ABB Installation Products 655LRTP-K0320 600 Amp, 15KV, Stick Op Connector Kit, Fixed Bolt, Insulating Cap, Stick Op Load Break…
UPC: 783786431960
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp, 15KV rating for medium-voltage applications
- Stick operated for safe and convenient connection
- Includes fixed bolt connector, insulating cap, and load break tap plug
- Elbow housing and threaded aluminum compression lug for cable termination
- Accommodates cable insulation diameters from 1.090" to 1.310"
Specifications
Amperage Rating | 600 to 200 A |
Application | Connect 600 Amp interface to 200 Amp Loadbreak Tap |
Color | Black |
Conductor Range | 450 kcmil , 500 to 550 kcmil |
Connection Type | Fixed Bolt |
Current Rating | 600 A |
Enclosure | Yes, EPDM Rubber |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Material | Aluminum |
Series | 655LRTP |
Size | Cable Insulation Diameter 1.090 inch to 1.310 inch |
Special Features | Reducing Tap Plug 600 to 200 Amps. Provides an External Visible Break by Hotstick Removal of the Elbow |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Stick Op Reducing Tap Plug Connector |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 0.0800 L |
Package Weight (Metric) | 0.0360 kg |

K656I-L0320
15-25kV 600 Series Deadbreak Separable Straight Joint Package (2-Way) with Test Point. Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size kcmil Compressed Stranded 450 /Solid 500/550.
655LRTP-J0270
600 Amp, 15kV, Deadbreak Stick-Op Connector Kit, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.
K655LRTP-L0380-DRG
600 Amp Elbow Connector, Stick Op Connector Kit, 25KV, Dead Break, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 700/750, Solid 900.
655LRTP-J0320
600 Amp, 15kV, Deadbreak Stick-Op Connector Kit, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550.
655LRTP-H0290
600 Amp, 15kV, Deadbreak Stick-Op Connector Kit, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 300 /Compacted Solid 350 /mmSquared Compact 150.
655LRTP-L0330-DRG-S
600 Amp, 15KV, Stick Op Connector Kit, Fixed Bolt, Insulating Cap, Stick Op Load Break Reducing Tap Plug, Elbow Housing, Cable Adapter and Threaded Lug, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. Cold-Shrinkable Jacket Seal Included.
675LRTP-G2220-DRG
900 Amp, DeadBreak, 15KV, Stick Op Elbow Kit, Cable Insulation Diameter 0.760 inch to 0.950 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62.Frequently Asked Questions
What is the voltage and current rating?
The connector is rated for 15kV and has a 600/200 Amp loadbreak rating.
What is the impulse withstand rating?
The impulse withstand rating is 95.0kV BIL (1.2 x 50 microsecond wave).
What connector material types are available?
Available connector material types are Aluminum (code 0), Copper (code 2), and Bi-metal (code 5).
What cable insulation diameters are supported?
Supported cable insulation diameters range from 0.42 inches to 2.12 inches, corresponding to specific letter codes.
How is the catalog number determined?
The catalog number is determined by selecting codes for cable insulation diameter, connector material type, and compression lug based on conductor size.
What is the AC and DC withstand voltage?
The connector has a 34 kV AC one-minute withstand and a 53 kV DC 15-minute withstand.
What is the continuous current rating?
The continuous current rating for the connector is 600 Amp.
What standards does this connector meet?
The connector meets ANSI/IEEE Standard 386, Latest Revision.
What is the maximum operating voltage?
The maximum operating voltage is 8.3 kV phase-to-ground and 15.0 kV phase-to-phase.
What does the 655LRTP-WOX kit connect to?
The kit mates with a 600 Amp elbow interface and provides a 200 Amp load break tap.
How to Install 655/675LR and K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 600-ampere or 900-ampere deadbreak elbow connectors on 15kV and 25kV class systems. Ensure all apparatus are de-energized before beginning installation.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool (per lug instructions), Wire brush (for aluminum conductors), Hotstick, Suitable sensing device for capacitive test points, Torque wrench (per mating part instructions)
Supplies needed:
655/675LR or K655/K675LR Deadbreak Elbow Connector kit (includes Elbow, Cable Adapter, Compression Lug, Insulating Plug, Lubricant, Stud Prepack), No. 14 AWG Copper wire (or equivalent) for grounding, Suitable connector for grounding wire, Silicone lubricant
- De-energize Apparatus and Prepare Cable
DANGER: All apparatus must be de-energized during installation or removal of parts. Assemble the cable in its final position with enough slack for elbow removal. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable a distance of 24 inches (610mm) or up to the bent back concentric neutral wires.
- Prepare Cable End
Remove the outer jacket (if applicable) and prepare the cable according to the specific cable type (e.g., non-jacketed concentric neutral, jacketed shield wires, flat metallic tape shield, fabric tape shield, or longitudinally corrugated shield) as shown in the product documentation, ensuring correct lengths for insulation, semi-con shield, and tape marker. Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, working toward the semi-con shield.
- Install Cable Adapter and Prepare Conductor
Install the cable adapter, small end first, until it is flush with the edge of the tape marker. Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of the exposed conductor should be between 4-1/4 inches and 4-9/16 inches (108mm-116mm). If not, redo the assembly.
- Install Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the 'Check Dimension' before crimping; it should be less than 6-3/8 inches. Crimp the compression lug following the crimping instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. The distance from the end of the compression lug to the cable adapter after crimping should be between 6-3/8 inches to 7-1/8 inches (162mm-181mm). If not, redo the assembly.
- Install Elbow and Prepare Mating Parts
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter is still flush with the tape marker; if not, reposition the cable adapter. Remove the tape marker. Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud supplied with the elbow into the mating part, if the mating part is not already equipped with a stud. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean.
- Connect Elbow to Mating Parts
WARNING: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Push the elbow onto the mating part, lining up the hole in the compression lug with the stud on the mating part. Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to the instructions supplied with that part. CAUTION: When constructing 600-amp L-Kits, ensure each component is tightened to the specified torque per instructions provided.
- Install Insulating Plug (If Applicable) and Ground Cable Shield
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow. Push down hard until the cap snaps into place. Insert one end of a piece of wire with ampacity at least equivalent to No. 14 AWG Copper through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The shield of the cable must be grounded according to the instructions supplied with the grounding device or by an alternate method if no device is used. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test
Remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the specific meter used. Test with a suitable sensing device, made for use with separable connectors manufactured with capacitive test points, to determine if the cable is energized. Contamination, moisture, dirt, or incorrect equipment can provide a false 'no voltage' indication. Treat the elbow as energized until the 'no voltage' test point indication is confirmed by other means to prevent serious or fatal injury. After voltage detection, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.