ABB Installation Products 756LR-K0240 35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and…
UPC: 783786440245
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV voltage rating for medium-voltage applications
- Supports cable insulation diameters from 1.090" to 1.310"
- Accommodates conductor sizes 1/0 AWG to 2/0 AWG (compressed stranded or compacted solid)
- Includes insulated plug, cap, stud, lug, and cable adapter for complete termination
- Integrated test point enables safe voltage verification without de-energizing the system
Specifications
Amperage Rating | 600 A |
Application | 35 kv, 600 Amp |
Color | Black |
Conductor Range | 1/0 STR/COMPR AWG , 2/0 SOL/COMPT AWG |
Connection | Compression |
Connection Type | Compression Lug |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | 600 Series |
Size | Cable Insulation Diameter 1.090 inch to 1.310 inch |
Special Features | 35kV, 600 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Width | 12.28 in |
Width | 311.912 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 8.3700 L |
Package Weight (Metric) | 3.7970 kg |

755LRTP-K0240-DRG
600 Amp, 35kV, Stick-Op Connector Kit with Test Point, Insulated Cap and Reducing Tap Plug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0.
756LR-M0300
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185.
756LR-M0320-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550. Cold-Shrinkable Jacket Seal Included.
756LR-K0230-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50. Cold-Shrinkable Jacket Seal Included.
756LR-M0330-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. Cold-Shrinkable Jacket Seal Included.
756LR-M0320
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550.
756LR-J0250-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG or kcmil, Compressed Stranded 2/0 /Compacted Solid 3/0 /mmSquared Compact 70. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.Frequently Asked Questions
What cable insulation diameters does this elbow support?
The elbow supports cable insulation diameters ranging from 1.090 inch to 1.310 inch.
What is the voltage rating of this elbow?
This elbow is rated for 35kV medium-voltage applications.
What conductor sizes are compatible with this elbow?
The elbow is compatible with 1/0 AWG to 2/0 AWG conductors, including compressed stranded and compacted solid types.
Does this elbow include a test point?
Yes, the elbow features an integrated test point for safe voltage verification without de-energizing the system.
What materials are used in the lug?
The lug is made of aluminum and designed for compression termination, ensuring strong mechanical and electrical connections.
How to Install 756LR/776LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe installation and connection of 756LR/776LR Deadbreak Elbow Connectors on 35kV class systems. Ensure all apparatus are de-energized before beginning and that installation is performed by competent personnel trained in high voltage safety practices.
Estimated time: 2h
Tools needed:
Crimping tool, Wire brush, Hotstick, Suitable sensing device for capacitive test points, Wire strippers, Cutting tool
Supplies needed:
756LR or 776LR Elbow Connector, Cable Adapter, Compression Lug, Insulating Plug (if used), Lubricant, Threaded Stud (if not integrated), Grounding wire (min. No. 14 AWG Copper), Suitable grounding connector, Mating product (e.g., apparatus bushing, connector plug)
- De-energize and Position Cable
DANGER: Ensure all apparatus are de-energized before starting. Position the cable in its final assembled location, allowing enough slack for elbow removal. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product.
- Clean Cable Outer Jacket
Clean the outer jacket of the cable for a distance of 24 inches (610mm) from the cut end.
- Prepare Cable
Prepare the cable according to its type (e.g., non-jacketed concentric neutral, jacketed shield wires, flat metallic tape shield, fabric tape shield, longitudinally corrugated shield). Remove the outer jacket (if applicable) and expose the cable insulation and semi-con shield to the specified dimensions as per the provided diagrams. If using a grounding device or shield adapter, refer to their specific instructions.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor
Carefully remove the protruding cable insulation by cutting it even with the end of the cable adapter. Ensure the exposed conductor length is between 4-3/8 inches to 4-3/4 inches (111mm-121mm). Do not cut or nick the cable adapter or the conductor.
- Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the lug. Measure the 'Check Dimension' (must be less than 7 inches / 178mm) before crimping. Crimp the lug following its specific instructions. Wipe off any excess inhibitor. Verify the distance from the end of the compression lug to the cable adapter is between 6-7/8 inches to 7-5/8 inches (175mm-194mm) after crimping.
- Install Elbow
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Confirm the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Prepare Mating Products
Remove any protective caps from both the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud (supplied with the elbow) into the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring all surfaces remain clean.
- Connect Elbow to Mating Part
Push the elbow firmly onto the mating part, carefully aligning the hole in the compression lug with the stud on the mating part.
- Connect Opposite End (if applicable)
If connecting to an opposite end, clean and lubricate the mating part for that end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to its specific instructions.
- Install Insulating Plug (if used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap onto the elbow and push down hard until it snaps securely into place. CAUTION: The insulating plug provides a means for detecting system voltage.
- Ground Cable Shield
Insert one end of a grounding wire (with ampacity at least equivalent to No. 14 AWG Copper) through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow instructions for any grounding device or use an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test (if applicable)
CAUTION: When constructing 600amp L-Kits, tighten each component to specified torque per instructions provided with plug connectors. If the elbow has an integral capacitance test point, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: This is a capacitance device; do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.