ABB - Installation Products 656CETP-M0380 - 15kV, 600 Amp Combo T, carries current. Combo Elbow with bus, stud and cable adapter, lug and insulated cap kit. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.

ABB Installation Products 656CETP-M0380 15kV, 600 Amp Combo T, carries current. Combo Elbow with bus, stud and cable adapter…

UPC: 075114125253


Documents & Media
BrochureInstallation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB 656CETP-M0380 Combo Elbow T is a deadbreak, loadbreak separable connector engineered for 15kV medium-voltage distribution networks. This integrated assembly combines a bus, 650SA stud, cable adapter, aluminum compression lug, and insulated cap kit into a single unit, eliminating the need for multiple components and reducing installation complexity. The connector is rated for 600A continuous current and supports cable insulation diameters from 1.370" to 1.630", accommodating compressed stranded conductors from 700/750 kcmil to compacted solid conductors up to 900 kcmil. The design features IEEE 386 color-coded PBT interfaces—red for 15kV reducing tap—to improve visibility, seating indication, and mating component alignment while preventing like-material sticking for easier removal. The internal hex broach ensures proper installation torque, and the short stack height of 2.67 inches enables installation in compact cabinets and tight spaces. The 25kV reducing tap variant includes vents to prevent partial-vacuum flashover. This connector is ideal for switchgear, transformers, and cable terminations where reliability and space efficiency are critical. The aluminum compression lug minimizes resistance, reducing heat buildup and enhancing system efficiency in utility, industrial, and commercial power distribution applications.
  • 15kV, 600A deadbreak loadbreak separable connector
  • Supports cable insulation diameters: 1.370" to 1.630"
  • Accommodates conductors: 700/750 kcmil (compressed stranded) to 900 kcmil (compacted solid)
  • IEEE 386 color-coded PBT interfaces (red for 15kV) for improved alignment and removal
  • Short stack height: 2.67 inches for compact installation

Specifications

Amperage Rating
600 A
Application
600 Amps, 15kV Connector
Color
Black
Conductor Range
700 to 750 kcmil , 900 kcmil
Connection Type
Compression Lug
Current Rating
600 A
Environmental Conditions
All Weather Conditions
Insulation
True
Material
Aluminum
Material
Housing - EPDM-Rubber
Series
656CETP
Size
Cable Insulation Diameter 1.370 inch to 1.630 inch
Size
1.370 inch to 1.630 inch
Special Features
Reducing Tap Plug with Stud, Cable Adapter, and Lug. Test Point
Standard
ANSI/IEEE Standard 386
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
ComboT Elbow
Voltage Rating
15 kV
Voltage Rating
15kV
Width
13.31 in
Width
338.074 mm
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Test and Ground Connector Kit, Insulated Cap. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size Compressed Stranded 700/750 kcmil or Compacted Solid 900 kcmil.

656ETP-M0380-DRG

600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Test and Ground Connector Kit, Insulated Cap. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size Compressed Stranded 700/750 kcmil or Compacted Solid 900 kcmil.
Single cable clamp 150-300mm2 for power terminal type 5

45000034

Single cable clamp 150-300mm2 for power terminal type 5
15kV, 600 Amp Combo T, carries current. Combo Elbow with bus, stud and cable adapter, lug and insulated cap kit. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.

656CETP-M0380-DRG

15kV, 600 Amp Combo T, carries current. Combo Elbow with bus, stud and cable adapter, lug and insulated cap kit. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
15kV, 600 Amp Combo T, carries current. Combo Elbow with bus, stud and cable adapter, lug and insulated cap kit. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.

656CETP-L0330

15kV, 600 Amp Combo T, carries current. Combo Elbow with bus, stud and cable adapter, lug and insulated cap kit. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
15kV, 600 Series ComboT Elbow with 200 Amp Reducing Tap Plug, Stud, Cable Adapter and Lug Kit with Test Point and Seal. Cable Insulation Diameter 1.180 - 1.465 inches (30.0-37.2mm). Aluminum Compression Lug. Conductor Size 330 - 500 kcmil Stranded/Compressed or 600 kcmil Solid/Compact. Kit Includes Elbow Connector Housing, Stud, Lug, Tube of Lubricant, Cable Adapter, Crimp Chart and Installation Instructions.

656CETP-L0330-S

15kV, 600 Series ComboT Elbow with 200 Amp Reducing Tap Plug, Stud, Cable Adapter and Lug Kit with Test Point and Seal. Cable Insulation Diameter 1.180 - 1.465 inches (30.0-37.2mm). Aluminum Compression Lug. Conductor Size 330 - 500 kcmil Stranded/Compressed or 600 kcmil Solid/Compact. Kit Includes Elbow Connector Housing, Stud, Lug, Tube of Lubricant, Cable Adapter, Crimp Chart and Installation Instructions.
15kV, 600 Amp Combo T, carries current. Combo Elbow with bus, stud and cable adapter, lug and insulated cap kit. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400.

656CETP-M0360-DRG

15kV, 600 Amp Combo T, carries current. Combo Elbow with bus, stud and cable adapter, lug and insulated cap kit. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400.
15kV, 600 Amp Combo T. Combo Elbow with bus, stud and cable adapter, lug and insulated cap kit. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size Compressed Stranded 500 kcmil or Compacted Solid 600 kcmil. Includes Insulated Cap.

656CETP-L0330-DRG

15kV, 600 Amp Combo T. Combo Elbow with bus, stud and cable adapter, lug and insulated cap kit. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size Compressed Stranded 500 kcmil or Compacted Solid 600 kcmil. Includes Insulated Cap.
15kV, 600 Amp Combo T, carries current. Combo Elbow with bus, stud and cable adapter, lug and insulated cap kit. Cable Insulation Diameter 1.090 inch to 1.310 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.

656CETP-K5330-SG3

15kV, 600 Amp Combo T, carries current. Combo Elbow with bus, stud and cable adapter, lug and insulated cap kit. Cable Insulation Diameter 1.090 inch to 1.310 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.

Frequently Asked Questions

What voltage rating does the 656CETP-M0380 support?

The connector is rated for 15 kilovolts (kV) maximum operating voltage.

What is the maximum current rating of this connector?

This connector supports a continuous current rating of 600 Amperes.

What cable insulation diameters does this connector fit?

The connector accommodates cable insulation diameters from 1.370 inch to 1.630 inch.

Is this connector suitable for medium-voltage applications?

Yes, the 656CETP-M0380 is designed for medium-voltage distribution systems.

What conductor sizes are compatible with this connector?

The aluminum compression lug fits compressed stranded conductors sized 700/750 kcmil or compacted solid 900 kcmil.

How to Install 656CETP Deadbreak Elbow Connectors

This guide provides step-by-step instructions for the safe and proper installation of 656CETP Deadbreak Elbow Connectors, including cable preparation, lug crimping, and final assembly to high voltage apparatus.

Estimated time: 1h 30m

Tools needed:

Wire strippers, Crimping tool, 600AT or 600ATM assembly tool, Hotstick, Suitable voltage sensing device, Wire brush, Measuring tape or ruler, Utility knife

Supplies needed:

656CETP Elbow Connector kit (Elbow, Cable Adapter, Compression Lug, Lubricant), Cable (appropriate type), Vinyl plastic tape, Tape retainer (if applicable), Tape marker (if applicable), Ground wire (at least No. 14 AWG Copper), Suitable ground connector, Waterproofing material for cable jacket, Silicone grease, HV insulated cap(s) or connector(s), Mating product or apparatus bushing, Bails (for 200A deadbreak connectors)

  1. Prioritize Safety and Inspect Components

    DANGER: Ensure all apparatus is de-energized before beginning installation or removal of any parts. Verify that all components are undamaged, correctly rated, and compatible with mating parts. This product must be installed only by competent personnel trained in high voltage electrical safety practices. Remove any protective shipping covers and replace with appropriate HV insulated caps or connectors before energizing or submerging the circuit.

  2. Position and Prepare Cable

    Position the cable in its final assembled location, ensuring sufficient slack for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent-back concentric neutral wires.

  3. Prepare Cable Jacket and Shield

    Remove the cable's outer jacket to the specified dimension. Fold back shield wires. Depending on the cable type (e.g., flat metallic tape, fabric tape, longitudinally corrugated, semi-con shield), remove the shield and secure it with vinyl plastic tape, or install tape retainers and markers as indicated in the product documentation. Do not cut or nick the cable insulation during this process. If using UNISHIELD® or lead sheath cable, refer to the 10TL cable shield adapter instructions.

  4. Prepare Cable Insulation and Conductor

    Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker. Carefully remove the protruding cable insulation, cutting it even with the end of the cable adapter. Ensure the exposed conductor length is 4 3/8 to 4 11/16 inches (111mm-119mm). Do not cut or nick the cable adapter or conductor.

  5. Install and Crimp Compression Lug

    For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the lug. Measure the 'Check Dimension' before crimping; it must be less than 6 1/2 inches (165mm). Crimp the compression lug according to the instructions supplied with the lug. After crimping, wipe off all excess inhibitor from the lug and cable adapter surface. The distance from the end of the compression lug to the cable adapter should be 6 1/2 to 7 1/4 inches (165mm-184mm).

  6. Install Elbow onto Cable Adapter

    Lubricate the cable adapter and the inside of the elbow's cable entrance with the supplied lubricant. Install the elbow onto the cable adapter until it cannot advance further. Verify that the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.

  7. Prepare Mating Product and Install Stud

    DANGER: Never connect or disconnect mating products while energized, and do not energize while disconnected. Remove protective caps from both the elbow and the mating part. Install the stud into the apparatus by hand until it is fully seated. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring all surfaces remain clean.

  8. Assemble Elbow to Mating Product

    Push the elbow onto the mating part. Engage the hex broach of the contact assembly with the appropriate assembly tool (600AT for products dated Sept 30, 2013 or earlier, or 600ATM for products dated Oct 1, 2013 or later). Insert the contact assembly into the elbow interface to engage the stud. For 600AT, torque the contact assembly until the torque limiter ratchets (19 to 25 foot-pounds). For 600ATM, tighten to 50-60 foot-pounds, but DO NOT EXCEED 60 foot-pounds torque.

  9. Ground the Connector and Waterproof Jacket

    Insert one end of a ground wire, with ampacity at least equivalent to No. 14 AWG Copper, through the grounding eye and twist to form a small loop without damaging the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow instructions supplied with any grounding device or use an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.

  10. Verify Seating and Perform Voltage Test (Optional)

    Confirm complete assembly by ensuring no portion of the colored interface sleeve is visible when viewed from the side. For 656CETP, the integral capacitance test point can be used to check if the circuit is energized. Remove the test point cap with a hotstick, peeling it off at an angle. WARNING: This is a capacitance device, not directly connected to the conductor. Use a suitable sensing device designed for capacitive test points and follow its manufacturer's directions. Contamination or incorrect equipment can cause false readings; always treat the elbow as energized until 'no voltage' is confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone grease and replace it on the test point.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.