ABB Installation Products 376LR-H-5240 200 Amp, 35kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter…
UPC: 783786648733
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 200 Amp, 35kV-rated medium-voltage loadbreak connector
- Integrated test point for safe diagnostics without de-energizing circuits
- Accommodates cable insulation diameters from 0.850" to 1.050"
- Bi-metal compression lug supports 1/0-2/0 AWG (53.49 mm²) conductors
- Designed for underground distribution, substations, and industrial power networks
Specifications
Amperage Rating | 200 A |
Application | 35 kv, 200 Amp |
Color | Black |
Conductor Range | 1/0 STR/COMPR AWG , 2/0 SOL/COMPT AWG |
Connection | Push-In |
Current Rating | 200 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Bi-Metal Compression Lug |
Material | Housing - EPDM-Rubber |
Series | 376LR-H |
Size | Cable Insulation Diameter 0.850 inch to 1.050 inch |
Size | 0.850" - 1.050" |
Special Features | 35kV, 200 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for hot stick operation. Provision for ground wire connection. Non-Corrosive Capacitive Voltage Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 3.1000 L |
Package Weight (Metric) | 1.4060 kg |

375LR-H5240
200 Amp, 35kV, Loadbreak Elbow Connector without Test Point, Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
167RLR-G-5230
15kV 200 Amp, Loadbreak Replacement Elbow Connector, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Bi-Metal Contact. Cable Insulation Diameter 0.760 inch to 0.950 inch. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.
274RLR-H-5230
25kV 200 Amp, Loadbreak Replacement Elbow Connector with Test Point. Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.
376LR-K-5240
35kV 200 Amp, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 1.090 inch to 1.310 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
273RLR-H-5240
25kV 200 Amp, Loadbreak Replacement Elbow Connector, Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
376LR-L-5270
35kV 200 Amp, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 1.180 inch to 1.465 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
376LR-L-5240
200 Amp, 35kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 1.180 inch to 1.465 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
755LR-J0250
600 Amp, 35KV, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.Frequently Asked Questions
What is the voltage and current rating?
The 376LR is rated for 35kV voltage class, with a maximum phase-to-ground operating voltage of 21.1kV and a continuous and loadbreak current of 200 Amps.
What types of conductors are compatible with the lugs?
Bi-metal compression lugs with universal aluminum barrels are suitable for both copper or aluminum conductors. Copper lugs are for copper conductors only.
What is the purpose of the 376LR connector?
The 376LR provides a convenient method to connect or disconnect 35kV Class, 200 Amp distribution apparatus and systems.
What is the corona extinction voltage?
The corona extinction voltage for the 376LR is 26kV AC at 3p.C. sensitivity.
Does the 376LR have a voltage test point?
Yes, the 376LR is equipped with an integral, non-corrosive capacitive voltage test point.
What is the maximum phase-to-phase voltage?
The maximum phase-to-phase voltage rating for the 376LR is 36.6kV.
What is included in the 376LR elbow connector kit?
Each kit contains an elbow connector housing, a bi-metal compression lug, a probe, a probe wrench, a tube of lubricant, installation instructions, and a crimp chart.
Is the 376LR elbow submersible?
Yes, the 376LR features a fully shielded and fully submersible molded rubber housing.
What is the impulse withstand rating?
The impulse withstand rating is 150kV BIL (Basic Impulse Level) with a 1.2 x 50 microsecond wave.
What standards does the 376LR meet?
The 376LR meets ANSI/IEEE Standard 386, Latest Revision, for 35kV Voltage Class 1 Ø and 3 Ø.
How to Install the 375LR/376LR Loadbreak Elbow Connector
This guide provides step-by-step instructions for the safe and proper installation of the 375LR and 376LR Loadbreak Elbow Connectors, including cable preparation, elbow assembly, and initial connection to a de-energized bushing.
Estimated time: 1h 30m
Tools needed:
Probe Wrench, Crimp tool, Wire brush, Hotstick, Cable cutting tool, Wire strippers, Suitable sensing device
Supplies needed:
Elbow Connector Housing, Compression Lug, Probe, Lubricant (Do Not Substitute), Copper wire (No. 14 AWG / 2.5mm or equivalent), Appropriate connector (for grounding neutral wires), HV insulated cap(s) or connector(s), Silicone grease
- Prepare for Installation and Ensure Safety
Ensure all apparatus is de-energized. Verify package contents are complete and undamaged. Check all components for proper fit with cable and mating products. Thread the probe into the compression lug to check for resistance; replace if damaged. Gather all required tools and maintain a clean work area. If supplied with shipping covers, remove them and replace with appropriate HV insulated caps or connectors before energizing or submerging.
- Prepare the Cable for Connection
Train the cable to ease operation, ensuring at least 20 inches beyond the end of the cable pad mount transformer. Cut excess cable squarely at the centerline of the bushing. Unwrap and bind concentric neutral wires 8-1/2 inches back from the cable end. Remove the shield and insulation from the cable end, cutting squarely without nicking the conductor. Wire brush bare aluminum conductors and immediately install the compression lug, rotating to spread inhibitor. Align the compression lug's threaded hole with the bushing bore. Crimp the lug according to the crimp chart, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Wipe excessive inhibitor from the lug and cable. Remove the insulation shield and bevel the insulation end a maximum of 1/8 inch. Thoroughly clean the insulation to remove all traces of conductive residue.
- Assemble the Elbow Connector
Lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant ONLY; do not substitute. Keep insulation clean. Slide the elbow connector onto the cable with a back and forth twisting motion, then wipe off any excess grease. Align the elbow with the compression lug’s threaded hole. Thread the probe into the lug by hand, ensuring it turns freely for approximately four turns before becoming snug. Tighten the probe with a wrench until the wrench bends. For 376LR models, lubricate the test point cap and assemble it tightly.
- Connect the Concentric Neutral
Insert one end of a separate copper wire (No. 14 AWG / 2.5mm or equivalent) through the grounding eye on the elbow. Twist the wire tight, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector. Provide adequate slack in the neutral wires to allow for elbow operation.
- Connect the Elbow to the Bushing Plug (De-energized)
Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant ONLY if both the transformer and elbow are known to be DE-ENERGIZED. Remove the insulated cap from the bushing using a hotstick tool. Securely fasten a hotstick to the loadbreak connector pulling eye. With firm footing and positive control, insert the probe tip approximately 2 inches into the bushing. Immediately push the elbow home with a fast, firm, straight motion, applying sufficient force to engage the internal lock. DO NOT HOLD IN THE PARTIALLY INSERTED POSITION. DO NOT OPERATE BY HAND.
- Perform Voltage Test (376LR Only)
If using a 376LR connector, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device and NOT directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device, designed for capacitive test points, to determine if the cable is energized, following the manufacturer's directions. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone grease and replace it tightly.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.