ABB Installation Products 756LR-M0320-S 35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and…
UPC: 783786475681
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV voltage rating with 600A continuous current capacity
- Built-in test point for safe electrical testing without disconnection
- Accommodates cable insulation diameters from 1.370 to 1.630 inches
- Supports conductor sizes: 450 kcmil compressed stranded, 500/550 kcmil compacted solid
- Fully shielded, submersible molded rubber housing with cold-shrinkable jacket seal
- Meets ANSI/IEEE Standard 386 with 150kV BIL impulse withstand rating
- Includes aluminum compression lug, insulated plug/cap, stud, and cable adapter
Specifications
Amperage Rating | 600 A |
Application | 35 kv, 600 Amp |
Color | Black |
Conductor Range | 450 kcmil , 500 to 550 kcmil |
Connection | Compression |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Housing - EPDM-Rubber |
Special Features | 35kV, 600 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. S - Cold-Shrinkable Jacket Seal |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Width | 12.28 in |
Width | 311.912 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 9.3300 L |
Package Weight (Metric) | 4.2320 kg |

755LR-M0320-S
35kv 600 Amp Elbow Deadbreak With Sealing Kit, 600 Series Elbow (with insulating Plug, Cap, Stud, Lug and Cable Adapter), Cable Insulation Diameter 1.370-1.630, Aluminum Lug, Conductor 450 Stranded/Compressed or 500 Compact/Solid.
756LR-K0230-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50. Cold-Shrinkable Jacket Seal Included.
756LR-M0330-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. Cold-Shrinkable Jacket Seal Included.
756LR-M0320
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550.
756LR-J0250-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG or kcmil, Compressed Stranded 2/0 /Compacted Solid 3/0 /mmSquared Compact 70. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
756LR-L2320-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
756LR-L2330-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
756LR-L0270
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.Frequently Asked Questions
What is the AC one-minute withstand voltage?
The AC one-minute withstand voltage is 50kV.
What is the primary application of the 756LR?
It provides fully shielded, dead-front submersible cable connections to high-voltage apparatus.
What is the maximum voltage rating of the 756LR?
The 756LR can be used through 35kV.
What conductor sizes are compatible with the 756LR?
It is compatible with conductor sizes from #2 AWG to 1250 kcmil for aluminum and copper conductors.
What cable insulation diameters does the 756LR support?
It supports cable insulation diameters from 0.760 inches to 2.120 inches.
What standard does the 756LR meet?
The 756LR meets ANSI/IEEE Standard 386, Latest Revision.
What is the maximum phase-to-ground operating voltage?
The maximum phase-to-ground operating voltage for the 35kV class is 21.1kV.
What is the continuous current rating of the 756LR?
The continuous current rating for the 756LR is 600 Amps.
Is the 756LR submersible?
Yes, the 756LR features a fully shielded, fully submersible molded rubber housing.
How is the 756LR connected or disconnected?
It can be easily connected or disconnected using standard hand tools and equipment, but only in a de-energized state.
How to Install 756/776LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 756LR and 776LR Deadbreak Elbow Connectors on 35kV class systems, including cable preparation, lug crimping, and connection to mating apparatus.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimp tool, Wire brush (for aluminum conductors), Hotstick, Suitable voltage sensing device (for capacitive test points), Torque wrench
Supplies needed:
756/776LR Elbow Connector Kit (Elbow, Cable Adapter, Compression Lug, Insulating Plug, Crimp connector, Lubricant, Stud Prepack), Grounding wire (at least No. 14 AWG Copper), Suitable ground connector, Waterproofing material (for cable jacket)
- Safety First: De-energize and Inspect
Before beginning, ensure all apparatus in the work area are completely de-energized. Do not touch or move energized products. Inspect all components of the 756/776LR connector kit for damage, correct rating, and compatibility with mating parts. Read these instructions fully before proceeding.
- Prepare the Cable for Connection
Position the cable in its final assembled location, ensuring enough slack for elbow removal. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer jacket of the cable for a distance of 24 inches (610mm). Then, prepare the cable according to its type (e.g., non-jacketed, jacketed shield, flat metallic tape, fabric tape, or longitudinally corrugated shield) by removing the outer jacket and preparing the insulation and semi-con shield to the specified dimensions as detailed in the product diagrams.
- Install Cable Adapter and Prepare Conductor
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean the cable insulation, then lubricate it, always working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker. Carefully remove the protruding cable insulation by cutting it even with the end of the cable adapter, ensuring not to nick the cable adapter or the conductor. The exposed conductor length must be between 4-3/8 inches to 4-3/4 inches (111mm-121mm).
- Crimp the Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the compression lug. Measure the 'Check Dimension' before crimping; it must be less than 7 inches (178mm). Crimp the compression lug following the specific instructions provided with the lug. After crimping, wipe all excess inhibitor from the compression lug and cable adapter surface. The distance from the end of the compression lug to the cable adapter should be between 6-7/8 inches to 7-5/8 inches (175mm-194mm).
- Install the Elbow onto the Cable Adapter
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter, pushing until it cannot advance further. Verify that the cable adapter remains flush with the tape marker; reposition if necessary. Once correctly seated, remove the tape marker.
- Connect the Elbow to Mating Apparatus
Remove any protective caps from both the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud supplied with the elbow into the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring all surfaces are clean. Push the elbow onto the mating part, carefully aligning the hole in the compression lug with the stud on the mating part. Clean and lubricate the mating part for the opposite end of the elbow, then insert it into the elbow, engage the threads, and hand tighten. Finally, torque the mating part according to its specific instructions.
- Install Insulating Plug and Ground the Cable Shield
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow, pushing down firmly until it snaps into place. Insert one end of a grounding wire (with ampacity at least equivalent to No. 14 AWG Copper) through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded according to the instructions supplied with any grounding device, or via an alternate method if no device is used. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test (Post-Installation)
To test for voltage, remove the test point cap using a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points and follow its manufacturer’s directions. Contamination or incorrect equipment can give a false 'no voltage' indication; treat the elbow as energized until the 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.