ABB Installation Products 35PCJ1L1290-S 35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 075114142410
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV rated power cable joint
- Single-piece housing, Style 1
- Accommodates 1.180" to 1.465" cable insulation diameter
- Designed for 350 AWG solid aluminum conductors
- Includes cold-shrinkable jacket seal for enhanced protection
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 350 kcmil |
Connection | Compression |
Insulation | Yes |
Material | Aluminum |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Series | 35PCJ1L1290-S |
Size | 14-3/8 inch long |
Size | 1.180 inch to 1.465 inch |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 3.4400 L |
Package Weight (Metric) | 1.5600 kg |

35PCJ1M1300
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 350.
15PCJ1H2300
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Copper Conductor. Conductor Size AWG Stranded 350.
15PCJ2J1270-F1220
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded #2/Solid #1.
35PCJ1J1230S
35kV Power Cable Joint Style 1, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50. Cold Shrinkable Jacket Seal included.
15PCJ2F2240
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Copper Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
25PCJ2H1250-H1240
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
25PCJ2K2300-J2270
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Conductor. Conductor Size AWG Stranded 350. Cable Insulation Diameter 0.980 inch to 1.180 inch. Copper Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.
15PCJ2F1210
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded #3/Solid #2.Frequently Asked Questions
Can copper connectors be used with aluminum conductors?
No, copper compression connectors are suitable for splicing copper conductors to copper conductors only and should not be used on aluminum conductors.
What safety standards do PCJ joints meet?
The shield design of PCJ joints meets IEEE 592 standard, and the connectors meet ANSI 119.4 Class A and Class 3 ratings.
What is the difference between PCJ Style 1 and Style 2?
Style 1 PCJ joints are for straight splicing of two similar cables. Style 2 includes separate cable adapters for transition splicing between two different cable sizes.
What conductor materials are compatible with PCJ joints?
PCJ power cable joints are compatible with copper or aluminum conductors, supporting a wide range of sizes up to 1250 kcmil.
What voltage classes are PCJ joints available in?
PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
Where can Elastimold PCJ joints be installed?
Elastimold PCJ power cable joints can be installed in direct-burial, underground vault, and even overhead applications as a permanent, fully shielded, submersible splice.
What types of cable splicing can PCJ joints perform?
PCJ power cable joints can perform straight splicing of two similar cables or transition splicing of different cable sizes up to 1250 kcmil.
What are Elastimold PCJ power cable joints?
Elastimold PCJ power cable joints are versatile cable splicing accessories with permanently crimped connectors inside EPDM rubber housings, offering proven reliability.
What types of cable splicing can PCJ joints perform?
PCJ power cable joints can perform straight splicing of two similar cables or transition splicing of different cable sizes up to 1250 kcmil.
What safety standards do PCJ joints meet?
The shield design of PCJ joints meets IEEE 592 standard, and the connectors meet ANSI 119.4 Class A and Class 3 ratings.
How to Install the 15/25/35PCJ1 Series Straight Joint
This guide provides step-by-step instructions for installing the 15/25/35PCJ1 series straight joint, a permanent, fully shielded, and submersible joint for aluminum or copper conductor wire shielded cables. Ensure all apparatus are de-energized before beginning installation.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Wire-brush, Crimping tool, T&B WT3D tool (for 35kV only)
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), DELTECt Cable ties (for 35kV only), #14 AWG copper wire (if needed), Appropriate connector
- Perform Initial Safety Checks and Prepare Workspace
Before starting, ensure all apparatus are de-energized. Inspect all parts for damage, correct rating, and compatibility with mating parts. Check the package contents to ensure they are complete and undamaged, and verify all components fit properly with the cable and/or mating products. Read these entire instructions and have all required tools at hand, maintaining cleanliness throughout the procedure.
- Prepare Cables for Joint Centerline
Overlap both cables and cut them to 12 inches (305mm) from the center line of the joint. Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm). Fold back the shield wires on both cables. Finally, cut both cables precisely at the joint centerline.
- Prepare Cable 1 and Store Joint Housing
Taper the edge of Cable 1's insulation shield from at least 1/2 inch (13mm) to no greater than 1-1/2 inches (38mm). Clean and lubricate the insulation shield of Cable 1. Lubricate the inside bore of the joint housing on both ends. Carefully slide the joint housing onto Cable 1, pushing it up to the shield wires. This procedure is designed not to contaminate electrical interfaces.
- Prepare Cables for Splice Installation
Carefully remove the cable insulation and then the insulation shield from both Cable 1 and Cable 2. Exercise extreme caution to avoid cutting or nicking the cable insulation or conductor. Refer to the provided dimensions (X and Y) for the precise lengths to remove based on your conductor size (e.g., 500-750 MCM or 1000 MCM).
- Install the Splice
If the conductors are aluminum, wire-brush them thoroughly and immediately insert them into the splice. Check the dimension against the 'Max Check Before' table; if it exceeds, redo the assembly. Crimp the splice following its specific recommendations. Wipe off any excess inhibitor. Check the distance between cable insulations against the 'Max Check After' table; if it exceeds, redo the assembly. Remove any sharp protrusions or burrs generated during crimping. Clean the cables where indicated and lubricate in the direction of the arrows to create a lubricant build-up or ramp at the edge of the insulation shield.
- Complete Joint Assembly and Grounding
Slide the joint housing into its final position. Ensure proper positioning by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield. For 35kV ONLY: Install two DELTECt Cable ties on each end of the cable entrance, approximately 1/4 inch (6mm) from the splice edge and 1/4 inch (6mm) from the first, with offset locking heads. Use a T&B WT3D tool to tighten and trim. For 35kV ONLY: Remove and discard the yellow pin from the joint grounding eye. Retrain the shield wires and secure them to the ends of the joint as shown. Insert one shield wire from Cable 1 (if #14 AWG or larger) through the joint grounding eye, and repeat for Cable 2. If shield wires are smaller than #14 AWG, use separate #14 AWG copper wire or equivalent. Connect the joint grounding wires and remaining shield wires using an appropriate connector. Finally, reconstruct the cable jacket (where applicable) over both cables and the joint housing.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.