Overview
- 600 Amp current rating
- 15kV voltage rating
- Deadbreak stick-operated connector
- Accommodates cable insulation diameter: 1.180" - 1.465"
- Aluminum compression lug for conductor connection
Specifications
Amperage Rating | 600 to 200 A |
Application | Connect 600 Amp interface to 200 Amp Loadbreak Tap |
Color | Black |
Conductor Range | 500 kcmil , 600 kcmil |
Connection Type | Deadbreak Stick-Op |
Current Rating | 600 A |
Enclosure | Yes, EPDM Rubber |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Material | Aluminum |
Series | 655LRTP |
Size | Cable Insulation Diameter 1.180 inch to 1.465 inch |
Special Features | Reducing Tap Plug 600 to 200 Amps. Provides an External Visible Break by Hotstick Removal of the Elbow |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Stick Op Reducing Tap Plug Connector |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 8.0000 L |
Package Weight (Metric) | 3.6290 kg |

656LRTP-L0330
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Stick-OP Elbow Connector Kit. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug.
655LRTP-K0320
600 Amp, 15KV, Stick Op Connector Kit, Fixed Bolt, Insulating Cap, Stick Op Load Break Reducing Tap Plug, Elbow Housing, Cable Adapter and Threaded Lug, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550.
655LRTP-J0270
600 Amp, 15kV, Deadbreak Stick-Op Connector Kit, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.
K655LRTP-L0380-DRG
600 Amp Elbow Connector, Stick Op Connector Kit, 25KV, Dead Break, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 700/750, Solid 900.
655LRTP-J0320
600 Amp, 15kV, Deadbreak Stick-Op Connector Kit, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550.
655LRTP-H0290
600 Amp, 15kV, Deadbreak Stick-Op Connector Kit, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 300 /Compacted Solid 350 /mmSquared Compact 150.
655LRTP-L0330-DRG-S
600 Amp, 15KV, Stick Op Connector Kit, Fixed Bolt, Insulating Cap, Stick Op Load Break Reducing Tap Plug, Elbow Housing, Cable Adapter and Threaded Lug, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. Cold-Shrinkable Jacket Seal Included.Frequently Asked Questions
What is the maximum operating voltage?
The maximum phase-to-ground operating voltage is 8.3 kV, and the maximum phase-to-phase is 15.0 kV.
What are the current ratings for the connector?
The connector kit has a 600/200 Amp rated loadbreak and a 600 Amp continuous current rating.
What is the voltage rating of this connector kit?
The 655LRTP-W0X connector kit is rated for a 15kV voltage class.
What standards does this connector meet?
The connector kit meets ANSI/IEEE Standard 386, Latest Revision.
What is the momentary current rating?
The momentary current rating is 25kA Symmetrical for 10 Cycles.
What is the DC 15-minute withstand voltage?
The DC 15-minute withstand voltage for the connector is 53 kV.
What is the AC one-minute withstand voltage?
The AC one-minute withstand voltage for the connector is 34 kV.
What is the impulse withstand rating (BIL)?
The impulse withstand (BIL) rating for the connector kit is 95.0kV.
What does the 655LRTP-W0X kit connect to?
The kit mates with a 600 Amp elbow interface and provides a 200 Amp load break tap.
What is the AC one-minute withstand voltage?
The AC one-minute withstand voltage for the connector is 34 kV.
How to Install 655/675LR and K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 600-ampere and 900-ampere deadbreak elbow connectors on 15kV and 25kV class systems, including cable preparation, lug crimping, and connection to mating apparatus.
Estimated time: 2h
Tools needed:
Screwdriver, Wire strippers, Wire brush, Crimping tool, Hotstick, Suitable sensing device, Torque wrench
Supplies needed:
655/675LR or K655/K675LR Elbow Connector, Cable Adapter, Compression Lug, Insulating Plug, Lubricant, Threaded Stud, Wire (minimum No. 14 AWG Copper), Suitable connector (for grounding), Silicone lubricant, HV insulated cap(s) or connector(s)
- Perform Initial Safety Checks and Inspection
DANGER: De-energize all apparatus completely before beginning installation or removal of any parts. Do not touch or move energized products in the work area. Inspect the package contents and all components for any damage, verify their rating, and ensure compatibility with mating parts. If the product was supplied with protective shipping covers, remove them and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit.
- Prepare the Cable
Assemble the cable in its final position, ensuring enough slack for adequate clearance. Unwind any concentric neutral wires if applicable. Cut the cable 1-3/4” (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24” (610mm) or up to the bent back concentric neutral wires. Remove the outer jacket (if present) and prepare the cable according to the specific cable type (e.g., non-jacketed, jacketed shield wires, etc.) as detailed in the product's instructions.
- Install the Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor and Crimp Compression Lug
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Ensure the length of the exposed conductor is between 4-1/4” and 4-9/16” (108mm-116mm). For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it. Measure the “Check Dimension” before crimping; it must be less than 6-3/8”. Crimp the compression lug following the instructions supplied with the lug. Wipe all excess inhibitor from the lug and cable adapter surface. Verify the distance from the end of the compression lug to the cable adapter is between 6-3/8” to 7-1/8” (162mm-181mm).
- Install the Elbow Connector
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker; reposition it if necessary. Remove the tape marker.
- Connect to Mating Products
DANGER: Do not connect or disconnect mating products while energized, and do not energize while disconnected. Remove protective caps from both the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud supplied with the elbow into the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant. Push the elbow onto the mating part, carefully aligning the hole in the compression lug with the stud on the mating part. If connecting to the opposite end of the elbow, clean and lubricate that mating part, insert it into the elbow, engage the threads, and hand tighten. Torque the mating part according to its specific instructions. If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow, pushing until it snaps into place.
- Ground the Cable Shield
Insert one end of a wire with ampacity at least equivalent to No. 14 AWG Copper through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. Ensure the shield of the cable is properly grounded, either through a dedicated grounding device or an alternate approved method. It is also recommended to waterproof the cable jacket at this point to prevent moisture from entering the cable.
- Perform Voltage Test
WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly. Use a suitable sensing device, specifically designed for separable connectors with capacitive test points, to determine if the cable is energized. Contamination, moisture, dirt, or incorrect equipment can provide a false “no voltage” indication. Treat the elbow as energized until the “no voltage” test point indication is confirmed by other means to prevent serious or fatal injury. After the voltage detection has been made, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.