ABB Installation Products 69TCT234143PBNN 69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 3, Connection…
UPC: 783786963898
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Class 1 termination for cable systems rated through 69kV
- Conforms to IEC-840 and IEEE-48 standards
- Accommodates insulation diameters up to 86.4mm (3.400")
- Supports conductor sizes from 90mm² (4/0) to 1700mm² (3500 kcmil)
- Durable molded EPDM elastomer housing with non-tracking properties
Specifications
Application | Cable Terminations, 69kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | 1.221 to 1.275 in |
Connection Type | 4 Hole NEMA |
Earthing | Products Includes Their Own Grounding System |
Material | Aluminum |
Mounting | No Bracket Required |
Nema Rating | 4 Hole NEMA |
Number Of Terminals | (1) Single Phase |
Series | 69TCT |
Size | Size 3 |
Special Features | Molded EPDM Elastomer Housing is Durable under Severe Envoronmental Conditions. Lightweight and easy to Handle |
Standard | IEEE 48 and IEC-840 |
Type | Cable Termination |
Voltage Rating | 69 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

69TCT302233PNAN
69kV, Transmission Cable Terminator, Base and Two Top Module, Housing Size 0 with Bore Diameter 1.35 inch with Insulation Range of 1.45 to 1.7 inch, Connection Type 2 - 2 Hole NEMA, Connector Type - Copper, Conductor Size Code 33P: 0.781 - 0.815 inch, Metallic Screen Kit - Not Required, Armor Kit - Jacketing Tape and Mastic, No Bracket Required
69TCT312233PAAN
69kV, Transmission Cable Terminator, Base and Two Top Module, Housing Size 1, Connection Type 2 - 2 Hole NEMA, Connector Type - Copper, Conductor Size Code 33P, Metallic Screen Kit - Flat Braid, Armour Kit - Jacketing Tape and Mastic, No Bracket Required
69TCT23N246PAAN
69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 3, Connection Type - None, Connector Type - Copper, Conductor Size Code 46P, Metallic Screen Kit - Flat Braid, Armour Kit - Jacketing Tape and Mastic, No Bracket Required
69TCT234140PAAN
69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 3, Connection Type 4 - 4 Hole NEMA, Connector Type - Aluminum, Conductor Size Code 40P, Metallic Screen Kit - Flat Braid, Armour Kit - Jacketing Tape and Mastic, No Bracket Required
R2T28M2-H0240
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .84 inch - 1.38 inch, Connector Type - Tinned Aluminum 1-Hole Spade #2-500 kcmil, Conductor Code - 240 -Stranded or Compressed 1/0 Compact or Solid 2/0.
R2IT15M4-N2410
Indoor Ranger2 Cable Termination. 15kV, Cable Type - Tape Shield/Wire Shield/UniShield. Insulation Range - 1.30 inch - 2.10 inch. Copper 2-Hole Spade #2-1250 kcmil, Conductor 1000 Stranded/Compressed
R2IT15M1N2250
Ranger2 Termination, Indoor, 15kv, Cable Type - Tape Shield/WireShield/UniShield, Insulation Range - .64 ich - 1.12 inch (16mm-28mm), Connector Type - N2 - Copper 2-Hole Spade #2-1250kcmil, Conductor Sizes 2/0 Stranded/Compressed or 3/0 Compact/Solid, No Cable Mounting Bracket
R2T35J4-N0300
Ranger2 Termination for 35KV outdoor application, cable insulation diameter 1.30 - 2.10 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2 through 1250 kcmil. Conductor Code 300 - 350 kcmil Stranded/Compressed or 400 kcmil Compact/Solid.Frequently Asked Questions
How can I order the 69TCT Terminator?
To order, provide cable cut sheet information and contact Thomas & Betts at 901-252-5000.
What items are included in the 69TCT Terminator kit?
Each kit includes one TCT Terminator, an instruction sheet, a conductive paint package, and two mastic tapes.
How long does it take to install the 69TCT Terminator?
Installation can be accomplished in 45 minutes after cable preparation, using the Elastimold TCJ-ATK-U Universal Assembly Tool.
Can the 69TCT Terminator be installed without a crane?
Yes, it can be assembled horizontally on the ground and then raised to the installation position without a crane.
What cable types and sizes are compatible with the 69TCT Terminator?
It is designed for solid dielectric cables with insulation diameters up to 3.400 inches and accommodates conductor sizes from 90mm2 (4/0) to 1700mm2 (3500 kcmil).
What is the application of the 69TCT Terminator?
The 69TCT Terminator provides a Class 1 termination for cable systems rated through 69kV class.
What is the maximum working voltage of the 69TCT Terminator?
The maximum working voltage for the 69TCT Terminator is 72.5 kV.
What is the nominal voltage for the 69TCT Terminator?
The nominal voltage for the 69TCT Terminator is 40kV/59kV.
What items are included in the 69TCT Terminator kit?
Each kit includes one TCT Terminator, an instruction sheet, a conductive paint package, and two mastic tapes.
What is the nominal voltage for the 69TCT Terminator?
The nominal voltage for the 69TCT Terminator is 40kV/59kV.
How to Install the ELASTIMOLD TCT Transmission Cable Termination
This guide provides step-by-step instructions for the safe and proper installation of the ELASTIMOLD TCT outdoor transmission cable termination, including cable preparation, component assembly, and final mounting.
Estimated time: 2h
Tools needed:
Screwdriver, Wire strippers, Cable knife, Hose clamp, Cable cleaner, Wirebrush, Crimping tool, Heat gun, Soldering iron, Measuring tape
Supplies needed:
ELASTIMOLD TCT kit (includes termination components, paint, lubricant, mastic, tape), Vinyl tape marker, Cable clamp, Winch assembly, Adapter plates, Housing clamp, Mounting hardware (customer supplied), System ground connection
- De-energize Apparatus and Review Instructions
DANGER: Ensure all apparatus is de-energized before beginning installation or removal. This product must be installed only by competent personnel trained in high voltage electrical equipment safety practices. Read all instructions completely before starting and ensure all parts are complete and undamaged.
- Straighten and Square Cut Cable
Straighten the cable and place it in its final position, using the spade contact as a guide. Square cut the cable end and note the depth of the spade contact hole (X).
- Remove Outer Jacket and Slide Heat Shrink Sleeve
Carefully remove the outer jacket material to a distance of 45.5 inches (111.6 cm) to expose the cable shield. Slide the heat shrink sleeve onto the cable, away from the exposed shield.
- Remove Cable Shield
Remove the cable shield to a distance of 43.5 inches (110.5 cm) from the end of the cable.
- Remove Non-Metallic Screen and Chamfer Edge
Remove the non-metallic screen to a distance of 40 inches (101.5 cm) from the end of the conductor. DO NOT cut or nick the exposed insulation. Chamfer the non-metallic screen edge for a minimum of 1/2 inch (1.5 cm).
- Square Cut and Chamfer Cable Insulation
Using a hose clamp as a guide, square cut the cable insulation at a distance of X+1 inch from the end of the conductor, being careful not to nick the conductor. Remove the hose clamp. Sand out all nicks and abrasions on the extruded non-metallic screen chamfer and cable insulation. Chamfer the edge of the cable insulation for approximately 3 inches (7.5 cm).
- Clean Insulation and Apply Semi-Conductive Paint
Using cable cleaner, clean the cable insulation and extruded non-metallic screen, cleaning toward the outer jacket. Place a vinyl tape marker on the cable insulation surface at 39.5 inches (100.5 cm) from the conductor end. Stir and paint the exposed insulation and 1 inch (2.5 cm) minimum of the extruded non-metallic screen with supplied semi-conductive paint. Remove the vinyl tape within 5 to 15 minutes, ensuring a smooth, square paint edge. Allow paint 60 minutes to dry.
- Place Vinyl Tape Marker on Shield
Place a vinyl tape marker onto the cable non-metallic shield 2 inches (5 cm) from the edge of the paint.
- Assemble Cable Clamp and Winch Assembly
Assemble the cable clamp at least 55 inches (140 cm) back from the conductor and tighten securely. Place the winch assembly in front of the cable clamp and attach stationary hooks to the cable clamp. Attach adapter plates to the housing clamp with supplied bolts and assemble the housing clamp around the terminator base section. Extend steel cables on the winch assembly and hook them to the housing clamp. Thoroughly lubricate the cable in the specified area and direction with the supplied lubricant.
- Install Terminator Base and Module Sections
Assemble the terminator base section on the cable approximately 12 inches from the end. Release tension on each steel cable, extend them, and the housing clamp. Position the terminator module section in the housing clamp. Install until units overlap and continue assembling mated units until the terminator base section is flush with the tape marker. Remove the winch assembly, housing clamp, adapter plate, and cable clamp.
- Prepare Conductor and Crimp Spade Contact
Remove the tape marker on the insulation shield. Remove the cut section of insulation on the cable to expose the conductor. Wirebrush the conductor immediately and insert it into the spade contact. Crimp the connector according to the enclosed crimping instructions, starting at the crimp line and working outward. Remove any excess inhibitor.
- Apply Mastic Layers
Apply two layers of mastic: one at the end of the stress cone and one 2 inches (5 cm) back from the end of the cable jacket.
- Install Grounding Components and Heat Shrink Sleeve
Install the scintillation ring and #12 AWG copper drain wire. Solder the flat braid and the #12 drain wire to the shield. Apply a second layer of mastic over the drain wire at the base of the stress cone, and a second layer over the flat braid on the cable jacket. Slide the heat shrink sleeve up to the grounding eye of the terminator base. Apply heat to the sleeve, starting in the middle and working toward each end until mastic sealer squeezes from the ends. Connect the flat braid to the system ground.
- Seal Crimp Connector and Apply Silicone Tape
Seal the cable end with mastic tape between the contact and cable insulation. Apply two half-lapped layers of silicone tape, covering the crimp connector, mastic tape, and the upper portion of the terminator skirt.
- Mount Terminated Cables to Supporting Structure
Mount the terminated cables to a supporting structure, ensuring a minimum clearance of 4.0 inches (10 cm) between the terminator stress cone base and the supporting structure. Ensure installation complies with all user, local, and national work rules.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.