ABB Installation Products 376LR-H5270 35kV 200 Amp, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.850…
UPC: 783786455218
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV, 200 Amp fully rated loadbreak elbow connector
- Accommodates cable insulation diameters 0.850"–1.050" (21.59–26.67 mm)
- Bi-metal compression lug for copper or aluminum conductors (AWG 4/0, solid 250, mm² 126.67)
- Integrated non-corrosive capacitive test point for safe voltage verification
- Fully shielded, submersible molded rubber housing with peroxide-cured EPDM materials
- Provisions for hot stick operation and ground wire connection
- Meets ANSI/IEEE Standard 386 with 150kV BIL and 200 Amp continuous/loadbreak ratings
Specifications
Amperage Rating | 200 A |
Application | 35 kv, 200 Amp |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Connection | Push-In |
Connection Type | Compression Lug |
Current Rating | 200 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Bi-Metal, EPDM Rubber |
Material | Housing - EPDM-Rubber |
Series | 376LR |
Size | Cable Insulation Diameter 0.850 inch to 1.050 inch |
Size | 0.850 inch to 1.050 inch (cable insulation diameter), AWG 4/0 /Solid 250 /mm² 126.67 |
Special Features | 35kV, 200 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for hot stick operation. Provision for ground wire connection. Non-Corrosive Capacitive Voltage Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 3.1000 L |
Package Weight (Metric) | 1.4060 kg |

375LR-L-2270
200 Amp, 35kV, Loadbreak Elbow Connector without Test Point, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Compression Lug, Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
167ELR-7495-5240-S
200 Amp, 15kV, Loadbreak Repair Elbow Connector without Test Point, Cable Insulation Diameter 0.740 inch to 0.950 inch. 200ECS Jacket Seal Included. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 3-1/4 inches in length. Includes 02509X long Bi-Metal Contact.
168ELR-7495-5230
200 Amp, 15kV, Loadbreak Repair Elbow Connector with Test Point, Cable Insulation Diameter 0.740 inch to 0.950 inch. Conductor Size #1 Stranded/Compressed or 1/0 Compact/Solid. Bi-Metal Compression Lug.
274RLR-J-5240
200 Amp, 25kV, Loadbreak Replacement Elbow Connector with Test Point, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact. Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
755LR-K0270-S
600 Amp, 35KV, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67. Cold-Shrinkable Jacket Seal Included.
168RLR-F-5210-S
200 Amp, 15kV, Loadbreak Replacement Elbow Connector with Test Point, Cable Insulation Diameter 0.640 inch to 0.820 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded #3/Solid #2/mmSquared 26.67. 200ECS Jacket Seal Included. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact.
168RLR-G-5230-S
200 Amp, 15kV, Loadbreak Replacement Elbow Connector with Test Point, Cable Insulation Diameter 0.760 inch to 0.950 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41. 200ECS Jacket Seal Included. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact.
168RLR-H5270-S
200 Amp, 15kV, Loadbreak Replacement Elbow Connector with Test Point, Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67. 200ECS Jacket Seal Included. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact.Frequently Asked Questions
What cable insulation diameters does it support?
The connector supports cable insulation diameters from 0.850 inch to 1.050 inch.
Does this connector include a test point?
Yes, the connector features an integrated test point for safe voltage verification.
Is this connector suitable for loadbreak operations?
Yes, the connector is designed for loadbreak operations, allowing safe connection and disconnection under load.
What is the maximum voltage rating for this connector?
The connector is rated for 35kV maximum operating voltage.
What is the current rating of the connector?
The connector has a continuous current rating of 200 Amps.
What conductor sizes are compatible with this connector?
The bi-metal compression lug supports AWG compressed stranded 4/0, solid 250, and mm² 126.67 conductor sizes.
How to Install 375LR/376LR Loadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of Elastimold 375LR and 376LR Loadbreak Elbow Connectors, including cable preparation, elbow assembly, neutral connection, and initial connection to a bushing. Always ensure apparatus is de-energized during installation.
Estimated time: 1h 30m
Tools needed:
Probe Wrench, Wire brush, Crimp tool, Hotstick, Suitable sensing device (for 376LR voltage test)
Supplies needed:
Elbow Connector Housing, Compression Lug, Probe, Lubricant (Do Not Substitute), Copper wire (No. 14 AWG / 2.5mm or equivalent), Appropriate connector (for neutral wires), Silicone grease (for 376LR test point cap)
- Train and Cut Cable
Train the cable as shown in the documentation to ease future operation, ensuring a minimum of 20 inches of cable extends beyond the end of the cable pad mount transformer. Cut the excess cable squarely at the center line of the bushing.
- Prepare Cable End
Unwrap and bind the concentric neutral wires 8-1/2 inches back from the end of the cable. Carefully remove the shield and insulation from the cable end, taking care not to nick the conductor. Ensure the cut is straight, smooth, and squared.
- Install Compression Lug
Wire brush the bare aluminum conductors immediately. Install the compression lug, rotating it to spread the inhibitor. Position the compression lug so its contact threaded hole aligns with the bushing bore. Crimp the lug according to the crimp chart packaged with the compression lug, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe any excessive inhibitor from the outside of the lug and cable.
- Finish Insulation Preparation
Remove the insulation shield as indicated by the cable cut back template. Bevel the insulation end a maximum of 1/8 inch. Thoroughly clean the insulation to remove all traces of conductive residue.
- Lubricate and Assemble Elbow Housing
Lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant; DO NOT SUBSTITUTE. Other lubricants may be harmful to this product or its mating product(s). Slide the elbow connector onto the cable using a back-and-forth twisting motion and wipe off all excess grease. Keep insulation clean of dirt and grime.
- Install Probe
Align the elbow with the compression lug's threaded hole. Thread the probe into the lug by hand, taking care not to cross-thread. The probe must turn freely for approximately four turns before becoming snug. Tighten the probe with the supplied wrench until the wrench bends.
- Connect Concentric Neutral
Using a separate No. 14 AWG (2.5mm) copper wire or equivalent, insert one end through the grounding eye on the elbow and twist it tight, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector, providing adequate slack in the wires for elbow operation.
- Connect Elbow to Bushing
LUBRICATE ONLY IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE-ENERGIZED. Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant. Securely fasten a hotstick to the loadbreak connector pulling eye. Insert the probe tip approximately 2 inches into the bushing, then immediately push the elbow home with a fast, firm, straight motion, applying sufficient force to engage the internal lock on the elbow connector and bushing interface.
- Perform Voltage Test (376LR Only)
For 376LR models, remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly in line. WARNING: The voltage test point is a capacitance device; do not use conventional voltage measuring equipment. Test with a suitable sensing device made for use with separable connectors manufactured with capacitive test points, following the manufacturer’s directions. After testing, clean and lubricate the inside surface of the cap with silicone grease and replace it tightly on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.