Contact for Pricing
Overview
- 35kV voltage rating with 21.1kV phase-to-ground and 36.6kV phase-to-phase operating voltage
- 600A continuous current rating; 25kA momentary fault current withstand (10 cycles)
- Supports cable insulation diameters from 1.090" to 1.310" (27.686 to 33.274 mm)
- Universal aluminum connector compatible with #1 AWG stranded/compressed or 1/0 AWG solid/compact conductors
- Fully shielded, submersible molded rubber housing with deadbreak (de-energized) disconnection capability
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | #1 STR/COMPR AWG , 1/0 SOL/COMPT AWG |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Housing - EPDM-Rubber |
Size | Cable Insulation Diameter 1.090 to 1.310 inches (27.686 to 33.274 mm) |
Special Features | 100 Percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected Using Standard Hand Tools and Equipment in a De-energized State. Optional Accessories allow Visible External Separation, By-Pass, Isolation, Dead-Ending, Grounding, and Testing as well as Adding Taps, Surge Arrestors, and Fault Current Indicators |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 8.1800 L |
Package Weight (Metric) | 3.7100 kg |

755LR-H0230
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50.
755LR-K-5240-SG3
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.090 inch to 1.310 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0. 200ECS-G3 Jacket Seal and Grounding Kit Included.
755LR-K-0260-S
600 Amp, 35kV, 600 Series Deadbreak Elbow with Sealing Kit (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95.
755LR-J2260
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.980 inch to 1.180 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95.
755LR-J2250
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.980 inch to 1.180 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 2/0 /Compacted Solid 3/0 /mmSquared Compact 70.
755LR-J0300-S
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185. 200ECS Cold-Shrinkable Jacket Seal Included.
755LR-J0230
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50.Frequently Asked Questions
What is the maximum operating voltage for the 755LR?
The 755LR elbow connector is designed for use through 35kV, with a maximum phase-to-ground operating voltage of 21.1kV.
Is the 755LR suitable for submersible applications?
Yes, the 755LR features a fully shielded, fully submersible molded rubber housing.
What is the Corona Extinction voltage?
The Corona Extinction voltage is 26kV AC at 3pC sensitivity.
What is the Impulse Withstand (BIL) rating?
The Impulse Withstand (BIL) rating for the 35kV voltage class is 150kV (1.2 x 50 microsecond wave).
What is recommended for metallic tape shield cables?
When used on metallic tape shield or drain wire cable, an ECS cable seal grounding device is recommended.
What standards does the 755LR meet?
The 755LR meets ANSI/IEEE Standard 386, Latest Revision.
What are the insulation diameter requirements for cables?
The 755LR is compatible with cables having insulation diameters from .760 inches to 2.120 inches.
What is the continuous current rating of the 755LR?
The 755LR elbow connector has a continuous current rating of 600 Amps.
What conductor sizes are compatible with the 755LR?
The 755LR is compatible with aluminum and copper conductors ranging from #2 AWG to 1250 kcmil.
What is the maximum phase-to-phase voltage?
The maximum phase-to-phase voltage for the 35kV voltage class is 36.6kV.
How to Install 755LR/775LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe installation and preparation of 755LR and 775LR Deadbreak Elbow Connectors on 35kV class systems, including cable preparation, lug crimping, and connection to mating parts. All apparatus must be de-energized during installation.
Estimated time: 1h 30m
Tools needed:
Cable knife or strippers, Beveling tool, Wire brush (for aluminum conductor), Crimping tool, Hotstick, Suitable voltage sensing device
Supplies needed:
755LR or 775LR Deadbreak Elbow Connector kit (Elbow, Cable Adapter, Compression Lug, Insulating Plug, Lubricant, Stud Prepack), Grounding wire (minimum No. 14 AWG Copper), Suitable ground connector, Waterproofing material for cable jacket, HV insulated cap(s) or connector(s) (if replacing shipping covers)
- Prepare for Installation and Inspect Parts
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products in the work area. Inspect all parts for damage, proper rating, and compatibility with mating parts. Check the package contents to ensure completeness. Read all instructions thoroughly before beginning.
- Position and Clean the Cable
Position the cable in its final assembled location, ensuring enough slack for elbow removal. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4 inches (45mm) from the center line of the mating product. Clean the outer jacket of the cable for a distance of 24 inches (610mm).
- Prepare the Cable End
Follow the specific cable preparation steps for your cable type (e.g., UNISHIELD, Lead Sheath, Jacketed, or Non-Jacketed). Remove the outer jacket (if applicable) and prepare the cable according to the specified dimensions for insulation, semi-con shield, and tape marker (e.g., 10-3/8", 11-3/8", 13-5/8" from the cable end).
- Install the Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Expose the Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Be careful not to cut or nick the cable adapter or the conductor. The exposed conductor length must be between 4-3/8 inches to 4-3/4 inches (111mm-121mm). If not, redo the assembly.
- Crimp the Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the 'Check Dimension' before crimping; it should be less than 7 inches (178mm). Crimp the compression lug following the instructions supplied with the lug. Wipe all excess inhibitor from the lug and cable adapter surface. The distance from the end of the compression lug to the cable adapter after crimping should be between 6-7/8 inches to 7-5/8 inches (175mm-194mm).
- Install the Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Prepare Mating Products
WARNING: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove any protective caps from the elbow and the mating part. Hand tighten the threaded stud supplied with the elbow into the mating part if the mating part is not already equipped with a stud. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.
- Connect Opposite Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert the mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to the instructions supplied with that specific mating part.
- Install Insulating Plug (if used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps into place.
- Ground the Cable Shield
Insert one end of a grounding wire (with ampacity at least equivalent to No. 14 AWG Copper) through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow instructions supplied with any grounding device or use an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test (Optional but Recommended)
CAUTION: When constructing 600amp L-Kits, tighten each component to specified torque per plug connector instructions. To test for voltage using the integral capacitance test point: 1. Remove the test point cap with a hotstick, peeling it off at an angle. 2. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device made for capacitive test points and follow its manufacturer’s directions. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means, as contamination or incorrect equipment can cause false readings. 3. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.