ABB Installation Products 35PCJ1L1250 35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786350988
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Single-piece molded rubber housing for simplified installation
- Accommodates cable insulation diameters from 1.180" to 1.465"
- Aluminum conductor supports stranded 2/0 AWG or solid 3/0 AWG
- Rated per IEEE Standard 404 for 35kV voltage class
- Fully shielded, fully submersible, withstands pulls up to 500 lbs
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 2/0 STR AWG , 3/0 SOL AWG |
Connection | Compression |
Insulation | Yes |
Material | Aluminum |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Series | 35PCJ1L |
Size | 14-3/8 inch long |
Size | Cable Insulation Diameter 1.180 inch to 1.465 inch |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 3.2500 L |
Package Weight (Metric) | 1.4740 kg |

35PCJ2L2250
35kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0.
15PCJ2J1230-G1230
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0.
15PCJ1J1240
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
15PCJ1H1280
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 250.
69TCJS1Q242PNDNNB
69 kv, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 1, Housing Size Q Bore Diameter at Jacket/Insulation Transition 1.750. Connector Type - Copper, Connector Code 42P - Conductor Diameter Range - 1.146-1.220 inch (29.11-30.99mm), Heatsink Bore - N - 1.500 inch Diameter. Type Shield - D - Copper Tape and Neutral Wire, Metallic Screen Continuity Kit - N - not required, Armor Kit - N - not required, Outer Jacket Restoration Kit - B - Heat Shrink
15PCJ2J127P-G125P
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. With Customer Specific Modifications
25PCJ1J1260
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 3/0 /Solid 4/0.
15PCJ2L1360
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Solid 750.Frequently Asked Questions
What material are PCJ cable joints made from?
Elastimold PCJ power cable joints feature permanently crimped connectors inside EPDM rubber housings.
What are the two styles of PCJ power cable joints?
Style 1 is for straight splicing of two similar cables. Style 2 allows for transition splicing between different cable sizes.
What type of connector is included in the N1 kit?
The N1 kit includes an aluminum compression connector suitable for splicing aluminum to aluminum or aluminum to copper conductors.
What is the short-time current rating for PCJ joints?
The short-time current rating for PCJ power cable joints is equal to that of the cable rating, up to 35 kA.
What is the continuous current rating for PCJ joints?
The continuous current rating for PCJ power cable joints is equal to that of the cable rating.
What safety standards do PCJ joints meet?
The shield design meets IEEE 592 standard, and connectors meet ANSI 119.4 Class A and Class 3 ratings.
Is taping required for PCJ joint cable entrances?
No, the cable entrance engages the insulation shielding of the cable, eliminating the need for taping.
What conductor materials are compatible with PCJ joints?
PCJ power cable joints are compatible with both copper and aluminum conductors.
What voltage classes are available for PCJ joints?
PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
Where can PCJ power cable joints be installed?
PCJ power cable joints can be installed in direct-burial, underground vault, and overhead applications.
How to Install the 15/25/35PCJ1 Straight Joint
This guide provides step-by-step instructions for the safe and proper installation of the 15/25/35PCJ1 straight joint for wire shielded cables, designed for permanent, fully shielded, and submersible applications.
Estimated time: 1h 30m
Tools needed:
Cable stripping tools, Wire brush, Crimping tool, T&B WT3D tool (for 35kV only)
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Appropriate connector (for grounding wires), DELTECt Cable ties (for 35kV only), #14 AWG copper wire (or equivalent, if needed), Cable jacket repair material (if applicable)
- Ensure Safety and Prepare Workspace
De-energize all apparatus in the work area. Inspect package contents and all components for damage, proper rating, and compatibility. Gather all required tools and maintain cleanliness throughout the procedure. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment.
- Prepare Cables for Jointing
Overlap both cables and cut them to 12 inches (305mm) from the joint centerline. Remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm). Fold back the shield wires and cut both cables at the joint centerline.
- Prepare Cable 1 and Position Joint Housing
Taper the edge of Cable 1 insulation from 1/2 inch to 1-1/2 inches (13mm to 38mm). Clean and lubricate the insulation shield. Lubricate the inside bore of the joint housing on both ends. Slide the housing onto Cable 1 up to the shield wires.
- Prepare Cables for Splice
Carefully remove the cable insulation and then the insulation shield from both Cable 1 and Cable 2 according to the specified dimensions ("X" and "Y" from the table). Ensure not to cut or nick the cable insulation or conductor during this process.
- Install and Crimp the Splice
If conductors are aluminum, wire-brush them immediately before insertion into the splice. Insert conductors into the splice and crimp it according to the splice manufacturer's recommendations. Wipe off any excess inhibitor. Verify the distance between cable insulations against the "Max Check After" dimension in the table; redo assembly if it exceeds. Remove any sharp protrusions or burrs from the crimped splice and clean the splice and joint assembly area. Clean and lubricate the cables where indicated, building up lubricant at the edge of the insulation shield.
- Finalize Joint Assembly and Grounding
Slide the joint housing into its final position, ensuring proper placement by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield. For 35kV installations only, install two DELTECt Cable ties on each end of the cable entrance as specified, using a T&B WT3D tool if available, and remove the yellow pin from the joint grounding eye. Retrain shield wires and secure them to the ends of the joint. Insert one shield wire from Cable 1 (if #14 AWG or larger) through the joint grounding eye, repeating for Cable 2. If shield wires are smaller than #14 AWG, use separate #14 AWG copper wire or equivalent. Connect joint grounding wires and remaining shield wires using an appropriate connector. Reconstruct the cable jacket over both cables and the joint housing where applicable.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.