ABB Installation Products 655LRTP-K0330-DRG 600 Amp, 15KV, Stick Op Connector Kit, Fixed Bolt, Insulating Cap, Stick Op Load Break…
UPC: 783786398942
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp continuous current rating with 25kA symmetrical momentary rating
- 15kV maximum phase-to-ground operating voltage; 95kV BIL impulse withstand
- Stick-Op design enables safe load-break operations without cable movement
- Supports cable insulation diameters from 1.090 inch to 1.310 inch
- Includes aluminum compression lug, elbow housing, cable adapter, and insulating cap
Specifications
Amperage Rating | 600 to 200 A |
Application | Connect 600 Amp interface to 200 Amp Loadbreak Tap |
Color | Red |
Color | Black |
Conductor Range | 500 kcmil , 600 kcmil |
Connection Type | Compression Lug |
Current Rating | 600 A |
Enclosure | Yes, EPDM Rubber |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Mounting Type | Fixed Bolt |
Series | 600 Series |
Size | 1.090 inch to 1.310 inch |
Special Features | Reducing Tap Plug 600 to 200 Amps. Provides an External Visible Break by Hotstick Removal of the Elbow |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Stick Op Reducing Tap Plug Connector |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 8.5000 L |
Package Weight (Metric) | 3.8560 kg |

K656YDSR-M0330
15-25kV 600 Series Deadbreak Direct Test Straight Receptacle Elbow with Test Point, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
K655LRTP-L0330-DRG
600 Amp, 25kV, Stick-Op Connector Kit with Insulated Cap. Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
K655LRTP-L0300-DRG
600 Amp Elbow Connector, Stick Op Connector Kit, 25KV, Dead Break, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 350 /Solid 400 /mmSquared 185.
655LRTP-M0380-DRG
600 Amp, 15KV, Stick Op Connector Kit, Fixed Bolt, Insulating Cap, Stick Op Load Break Reducing Tap Plug, Elbow Housing, Cable Adapter and Threaded Lug, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
655LRTP-H0270-DRG
600 Amp, 15kV, Deadbreak Stick-Op Connector Kit, With Insulated Cap. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size 4/0 Compressed/Stranded or 250 kcmil Compacted/Solid or mmSquared Compact 125.
K655LRTP-H0240-DRG
600 Amp, 25kV, Stick-Op Connector Kit with Insulated Cap. Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0.
655LRTP-L0330
600 Amp, 15kV, Deadbreak Stick-Op Connector Kit, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.Frequently Asked Questions
What is the Corona Extinction voltage?
The Corona Extinction voltage is 11 kV AC at 3pC sensitivity.
What is the voltage rating of this connector?
The connector has a 15kV voltage class with an 8.3 kV maximum phase-to-ground operating voltage and 15.0 kV maximum phase-to-phase.
What is the continuous current rating?
The connector has a continuous current rating of 600 Amp.
What materials are used in the connector?
The connector is constructed of EPDM molded rubber and features an all copper current path.
What industry standards does this connector meet?
The connector meets ANSI/IEEE Standard 386, Latest Revision.
What is the impulse withstand rating?
The impulse withstand rating is 95.0kV BIL, based on a 1.2 x 50 microsecond wave.
What type of elbow is compatible with this connector?
The connector kit mates with a 600 Amp elbow interface.
What is the load break tap rating?
The connector provides a 200 Amp load break tap.
What is the momentary current rating?
The momentary current rating is 25kA Symmetrical for 10 Cycles.
What is the AC one-minute withstand voltage?
The AC one-minute withstand voltage for this connector is 34 kV.
How to Install and Remove the ELASTIMOLD 160/167DRG Insulated Cap
This guide provides step-by-step instructions for the safe installation and removal of the ELASTIMOLD 160DRG and 167DRG insulated caps with ground lead on 15kV class loadbreak bushing interfaces.
Estimated time: 15m
Tools needed:
Insulated hotstick
Supplies needed:
ELASTIMOLD 160DRG/167DRG Insulated Cap with Ground Lead, ELASTIMOLD Approved Lubricant
- Connect Electrostatic Grounding Wire
Before beginning, ensure all apparatus is de-energized. Connect the free end of the insulated cap's electrostatic grounding wire to the system ground. Leave sufficient slack for hot-stick operation and ensure the wire is trained not to contact the bushing interface during operation. WARNING: If the ground lead disconnects during operation, do not attempt to reattach without first pulling the insulated cap off the bushing with a hotstick.
- Prepare and Lubricate Insulated Cap
Remove the protective cover from the insulated cap. Apply only the supplied lubricant or ELASTIMOLD approved lubricants to the cap's internal mating surface. Do not substitute other lubricants, as they may be harmful. Keep the internal mating surface clean and free from dirt and grime. Always replace the protective cover when the cap is not in use.
- Install Insulated Cap onto Loadbreak Bushing
Firmly attach an insulated hotstick to the pulling eye of the insulated cap. Carefully insert the male contact of the insulated cap into the loadbreak bushing. Push the cap home with a fast, firm, and straight motion until it is fully mated and the locking ring is seated. Detach the hotstick from the insulated cap. Ensure all apparatus remains de-energized during this installation.
- Remove Insulated Cap
To remove the insulated cap, first ensure the circuit is de-energized if it's a deadbreak connector, or use appropriate live-line tools for loadbreak. Attach an insulated hotstick to the pulling eye. Before pulling, rotate the insulated cap clockwise slightly while it is in the mated position to break surface friction. Pull the cap off with a fast, firm, straight motion. Finally, remove the electrostatic grounding wire from the system ground and replace the protective cover on the insulated cap to keep its internal surface clean.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.