ABB Installation Products 35PCJ1P1410 35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786093007
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV rated power cable joint
- Single-piece housing for simplified installation
- Accommodates cable insulation diameter: 1.725" to 1.935"
- Designed for 1000 AWG stranded aluminum conductors
- ABB Installation Products quality
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 1000 kcmil |
Connection | Compression |
Insulation | Yes |
Material | Aluminum |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Series | Style 1 |
Size | 15-3/4 inch long |
Size | 1.725 inch to 1.935 inch |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

35PCJ2P1410
35kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Conductor. Conductor Size AWG Stranded 1000.
15PCJ2J1270-G1240
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
25PCJ1K1290
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Solid 350.
25PCJ2J1240-H1240
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
69TCJS4-3-4Q
69 kv, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 3, Housing Size 4, - 4Q
35PCJ1P2400
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.725 inch to 1.935 inch. Copper Conductor. Conductor Size AWG Solid 1000.
25PCJ2H1220
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded #2/Solid #1.
15PCJ1K2310
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Conductor. Conductor Size AWG Solid 500.Frequently Asked Questions
What types of cable splicing do PCJ joints support?
PCJ power cable joints support straight splicing of two similar cables or transition splicing of different cable sizes.
What is the continuous current rating of PCJ power cable joints?
The continuous current rating of PCJ power cable joints is equal to that of the cable rating.
What type of connector is included for aluminum to copper splicing?
The kit includes an aluminum compression connector suitable for splicing aluminum conductor to aluminum conductor or aluminum conductor to copper conductor.
Can copper connectors be used with aluminum conductors in PCJ joints?
No, copper compression connectors are suitable for splicing copper conductors to copper conductors only and should not be used on aluminum conductors.
What is the AC withstand for a 15 kV class PCJ joint?
For a 15 kV class PCJ joint, the AC withstand at 60 Hz for 1 minute is 35 kV.
What is the BIL impulse withstand for a 35 kV class PCJ joint?
For a 35 kV class PCJ joint, the BIL impulse withstand (1.2 x 50 μsec. wave) is 300 kV.
What is the short-time current rating for PCJ power cable joints?
The short-time current rating for PCJ power cable joints is equal to that of the cable rating, up to 35 kA.
What safety standards do PCJ power cable joints meet?
The shield design meets IEEE 592 standard. The connectors meet ANSI 119.4 Class A and Class 3 ratings.
What is the pull force rating for the PCJ joint's interlock?
The pin-and-socket interlock of the PCJ power cable joint is designed to withstand a pull force of up to 500 lb.
What conductor materials are compatible with PCJ power cable joints?
PCJ power cable joints can be used with copper or aluminum conductors. They support a wide range of sizes up to 1250 kcmil.
How to Install the 15/25/35PCJ1 Series Straight Joint
This guide provides step-by-step instructions for installing the 15/25/35PCJ1 series straight joint, a permanent, fully shielded, and submersible joint for connecting aluminum and/or copper conductors in wire shielded cables.
Estimated time: 2h
Tools needed:
Cable cutter, Measuring tape, Cable insulation removal tool, Insulation shield removal tool, Wire brush (for aluminum conductors), Crimping tool, Deburring tool, Cleaning supplies, T&B WT3D tool (for 35kV cable ties), Wire strippers
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Connector (user supplied, for grounding), Grounding wire (e.g., #14 AWG copper wire), DELTECt Cable ties (for 35kV applications), Cable jacket reconstruction material (if applicable)
- Ensure Safety and Inspect Components
DANGER: De-energize all apparatus in the work area before beginning installation. This product must be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. Inspect all package contents and components for damage, proper rating, and compatibility with mating parts and cables.
- Prepare Cables for Joint Assembly
Overlap both cables and cut them to 12 inches (305mm) from the joint's centerline, ensuring sufficient shield wire length. Where applicable, remove the cable jacket from Cable 1 to 37 inches (940mm) and from Cable 2 to 21 inches (530mm). Fold back the shield wires, then cut both cables at the joint's centerline.
- Prepare Cable 1 and Store Housing
Taper the edge of Cable 1's insulation shield from 1/2 inch to 1-1/2 inches (13mm to 38mm). Clean and lubricate the insulation shield. Lubricate the inside bore of the joint housing on both ends. Slide the joint housing onto Cable 1 up to the shield wires for temporary storage.
- Prepare Cables for Splice Installation
Carefully remove the cable insulation and then the insulation shield from both cables according to the specified 'X' and 'Y' dimensions for your conductor sizes. DO NOT CUT OR NICK THE CABLE INSULATION OR CONDUCTOR during this process.
- Install the Splice
If conductors are aluminum, wire-brush them immediately before insertion into the splice. Insert conductors into the splice and check the 'Max Check Before' dimension. Crimp the splice following its recommendations. Wipe off any excess inhibitor. Check the distance between cable insulations against the 'Max Check After' dimension. Remove any sharp protrusions or burrs from the crimped splice and thoroughly clean the splice and joint assembly area. Clean and lubricate the cables as indicated, building up a ramp of lubricant at the edge of the insulation shield.
- Complete Joint Assembly and Grounding
Slide the joint housing into its final position, ensuring proper placement by observing and equalizing the deformation of the joint ends. For 35kV applications ONLY, install two DELTECt Cable ties on each end of the cable entrance, using a T&B WT3D tool for tightening, and remove the yellow pin from the joint grounding eye. Retrain the shield wires and secure them to the ends of the joint. Insert one shield wire from each cable (if #14 AWG or larger, otherwise use separate #14 AWG copper wire) through the joint grounding eye. Connect the joint grounding wires and remaining shield wires using an appropriate connector. Finally, reconstruct the cable jacket over both cables and the joint housing where applicable.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.