
ABB Installation Products 35PCJ1P2400 35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786075164
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Single-piece molded rubber housing for simplified installation and reduced leak paths
- Accommodates 35kV cables with 1.725" to 1.935" insulation diameter and 1000 AWG solid copper conductor
- Meets IEEE Standard 404 with 200kV BIL impulse withstand and 69kV AC withstand ratings
- Fully shielded and submersible design withstands 500 lbs pull force for direct burial or vault installations
- Molded conductive shield with grounding eye for true deadfront construction and easy grounding
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 1000 kcmil |
Connection | Compression |
Insulation | Yes |
Material | Copper |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Series | 35PCJ1P |
Size | 15-3/4 inch long |
Size | 1.725 inch to 1.935 inch |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

35PCJ2P1410
35kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Conductor. Conductor Size AWG Stranded 1000.
25PCJ2H1220
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded #2/Solid #1.
15PCJ1K2310
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Conductor. Conductor Size AWG Solid 500.
28PCJ1K1290
28kV Power Cable Joint Style 1 with Single Piece Housing for Canada, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Solid 350.
35PCJ1P1380-S
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Conductor. Conductor Size AWG Stranded 750. Cold-Shrinkable Jacket Seal Included.
15PCJ1J2330
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.980 inch to 1.180 inch. Copper Conductor. Conductor Size AWG Stranded 500.
25PCJ2L1300-J1270
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded 350. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.
15PCJ1H2250
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Copper Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0.Frequently Asked Questions
How are connectors selected for different conductor types?
Aluminum compression connectors are for aluminum-to-aluminum or aluminum-to-copper. All-copper connectors are required for copper-to-copper connections.
Can copper connectors be used with aluminum conductors?
No, copper compression connectors are suitable for splicing copper conductors to copper conductors only. Do not use copper connectors on aluminum conductors.
What is the DC withstand during installation for 35 kV class?
For the 35 kV class, the DC withstand during installation is 100 kV.
What is the BIL impulse withstand for 35 kV class?
For the 35 kV class, the BIL impulse withstand (1.2 x 50 μsec. wave) is 300 kV.
What is the phase-to-ground voltage for 35 kV class?
For the 35 kV class, the phase-to-ground voltage is 20.2 kV.
What are the continuous and short-time current ratings?
The continuous current rating is equal to that of the cable rating. The short-time current rating is equal to the cable rating up to 35 kA.
What safety standards do PCJ power cable joints meet?
The shield design meets the IEEE 592 standard. The connectors meet ANSI 119.4 Class A and Class 3 ratings.
What pull force can the PCJ joint withstand?
The pin-and-socket interlock of the PCJ power cable joint is designed to withstand a pull force of up to 500 lb.
What cable types are compatible with PCJ power cable joints?
They are designed for UD cable with concentric neutral and extruded insulation shielding. They also work with fabric-tape shielded or lead-jacketed cables using proper adapters.
Where can PCJ power cable joints be installed?
PCJ power cable joints can be installed in direct-burial, underground vault, and even overhead applications. They provide a permanent, fully shielded, fully submersible splice.
How to Install the 15/25/35PCJ1 Series Straight Cable Joint
This guide provides detailed instructions for the permanent, fully shielded, and submersible installation of the 15/25/35PCJ1 series straight joint on wire shielded cables. Ensure all safety precautions are followed for high voltage electrical equipment.
Estimated time: 2h
Tools needed:
Cable cutting tool, Insulation removal tool, Wire-brush, Crimping tool, T&B WT3D tool (for 35kV cable ties)
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), User-supplied connector, DELTECt Cable ties (TYD5135, for 35kV only), No. 14 AWG copper wire or equivalent (if shield wires are smaller)
- De-energize and Inspect Apparatus
DANGER: Ensure all apparatus is de-energized before beginning installation. Do not touch or move energized products. Inspect all parts for damage, proper rating, and compatibility with mating parts. Verify package contents are complete and undamaged, and have all required tools at hand.
- Prepare Cable Lengths
Overlap both cables and cut them to 12 inches (305mm) from the centerline of the joint. This ensures sufficient length of shield wires for rejoining over the joint.
- Remove Cable Jackets and Position Shield Wires
Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm). Fold back the shield wires. Cut both cables at the joint centerline.
- Prepare Cable 1 Insulation Shield
Taper the edge of Cable 1 at least 1/2 inch (13mm) to no greater than 1-1/2 inches (38mm). Clean and lubricate the insulation shield.
- Lubricate and Position Joint Housing
Lubricate the inside bore of the joint housing on both ends. Slide the housing onto Cable 1 up to the shield wires.
- Remove Cable Insulation and Shield
Carefully remove the cable insulation and then the insulation shield from both cables according to the dimensions provided in the documentation (e.g., 'X' and 'Y' dimensions for conductor and insulation shield). DO NOT CUT OR NICK THE CABLE INSULATION OR CONDUCTOR.
- Install and Crimp Conductor Splice
If conductors are aluminum, wire-brush them thoroughly and immediately insert them into the splice. Check the dimension against the 'Max Check Before' table in the documentation; if it exceeds this, redo the assembly. Crimp the splice following the manufacturer's recommendations provided with it.
- Clean Splice and Verify Dimensions
Wipe off all excess inhibitor where applicable. Check the distance between cable insulations against the 'Max Check After' table; if it exceeds this, redo the assembly. Remove any sharp protrusions or burrs generated during crimping. Ensure all metal chips or filings are removed from the splice and joint assembly area before sliding the joint.
- Prepare Cables for Housing Placement
Clean the cables where indicated in the diagram. Lubricate in the direction of the arrows to create a build-up or ramp of lubricant at the edge of the insulation shield.
- Slide Housing into Final Position
Slide the joint housing into its final position. Ensure proper positioning by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield.
- Install Cable Ties (35kV Only)
For 35kV installations ONLY: Install two DELTECt Cable ties (TYD5135) on each end of the cable entrance. Install the outer ties approximately 1/4 inch (6mm) from the edge of the splice, then install the second ties approximately 1/4 inch (6mm) from the first, with an offset of the locking heads. Use the T&B WT3D tool (not included) to tighten and trim the ties.
- Prepare Grounding and Secure Shield Wires
Remove and discard the yellow pin from the joint grounding eye (for 35kV ONLY). Retrain the shield wires and secure them to the ends of the joint as shown in the diagram.
- Connect Joint Grounding Wires
Insert one of the shield wires from Cable 1 (if #14 AWG or larger) through the joint grounding eye. Repeat for Cable 2. If shield wires are smaller than #14 AWG, use a separate #14 AWG copper wire or equivalent. Connect the joint grounding wires and remaining shield wires using an appropriate user-supplied connector.
- Reconstruct Cable Jacket
Reconstruct the cable jacket (where applicable) over both cables and the joint housing to complete the installation.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.