ABB Installation Products 756LR-P2380 35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and…
UPC: 783786024667
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV operating voltage rating
- 600 Series Deadbreak Elbow design
- Integrated test point with insulated plug
- Accommodates cable insulation diameters from 1.725" to 1.935"
- Includes copper compression lug for secure termination
Specifications
Amperage Rating | 600 A |
Application | 35 kv, 600 Amp |
Color | Black |
Conductor Range | 700 to 750 kcmil , 900 kcmil |
Connection | Compression |
Connection Type | Compression Lug |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Copper |
Material | Housing - EPDM-Rubber |
Series | 600 Series |
Size | Cable Insulation Diameter 1.725 inch to 1.935 inch |
Special Features | 35kV, 600 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Width | 12.28 in |
Width | 311.912 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

756LR-N0380-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. Cold-Shrinkable Jacket Seal Included.
776LR-P2380
900 Amp, 35kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.725 inch to 1.935 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
756LR-N2330
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
776LR-L5270-S
900 Amp, 35kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cold-Shrinkable Jacket Seal Included. Cable Insulation Diameter 1.180 inch to 1.465 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold-Shrinkable Jacket Seal Included.
756LR-N0330
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
756LR-P0410-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.725 inch to 1.935 inch. Conductor Size AWG or kcmil, Compressed Stranded 1000. Cold-Shrinkable Jacket Seal Included.Frequently Asked Questions
Does this deadbreak elbow have a test point?
Yes, the ABB 756LR-P2380 features a test point with an insulated plug for testing.
What is the maximum operating voltage for this deadbreak elbow?
The ABB 756LR-P2380 deadbreak elbow is rated for 35kV operation.
What is the range of cable insulation diameters supported?
This deadbreak elbow supports cable insulation diameters from 1.725 inches to 1.935 inches.
What type of lug is included with this deadbreak elbow?
The ABB 756LR-P2380 includes a copper compression lug for secure termination.
What conductor sizes are compatible with this elbow?
It is compatible with compressed stranded conductors from 700 to 750 kcmil and compacted solid conductors up to 900 kcmil.
How to Install 756/776LR Deadbreak Elbow Connectors
This guide provides detailed instructions for the safe and proper installation of 756/776LR Deadbreak Elbow Connectors on 35kV class systems, including cable preparation, lug crimping, and connection to mating products. Ensure all apparatus are de-energized before starting.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Wire brush, Crimping tool, Torque wrench, Hotstick, Suitable sensing device (for capacitive test points), Suitable connector (for grounding wire), Cleaning cloths
Supplies needed:
756LR/776LR Deadbreak Elbow Connector, Cable Adapter, Compression Lug, Insulating Plug (if used), Lubricant (silicone), Threaded stud, Tape marker, Wire (min. No. 14 AWG Copper) for grounding, Mating product (e.g., apparatus bushing, connector plug), Grounding device (optional), Waterproofing material (for cable jacket), HV insulated cap(s) or connector(s) (if replacing shipping covers)
- Position and Cut Cable
Position the cable in its final assembled location, ensuring enough slack for elbow removal. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. DANGER: All apparatus must be de-energized during installation.
- Clean Cable Outer Jacket
Clean the outer jacket of the cable for a distance of 24 inches (610mm).
- Prepare Cable End
Prepare the cable according to its type (Unishield, Lead Sheath, Jacketed, or Non-Jacketed). Remove the outer jacket (if applicable) and prepare the cable insulation and semi-con shield to the dimensions specified in the documentation, applying a tape marker as indicated.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Expose Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Ensure not to cut or nick the cable adapter or the conductor. The exposed conductor length must be between 4-3/8 inches to 4-3/4 inches (111mm-121mm). If not, redo the assembly.
- Crimp Compression Lug
For copper, fully insert conductor into lug. For aluminum, wire brush and immediately insert. Measure 'Check Dimension' (<7in/178mm) before crimping; redo if not met. Crimp lug per instructions. Wipe excess inhibitor. Verify post-crimp distance from lug end to cable adapter is 6-7/8in to 7-5/8in (175mm-194mm); redo if not met.
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Verify the cable adapter is still flush with the tape marker; reposition if necessary. Remove the tape marker.
- Prepare Mating Part for Connection
DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud (if supplied with elbow) into the mating part if it's not already equipped. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, aligning the hole in the compression lug with the stud on the mating part.
- Connect Second Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to its specific instructions.
- Install Insulating Plug and Voltage Detection Cap
If an insulating plug is used, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps into place. CAUTION: The insulating plug provides a means for detecting system voltage.
- Ground Cable Shield
Insert one end of a wire (at least No. 14 AWG Copper ampacity) through the grounding eye and twist to form a small loop, ensuring not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded either via a grounding device or an alternate method. Waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test (Optional)
If the connector has an integral capacitance test point, remove the test point cap with a hotstick by peeling it off at an angle. WARNING: This is a capacitance device, not directly connected to the conductor. Use a suitable sensing device designed for capacitive test points and follow its manufacturer's directions. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the cap and replace it.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.