ABB Installation Products 655CETPN0410DRGS 600 Amp, 15kV, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Lug and…
UPC: 783786401925
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp current rating for high-capacity power distribution.
- 15kV voltage rating suitable for medium voltage applications.
- Combo T Elbow connection type for versatile termination.
- Aluminum construction for durability and conductivity.
- Accommodates cable insulation diameters from 1.515" to 1.780".
Specifications
Amperage Rating | 600 A |
Application | 600 Amps, 15kV Connector |
Color | Black |
Conductor Range | 1000 kcmil |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Special Features | Reducing Tap Plug with Stud, Cable Adapter, Lug and Insulated Cap |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | ComboT Elbow |
Voltage Rating | 15 kV |
Width | 13.31 in |
Width | 338.074 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K656CYP0410P0410P041
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, with 3 X ( Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000. )
655CETPM0380DRGS
600 Amp, 15kV, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Lug and Insulated Cap Kit, No Test Point, Aluminum, Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. With Shrink-Fit Jacket Seal Kit.
655CETPN0410DRG
600 Amp, 15kV, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Lug and Insulated Cap Kit, No Test Point, Aluminum, Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 1000.
655CETPM2380DRGS
600 Amp, 15kV, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Lug and Insulated Cap Kit, No Test Point, Copper, Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. With Shrink-Fit Jacket Seal Kit.
K656CETP
15/25kV, 600 Amp Base Aluminum, includes test point, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Lug and Insulated Cap Kit.
K655CETPL5270
15/25kV, 600 Amp, no test point, Combo T Elbow Reducing Plug with Stud, Cable Adapter, Lug and Insulated Cap Kit. Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.
162LR-C5190-SG3
15kV 200 Amp, Loadbreak Elbow Connector with Test Point, .805 inch - 1.060 Inch Cable Insulation Diameter, Conductor Size #4 Solid/Compact, Bi-Metal Compression Lug. SG3 - Cold-Shrinkable Seal with Copper Braid and Constant Force Spring.
756LR-L0270-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold-Shrinkable Jacket Seal Included.Frequently Asked Questions
What is the maximum conductor size supported by this tap plug?
This tap plug supports compressed stranded aluminum conductors up to 1000 kcmil.
What is the voltage rating of the ABB 655CETPN0410DRGS?
The ABB 655CETPN0410DRGS has a voltage rating of 15kV.
What is the current rating for this reducing tap plug kit?
The current rating for this reducing tap plug kit is 600 Amps.
What is the range of cable insulation diameters this kit accommodates?
This kit accommodates cable insulation diameters ranging from 1.515 inches to 1.780 inches.
Does this kit include a test point?
No, this specific model (655CETPN0410DRGS) does not include a test point.
What material is the ABB 655CETPN0410DRGS made from?
The ABB 655CETPN0410DRGS is made from aluminum.
What components are included in the 655CETPN0410DRGS kit?
The kit includes a cable adapter, a lug, an insulated cap, and a Shrink-Fit Jacket Seal Kit.
How to Install 655/656/675/676CETP Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 655/656/675/676CETP Deadbreak Elbow Connectors, including cable preparation, crimping, and connection to high voltage apparatus.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Wire brush (for aluminum conductor), 600ATM assembly tool (or 600AT for older products), Hotstick, Suitable voltage sensing device, Measuring tape
Supplies needed:
655/656/675/676CETP Elbow Connector kit (includes Elbow, Cable Adapter, Compression Lug, Lubricant), Vinyl plastic tape, Tape retainer (if applicable), Tape marker, No. 14 AWG Copper equivalent grounding wire, Suitable grounding connector, Silicone grease, HV insulated cap(s) or connector(s)
- Prepare for Installation and Ensure Safety
DANGER: De-energize all apparatus before installation or removal. Read all instructions, check package contents, and ensure components fit the cable and mating products. Have all required tools ready and maintain cleanliness. Remove any protective shipping covers and replace with appropriate HV insulated caps or connectors before energizing.
- Position Cable and Clean Outer Surface
Position the cable in its final assembled location with enough slack for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent-back concentric neutral wires.
- Prepare Cable Jacket and Shield
Remove the outer jacket to the specified dimension. Fold back shield wires. Depending on cable type, remove flat metallic tape shield (secure with vinyl plastic tape), fabric tape shield (install tape retainer and marker), or longitudinally corrugated shield (install tape marker). If using UNISHIELD® or lead sheath cable, refer to 10TL cable shield adapter instructions. Remove semi-con shield and install tape marker, ensuring not to cut or nick the cable insulation.
- Bevel Insulation and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation (working toward the semi-con shield) with the supplied lubricant. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Expose Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Be careful not to cut or nick the cable adapter or the conductor. The exposed conductor length should be 4-3/8 to 4-11/16 inches (111mm to 119mm). If not, redo the assembly.
- Crimp Compression Lug
Fully insert the conductor into the compression lug. If using an aluminum conductor, wire brush it immediately before insertion. Measure the 'Check Dimension' before crimping (must be less than 6-1/2 inches / 165mm). Crimp the compression lug according to the supplied crimping instructions. Wipe off any excess inhibitor. The distance from the end of the compression lug to the cable adapter after crimping should be 6-1/2 to 7-1/4 inches (165mm to 184mm). If not, redo the assembly.
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow cable entrance with the supplied lubricant. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker. If not, reposition the cable adapter. Remove the tape marker.
- Connect Elbow to Mating Apparatus
DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. Install the stud into the apparatus by hand until fully seated. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean.
- Torque Contact Assembly
Push the elbow onto the mating part. Using the 600ATM assembly tool (for products dated October 1, 2013, or later), engage the hex broach in the contact assembly. Insert the contact assembly into the elbow interface to engage the stud. Tighten the contact assembly to 50-60 foot-pounds torque. DO NOT EXCEED 60 FOOT-POUNDS TORQUE. (For products dated September 30, 2013, or earlier, use the 600AT tool and torque to 19-25 foot-pounds until it ratchets).
- Ground Cable Shield and Waterproof
Insert one end of a No. 14 AWG Copper equivalent wire through the grounding eye and twist to form a small loop, avoiding damage to the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded according to grounding device instructions or an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Install Loadbreak Interface (Optional)
Clean and lubricate the entire loadbreak interface and either a DR(G), ESA, GLR, or LR of the appropriate voltage class with the supplied or ELASTIMOLD® approved lubricant. Install the DR(G), ESA, GLR, or LR to the tap plug interface following the instructions supplied with those specific products.
- Verify Seating and Perform Voltage Test
Confirm complete assembly by ensuring no portion of the colored interface sleeve is visible when viewed from the side. For 656CETP models, remove the test point cap with a hotstick (peel off at an angle). WARNING: The voltage test point is a capacitance device; do not use conventional voltage measuring equipment. Use a suitable sensing device and follow its manufacturer's directions. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means. After testing, clean, lubricate the cap with silicone grease, and replace it.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.