ABB Installation Products 756LR-N0330 35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and…
UPC: 783786198726
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV voltage rating for medium voltage applications
- 600A current rating for standard distribution loads
- Test point for diagnostic testing and troubleshooting
- Accommodates cable insulation diameters from 1.515" to 1.780"
- Compatible with 500 kcmil stranded, 600 kcmil solid, and 250-300 mm² compact conductors
Specifications
Amperage Rating | 600 A |
Application | 35 kv, 600 Amp |
Color | Black |
Conductor Range | 500 kcmil , 600 kcmil |
Connection | Compression |
Connection Type | Compression |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | 600 Series |
Size | Cable Insulation Diameter 1.515 inch to 1.780 inch |
Special Features | 35kV, 600 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Width | 12.28 in |
Width | 311.912 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 8.9000 L |
Package Weight (Metric) | 4.0370 kg |

755LR-L0330
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
756LR-P0410-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.725 inch to 1.935 inch. Conductor Size AWG or kcmil, Compressed Stranded 1000. Cold-Shrinkable Jacket Seal Included.
776LR-J5240-S
900 Amp, 35kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cold-Shrinkable Jacket Seal Included. Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0. Cold-Shrinkable Jacket Seal Included.
776LR-P2380-SG3
900 Amp, 35kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included. Cable Insulation Diameter 1.725 inch to 1.935 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
756LR-N0350
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 600 /Compacted Solid 600.
776LR-P5410-S
900 Amp, 35kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cold-Shrinkable Jacket Seal Included. Cable Insulation Diameter 1.725 inch to 1.935 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000. Cold-Shrinkable Jacket Seal Included.
775LR-J2230
900 Amp, 35kV, 600 Series Elbow with insulated plug, cap, stud, lug and cable adapter. Cable Insulation Diameter 0.980 inch to 1.180 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50.Frequently Asked Questions
What is the primary application of the 756LR?
The Elastimold® 756LR provides fully shielded, dead-front submersible cable connections to high-voltage apparatus.
What is the primary application of the 756LR?
The Elastimold® 756LR provides fully shielded, dead-front submersible cable connections to high-voltage apparatus.
What is the primary application of the 756LR?
The Elastimold® 756LR provides fully shielded, dead-front submersible cable connections to high-voltage apparatus.
What is the voltage class and continuous current rating?
The 756LR is for the 35kV voltage class with a continuous current rating of 600 Amps.
What is the voltage class and continuous current rating?
The 756LR is for the 35kV voltage class with a continuous current rating of 600 Amps.
What is the voltage class and continuous current rating?
The 756LR is for the 35kV voltage class with a continuous current rating of 600 Amps.
What cable insulation diameters does the 756LR support?
The 756LR supports cable insulation diameters ranging from 0.760 in to 2.120 in.
What conductor sizes are compatible with the 756LR?
It is compatible with #2 AWG to 1250 kcmil aluminum and copper conductors.
What conductor sizes are compatible with the 756LR?
It is compatible with #2 AWG to 1250 kcmil aluminum and copper conductors.
What cable insulation diameters does the 756LR support?
The 756LR supports cable insulation diameters ranging from 0.760 in to 2.120 in.
How to Install 756LR/776LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe installation and wiring of 756LR and 776LR Deadbreak Elbow Connectors on 35kV class systems. It covers cable preparation, connector assembly, and final connections, emphasizing safety throughout the process.
Estimated time: 2h
Tools needed:
Crimping tool, Wire brush, Hotstick, Suitable sensing device, Cutting tool, Measuring tape or ruler, Wire strippers
Supplies needed:
756LR or 776LR Deadbreak Elbow Connector kit, Cable (appropriate for 35kV class systems), No. 14 AWG Copper wire (or equivalent) for grounding, Suitable connector for grounding wire, HV insulated cap(s) or connector(s) (if replacing shipping covers), Silicone lubricant
- Ensure Apparatus is De-energized and Inspect Parts
Before beginning, ensure all apparatus in the work area are de-energized. Do not touch or move energized products. Inspect all parts from the connector package for damage, correct rating, and compatibility with mating parts.
- Position and Cut Cable
Position the cable in its final assembled location, ensuring enough slack to provide adequate clearance for removing the elbows. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product.
- Clean Cable Outer Jacket
Thoroughly clean the outer jacket of the cable for a distance of 24 inches (610mm).
- Prepare Cable Insulation and Shield
Follow the specific cable preparation instructions for your cable type (e.g., UNISHIELD, LEAD SHEATH, Jacketed, or Non-Jacketed Concentric Neutral) as detailed in the product documentation or supplied with any grounding devices or cable seals being used. Prepare the cable as shown in the diagrams, removing the outer jacket and semi-con shield to the specified dimensions.
- Bevel, Clean, Lubricate, and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Remove Protruding Insulation and Verify Conductor Length
Carefully remove any protruding cable insulation by cutting it even with the end of the cable adapter. Ensure not to cut or nick the cable adapter or the conductor. The exposed conductor length must be between 4-3/8 inches to 4-3/4 inches (111mm-121mm). If not, redo the assembly.
- Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the lug. Measure the 'Check Dimension' (must be less than 7 inches/178mm) before crimping. Crimp the compression lug according to its supplied instructions. After crimping, wipe all excess inhibitor from the lug and cable adapter surface. The distance from the end of the compression lug to the cable adapter should be between 6-7/8 inches to 7-5/8 inches (175mm-194mm).
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Verify the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Prepare Mating Products for Connection
Remove any protective caps from both the elbow and the mating part. If the mating part lacks a stud, hand tighten the threaded stud supplied with the elbow into it. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring surfaces remain clean.
- Connect Elbow to Mating Part
Push the elbow firmly onto the mating part, carefully aligning the hole in the compression lug with the stud on the mating part.
- Connect Opposite End Mating Part (if applicable)
If connecting an opposite end mating part, clean and lubricate its surface. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to its specific instructions.
- Install Insulating Plug and Voltage Detection Cap (if applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps into place. This plug provides a means for detecting system voltage.
- Ground the Cable Shield
Insert one end of a wire (at least No. 14 AWG Copper equivalent) through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded either through a grounding device (following its instructions) or an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test (Post-Installation Check)
CAUTION: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Remove the test point cap with a hotstick, peeling it off at an angle. Use a suitable sensing device, made for use with separable connectors manufactured with capacitive test points, to determine if the cable is energized. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.