ABB Installation Products 755LR-K0240 600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable…
UPC: 783786627110
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp continuous current rating, 35kV class insulation
- Includes insulated plug, cap, stud, lug, and cable adapter
- Aluminum compression lug for 1/0 AWG (compressed stranded) or 2/0 AWG (compacted solid) conductors
- Cable insulation diameter range: 1.090 inch to 1.310 inch
- Part of ABB’s 600 Series deadbreak elbows for medium-voltage applications
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | 1/0 STR/COMPR AWG , 2/0 SOL/COMPT AWG |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Housing - EPDM-Rubber |
Size | Cable Insulation Diameter 1.090 inch to 1.310 inch |
Special Features | 100 Percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected Using Standard Hand Tools and Equipment in a De-energized State. Optional Accessories allow Visible External Separation, By-Pass, Isolation, Dead-Ending, Grounding, and Testing as well as Adding Taps, Surge Arrestors, and Fault Current Indicators |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 35 kV |
Package Weight (Imperial) | 8.5000 L |
Package Weight (Metric) | 3.8560 kg |

756ETP-J0240-DRG-S
600 Amp, 35kV, Deadbreak, Window Op With Test Point, Elbow Tap Plug, Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG, Compressed Stranded 1/0 Compacted Solid 2/0. With Insulated Cap and Cold-Shrinkable Jacket Seal.
755LR-K0250-SG3
35kv, 600 Amp, Loadbreak, Elbow, with Sealing Kit, Cable Insulation Diameter 1.090-1.310 inches, Aluminum Lug, Conductor Size 2/0 Compressed/Stranded or 3/0 Compact/Solid.
755LR-K0230
35kV, 600 Amp Deadbreak Elbow without Test Point, Cable Insulation Diameter 1.090 to 1.310 inches (27.686 to 33.274 mm), Universal Aluminum Connector, For Cable Size #1 Stranded/Compressed, 1/0 Solid/Compact
755LR-K-5240-SG3
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.090 inch to 1.310 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0. 200ECS-G3 Jacket Seal and Grounding Kit Included.
755LR-K-0260-S
600 Amp, 35kV, 600 Series Deadbreak Elbow with Sealing Kit (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95.
755LR-J2260
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.980 inch to 1.180 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95.
755LR-J2250
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.980 inch to 1.180 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 2/0 /Compacted Solid 3/0 /mmSquared Compact 70.
755LR-J0300-S
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185. 200ECS Cold-Shrinkable Jacket Seal Included.Frequently Asked Questions
What is the primary application of the 755LR elbow?
The 755LR is designed to provide fully shielded, dead-front submersible cable connections to high-voltage apparatus.
Does the 755LR meet any industry standards?
Yes, the 755LR meets ANSI/IEEE Standard 386, Latest Revision.
How is the 755LR connected or disconnected?
It can be easily connected or disconnected using standard hand tools and equipment in a de-energized state.
What materials are used in the 755LR construction?
It features 100% peroxide-cured construction, including insulation and conductive EPDM materials.
Is the 755LR submersible?
Yes, it features a fully shielded, fully submersible molded rubber housing.
What is the impulse withstand rating of the elbow?
The impulse withstand (BIL) rating is 150kV (1.2 x 50 microsecond wave).
What is the continuous current rating of the 755LR?
The 755LR has a continuous current rating of 600 Amps.
What is the maximum operating voltage for the 755LR?
The maximum phase-to-ground operating voltage is 21.1kV, and the maximum phase-to-phase is 36.6kV.
What insulation diameters does the 755LR support?
The 755LR supports cable insulation diameters ranging from 0.760 in to 2.120 in.
What conductor sizes are compatible with the 755LR?
It is compatible with conductor sizes from #2 AWG to 1250 kcmil for both aluminum and copper conductors.
How to Install 755/775LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 755/775LR Deadbreak Elbow Connectors, designed for fully shielded, submersible cable connections to high voltage apparatus on 35kV class systems.
Tools needed:
Crimping tool, Wire brush, Hotstick, Suitable sensing device for capacitive test points, Cable preparation tools (e.g., wire strippers, knife), Torque wrench
Supplies needed:
Lubricant (supplied with kit), Tape marker, Grounding wire (minimum No. 14 AWG Copper equivalent), Suitable connector for grounding wire, Silicone lubricant, Waterproofing material (for cable jacket)
- Prepare for Installation and De-energize Apparatus
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products in the work area. Inspect all package contents and components for completeness, damage, proper rating, and compatibility with mating products. Read the entire installation instructions before starting and ensure all required tools are at hand, maintaining cleanliness throughout the procedure.
- Position and Clean Cable
Position the cable in its final assembled location, ensuring enough slack for adequate clearance to remove the elbows. If using concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer jacket of the cable for a distance of 24 inches (610mm).
- Prepare Cable Jacket and Shield
Prepare the cable by removing the outer jacket (if applicable) and shield according to the specific dimensions and diagrams provided for your cable type (e.g., non-jacketed concentric neutral, jacketed shield wires, flat metallic tape shield, fabric tape shield, or longitudinally corrugated shield). Refer to the installation instructions supplied with any grounding devices or cable shield adapters if they are being used.
- Bevel, Clean, Lubricate, and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Trim Cable Insulation
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Exercise caution to avoid cutting or nicking the cable adapter or the conductor. Verify that the exposed conductor length is between 4-3/8 inches to 4-3/4 inches (111mm-121mm). If the length is outside this range, redo the assembly.
- Install and Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the 'Check Dimension' before crimping; it should be less than 7 inches (178mm). If not, redo the assembly. Crimp the compression lug following the crimping instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. Verify the distance from the end of the compression lug to the cable adapter after crimping is between 6-7/8 inches to 7-5/8 inches (175mm-194mm). If not, redo the assembly.
- Lubricate and Install Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker; if not, reposition the cable adapter. Remove the tape marker.
- Prepare Mating Products and Stud
WARNING: DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED. Remove protective caps from both the elbow and the mating part. Hand tighten the threaded stud supplied with the elbow into the mating part, if the mating part is not already equipped with a stud. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring all surfaces remain clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, carefully aligning the hole in the compression lug with the stud on the mating part.
- Connect Opposite End of Elbow (if applicable)
Clean and lubricate the mating part intended for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to the instructions supplied with that specific mating part.
- Install Insulating Plug (if used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap onto the elbow and push down firmly until it snaps securely into place.
- Ground the Cable Shield
Insert one end of a piece of wire, with ampacity at least equivalent to No. 14 AWG Copper, through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow the instructions supplied with the grounding device, or use an alternate method if no device is used. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test
CAUTION: When constructing 600amp L-Kits, ensure each component is tightened to the specified torque per the instructions provided with plug connectors. To test for voltage, remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device designed for separable connectors with capacitive test points, following the manufacturer’s directions. Contamination, moisture, dirt, or incorrect equipment can provide a false 'no voltage' indication on an energized elbow. To prevent serious or fatal injury, treat the elbow as energized until the 'no voltage' test point indication is confirmed by other means. After voltage detection, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.