de-energizing the system, reducing downtime during inspections or reconfigurations. The connector accommodates cable insulation diameters between 1.900 and 2.120 inches, making it compatible with 1000 kcmil compressed stranded copper conductors. The integrated test point allows safe voltage verification without system shutdown, while the cold-shrinkable jacket seal provides reliable environmental protection and insulation integrity. The copper compression lug ensures low-resistance connections with long-term mechanical stability. The compact footprint and field-proven reliability make it ideal for space-efficient installations where operational safety is critical. Installation is simplified by the cold-shrinkable seal, which eliminates heat-shrink processes, reducing labor time and minimizing thermal stress on cable insulation. The product meets ANSI/IEEE Standard 386 and is designed for fully shielded, dead-front submersible cable connections to high-voltage apparatus. It supports conductor ranges from #2 AWG to 1250 kcmil for aluminum and copper conductors, with insulation diameters from 0.640" to 1.935". The 900A continuous rating and 25kA symmetrical momentary rating ensure robust performance under fault conditions. Optional accessories allow visible external separation, bypass, isolation, dead-ending, grounding, and testing, as well as adding taps, surge arrestors, and fault current indicators.
  • 900A continuous current rating with 25kA symmetrical momentary rating
  • Accommodates cable insulation diameters from 1.900" to 2.120"
  • Compatible with 1000 kcmil compressed stranded copper conductors
  • Integrated test point for safe voltage verification without system shutdown
  • Cold-shrinkable jacket seal for reliable environmental protection and insulation integrity

Specifications

Amperage Rating
900 A
Application
35 kV, 900 Amps
Color
Black
Conductor Range
1000 kcmil
Connection
Compression
Connection Type
Compression Lug
Current Rating
900 A
Environmental Conditions
All Weather Conditions
Insulation
True
Material
Copper, Cold-Shrinkable Jacket Seal
Material
Housing - EPDM-Rubber
Series
776LR
Size
1.900-2.120 inch (Insulation Diameter)
Special Features
Fully Shielded, Fully Submersible Molded Rubber Housing. 100 percent Peroxide-Cured Construction includes Insulation and Conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. S - Cold Shrinkable Jacket Seal
Standard
ANSI/IEEE Standard 386
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Deadbreak Elbow Connector with Test Point
Voltage Rating
35 kV
Width
12.28 in
Width
311.912 mm
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
10.9600 L
Package Weight (Metric)
4.9720 kg
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.900 inch to 2.120 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000.

755LR-Q0410

600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.900 inch to 2.120 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000.
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. Cold-Shrinkable Jacket Seal Included.

756LR-N0380-S

35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. Cold-Shrinkable Jacket Seal Included.
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 1.725 inch to 1.935 inch. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.

756LR-P2380

35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 1.725 inch to 1.935 inch. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
900 Amp, 35kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.725 inch to 1.935 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.

776LR-P2380

900 Amp, 35kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.725 inch to 1.935 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.

756LR-N2330

35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
900 Amp, 35kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cold-Shrinkable Jacket Seal Included. Cable Insulation Diameter 1.180 inch to 1.465 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold-Shrinkable Jacket Seal Included.

776LR-L5270-S

900 Amp, 35kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cold-Shrinkable Jacket Seal Included. Cable Insulation Diameter 1.180 inch to 1.465 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold-Shrinkable Jacket Seal Included.
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.

756LR-N0330

35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.725 inch to 1.935 inch. Conductor Size AWG or kcmil, Compressed Stranded 1000. Cold-Shrinkable Jacket Seal Included.

756LR-P0410-S

35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.725 inch to 1.935 inch. Conductor Size AWG or kcmil, Compressed Stranded 1000. Cold-Shrinkable Jacket Seal Included.

Frequently Asked Questions

What cable insulation diameter does this elbow support?

The elbow supports cable insulation diameters between 1.900 and 2.120 inches.

What conductor size is compatible with this elbow?

The elbow is designed for 1000 kcmil compressed stranded copper conductors.

Does this elbow include a test point?

Yes, the elbow features an integrated test point for safe voltage verification.

What is the voltage rating of this elbow?

The voltage rating is 35 kilovolts, suitable for medium-voltage applications.

Is a cold-shrinkable jacket seal included?

Yes, a cold-shrinkable jacket seal is included for environmental protection.

What type of lug is used in this elbow?

The elbow uses a copper compression lug for low-resistance connections.

Is this elbow suitable for hot-line maintenance?

Yes, the deadbreak design allows for safe operation and maintenance without de-energizing the system.

How to Install 755/775LR Deadbreak Elbow Connectors

This guide details the installation of 755/775LR Deadbreak Elbow Connectors, providing fully shielded, fully submersible deadfront cable connections for 35kV class systems. It covers cable preparation, connector assembly, and final grounding procedures.

Estimated time: 2h

Tools needed:

Wire strippers, Wire brush (for aluminum conductors), Crimping tool, Hotstick, Suitable sensing device/meter (for capacitive test point), Torque wrench

Supplies needed:

755/775LR Elbow Connector kit (Elbow, Cable Adapter, Compression Lug, Insulating Plug, Lubricant, Stud Prepack), Cable (appropriate type for connection), Grounding wire (at least No. 14 AWG Copper), Suitable grounding connector, Silicone lubricant, HV insulated cap(s) or connector(s) (to replace shipping covers), Waterproofing material (for cable jacket)

  1. De-energize Apparatus and Inspect Components

    DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products in the work area. Inspect all parts for damage, rating, and compatibility with mating parts. Ensure all required tools and supplies are at hand.

  2. Position and Cut Cable

    Position the cable in its final assembled location, ensuring enough slack for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product.

  3. Clean Cable Jacket

    Clean the outer jacket of the cable for a distance of 24 inches (610mm) from the cut end.

  4. Prepare Cable Insulation

    Remove the outer jacket (if applicable) and prepare the cable according to its specific type (e.g., non-jacketed concentric neutral, jacketed shield wires, flat metallic tape shield, fabric tape shield, longitudinally corrugated shield). Refer to the provided diagrams for precise measurements for the cable insulation, semi-con shield, and tape marker locations.

  5. Install Cable Adapter

    Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.

  6. Prepare Conductor

    Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Ensure not to cut or nick the cable adapter or the conductor. The exposed conductor length must be between 4-3/8 inches to 4-3/4 inches (111mm-121mm); otherwise, redo the assembly.

  7. Install Compression Lug

    For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the lug. Measure the 'Check Dimension' (must be less than 7 inches/178mm) before crimping. Crimp the compression lug according to its supplied instructions. Wipe off any excess inhibitor from the lug and cable adapter. After crimping, the distance from the end of the lug to the cable adapter should be 6-7/8 inches to 7-5/8 inches (175mm-194mm); otherwise, redo the assembly.

  8. Install Elbow

    Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Verify the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.

  9. Prepare Mating Products

    DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove any protective caps from the elbow and the mating part. If the mating part lacks a stud, hand tighten the threaded stud supplied with the elbow into it. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean.

  10. Connect Elbow to Mating Part

    Push the elbow onto the mating part, carefully aligning the hole in the compression lug with the stud on the mating part.

  11. Connect Opposite End (Optional)

    If connecting the opposite end of the elbow, clean and lubricate the mating part. Insert the mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to its specific instructions.

  12. Install Insulating Plug (Optional)

    If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down firmly until it snaps into place.

  13. Ground Cable Shield

    Insert one end of a grounding wire (at least No. 14 AWG Copper) through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow instructions for any grounding device used or an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.

  14. Perform Voltage Test

    CAUTION: When constructing 600amp L-Kits, tighten each component to specified torque per plug connector instructions. To test for voltage, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points and follow its manufacturer’s directions. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means, as contamination or incorrect equipment can give false readings. After testing, clean and lubricate the inside of the cap with silicone lubricant and replace it on the test point.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.