ABB Installation Products 756LR-J0270 35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and…
UPC: 075114249201
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV Voltage Rating
- 600 Series Deadbreak Elbow Design
- Test Point for Diagnostics
- Aluminum Compression Lug
- Cable Insulation Diameter: 0.980" - 1.180"
Specifications
Amperage Rating | 600 A |
Application | 35 kv, 600 Amp |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Connection | Compression |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Housing - EPDM-Rubber |
Special Features | 35kV, 600 Amp Deadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Width | 12.28 in |
Width | 311.912 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 8.4600 L |
Package Weight (Metric) | 3.8380 kg |

756LR-K0270-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
756LR-J2230-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG or kcmil, Compressed Stranded #1 /Compacted Solid 1/0. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
756LR-K0260-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95. Cold-Shrinkable Jacket Seal Included.
756LR-K0240
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0.
756LR-M0300
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185.
756LR-M0320-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550. Cold-Shrinkable Jacket Seal Included.
756LR-K0230-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50. Cold-Shrinkable Jacket Seal Included.
756LR-M0330-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. Cold-Shrinkable Jacket Seal Included.Frequently Asked Questions
Can the elbow connector be connected or disconnected while energized?
No, it can only be easily connected or disconnected using standard hand tools and equipment in a de-energized state.
What standard does the 756LR meet?
The 756LR meets ANSI/IEEE Standard 386, Latest Revision.
What is the impulse withstand rating (BIL)?
The impulse withstand (BIL) rating is 150kV.
What is the continuous current rating?
The continuous current rating for the 756LR is 600 Amps.
What is the maximum operating phase-to-ground voltage?
The maximum phase-to-ground operating voltage for the 35kV class is 21.1kV.
What insulation diameter range does it support?
It supports insulation diameters from 0.760 inches to 2.120 inches.
What conductor types and sizes are compatible?
It is compatible with aluminum and copper conductors ranging from #2 AWG to 1250 kcmil.
What voltage class is the 756LR rated for?
The 756LR is rated for use through 35kV voltage class applications.
What is the purpose of the 756LR elbow connector?
It provides fully shielded, dead-front submersible cable connections to high-voltage apparatus.
Can the elbow connector be connected or disconnected while energized?
No, it can only be easily connected or disconnected using standard hand tools and equipment in a de-energized state.
How to Install 756LR/776LR Deadbreak Elbow Connectors
This guide provides detailed instructions for the safe and proper installation of 756LR and 776LR deadbreak elbow connectors on 35kV class systems, including cable preparation, lug crimping, and connection to mating apparatus. Ensure all apparatus are de-energized before starting.
Estimated time: 1h 30m
Tools needed:
Cutting tool, Wire strippers, Wire brush, Crimping tool, Torque wrench, Hotstick, Suitable sensing device for capacitive test points, Cleaning cloths
Supplies needed:
756LR/776LR Elbow Connector, Cable Adapter, Compression Lug, Insulating Plug, Crimp connector, Lubricant (silicone), Stud Prepack, No. 14 AWG Copper wire (or equivalent), Grounding connector, Waterproofing material for cable jacket, Protective caps
- De-energize Apparatus and Inspect Parts
DANGER: Ensure all apparatus in the work area are de-energized during installation or removal of any parts. Do not touch or move energized products. This product should only be installed by competent personnel trained in high voltage safety practices. Inspect all parts for damage, correct rating, and compatibility with mating components.
- Prepare Cable Position and Clean Jacket
Position the cable in its final assembled location, ensuring enough slack to provide adequate clearance for removing the elbows. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer jacket of the cable for a distance of 24 inches (610mm).
- Prepare Cable Ends
Follow the specific instructions supplied with any grounding device or cable shield adapter (e.g., 20MA, 21MA, 600ECS, 10TL) for removal of the cable outer jacket, shield connection, and grounding. For jacketed and non-jacketed cables, remove the outer jacket (where applicable) and prepare the cable as shown in the provided diagrams, exposing insulation, semi-con shield, and neutral/shield wires to specified lengths.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean, then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor for Lug
Remove any protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. Verify the length of the exposed conductor is between 4-3/8 inches (111mm) and 4-3/4 inches (121mm). If not, redo the assembly.
- Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the “Check Dimension” before crimping; it should be less than 7 inches (178mm). Crimp the compression lug following its supplied instructions. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. Verify the distance from the end of the compression lug to the cable adapter after crimping is between 6-7/8 inches (175mm) and 7-5/8 inches (194mm). If not, redo the assembly.
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until the elbow cannot advance further. Make sure the cable adapter is still flush with the tape marker. If not, reposition the cable adapter. Remove the tape marker.
- Connect Elbow to Mating Part
DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from both the elbow and the mating part. Hand tighten the threaded stud (supplied with the elbow) into the mating part if it is not already equipped. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean. Push the elbow onto the mating part, lining up the hole in the compression lug with the stud on the mating part.
- Connect Opposite Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to the instructions supplied with that specific mating part.
- Install Insulating Plug and Cap (if used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps into place. CAUTION: The insulating plug provides a means for detecting system voltage; follow voltage test directions.
- Ground the Cable Shield
Insert one end of a piece of wire with ampacity at least equivalent to No. 14 AWG Copper through the grounding eye and twist to make a small loop. Do not damage the eye. Connect this wire to ground using a suitable connector. The shield of the cable must be grounded according to the instructions supplied with the grounding device, or through an alternate method if no grounding device is used.
- Waterproof Cable Jacket and Perform Voltage Test
It is recommended that the jacket of the cable be waterproofed at this point to prevent moisture from entering the cable. For voltage testing, remove the test point cap with a hotstick (peel off at an angle). WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Use a suitable sensing device made for capacitive test points. Do not use conventional voltage measuring equipment. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.