ABB Installation Products 25PCJ1J1260 25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786360338
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 25 kV voltage rating for medium-voltage applications
- Style 1 single-piece housing design
- Accommodates cable insulation diameter from 0.980" to 1.180"
- Designed for aluminum conductors: AWG Stranded 3/0 to Solid 4/0
- Includes housing, connector, lubricant, and installation instructions
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 3/0 STR AWG , 4/0 SOL AWG |
Connection | Compression |
Insulation | Yes |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Size | 14-3/8 inch long |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 15.0000 L |
Package Weight (Metric) | 6.8040 kg |

15PCJ1G1260
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded 3/0 /Solid 4/0.
15PCJ2L1360
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Solid 750.
35PCJ1K1270-S
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250. Cold-Shrinkable Jacket Seal Included.
15PCJ2G1230
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0.
15PCJ1J1290
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Solid 350.
15PCJ1P2410
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.725 inch to 1.935 inch. . Copper Conductor. Conductor Size AWG Stranded 1000.
25PCJ1L2330-2320
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Conductor. Conductor Size AWG Stranded 500. Copper Conductor. Conductor Size AWG Stranded 450.
25PCJ1M1320
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 450.Frequently Asked Questions
What is the maximum voltage rating for this cable joint?
The 25PCJ1J1260 power cable joint has a voltage rating of 25 kV.
What conductor sizes does this joint support?
This joint supports aluminum conductors sized AWG Stranded 3/0 or Solid 4/0.
What is the compatible cable insulation diameter range?
The joint is designed for cable insulation diameters between 0.980 inches and 1.180 inches.
What type of conductor material is this joint for?
This power cable joint is specifically designed for aluminum conductors.
What is the housing style of this ABB cable joint?
The 25PCJ1J1260 features a single-piece housing, Style 1.
How to Install the ABB 25PCJ1 Series Straight Joint
This guide provides step-by-step instructions for the safe and proper installation of the ABB 15/25/35PCJ1 series straight joint for wire shielded cables. It covers cable preparation, splice installation, and final assembly.
Estimated time: 2h
Tools needed:
Cable stripping tools, Wire brush, Crimping tool, T&B WT3D tool (recommended for 35kV installations)
Supplies needed:
Joint Housing (15/25/35PCJ1WXXXX), Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), DELTECt Cable ties (TYD5135, for 35kV only), #14 AWG copper wire (if needed for grounding), Appropriate grounding connector, Cable jacket repair material
- Ensure Safety and Inspect Components
DANGER: De-energize all apparatus before starting installation. Inspect all parts, including the joint housing, splice, and lubricant, for any damage, correct rating, and compatibility with the mating cables and products.
- Gather Tools and Maintain Cleanliness
Have all required tools at hand and ensure a clean work environment throughout the entire installation procedure to prevent contamination.
- Overlap and Cut Cables
Overlap both cables and cut them to 12 inches (305mm) from the center line of the joint. This ensures sufficient length of shield wires to be able to rejoin over the joint.
- Remove Cable Jackets
Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and the cable jacket of Cable 2 to 21 inches (530mm).
- Fold Back Shield Wires and Cut Cables
Fold back the shield wires on both cables. Cut both cables at the center line of the joint.
- Taper Cable 1 and Lubricate
Taper the edge of Cable 1's insulation shield at least 1/2 inch (13mm) to no greater than 1-1/2 inches (38mm). Clean and lubricate the insulation shield.
- Lubricate and Store Joint Housing
Lubricate the inside bore of the joint housing on both ends. Slide the housing onto Cable 1 up to its shield wires.
- Remove Cable Insulation and Shield
Carefully remove the cable insulation and then the insulation shield from both Cable 1 and Cable 2 according to the 'X' and 'Y' dimensions provided in the document's table. DO NOT CUT OR NICK THE CABLE INSULATION OR CONDUCTOR.
- Prepare Conductors and Insert into Splice
If conductors are aluminum, wire-brush them immediately before insertion into the splice. Insert the prepared conductors into the splice.
- Crimp the Splice
Crimp the splice following the recommendations provided with the splice itself.
- Clean and Verify Splice
Wipe off all excess inhibitor where applicable. Check the distance between cable insulations against the 'Max Check After' dimension table; if it exceeds, redo the assembly. Remove any sharp protrusions or burrs generated during crimping.
- Clean and Lubricate Cables
Clean the cables where indicated. Lubricate in the direction of the arrows to provide a build-up or ramp of lubricant at the edge of the insulation shield.
- Slide Housing into Final Position
Slide the joint housing into its final position. Proper positioning is ensured by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield.
- Install Cable Ties (35kV Only)
For 35kV installations ONLY: Install two DELTECt Cable ties on each end of the cable entrance. Install the outer ties approximately 1/4 inch (6mm) from the splice edge, then the second ties approximately 1/4 inch (6mm) from the first with an offset of the locking heads. Use a T&B WT3D tool to tighten and trim.
- Remove Grounding Pin (35kV Only)
For 35kV installations ONLY: Remove the yellow pin from the joint grounding eye and discard it.
- Retrain and Secure Shield Wires
Retrain the shield wires and secure them to the ends of the joint as shown in the installation diagrams.
- Insert Shield Wires into Grounding Eye
Insert one of the shield wires from Cable 1 (if #14 AWG or larger) through the joint grounding eye. Repeat this for Cable 2. If shield wires are smaller than #14 AWG, use a separate #14 AWG copper wire or equivalent.
- Connect Grounding Wires
Connect the joint grounding wires and the remaining shield wires using an appropriate connector.
- Reconstruct Cable Jacket
Reconstruct the cable jacket (where applicable) over both cables and the joint housing to complete the installation.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.