ABB Installation Products 35PCJ1K1260-S 35kV Power Cable Joint Style 1, Cable Insulation Diameter 1.090 inch to 1.310 inch.…
UPC: 783786338016
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV rated per IEEE Standard 404 with 200kV BIL impulse withstand
- Accommodates 1.090-1.310" insulation diameter and 3/0-4/0 AWG or 95 mm² compact conductors
- Fully shielded, fully submersible, and straight splice design
- Cold shrinkable jacket seal for watertight, corrosion-resistant installation
- Aluminum compression lug ensures secure, low-resistance connections
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 3/0 STR AWG , 4/0 SOL AWG |
Connection | Compression |
Connection Type | Compression Lug |
Insulation | Yes |
Material | Aluminum |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Size | 14-3/8 inch long |
Size | Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95 |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 10.5 IN x 19.12 IN x 12.5 IN |
Package Dimensions (L x W x H) | 26.67 cm x 48.5648 cm x 31.75 cm |
Package Weight (Imperial) | 3.0400 L |
Package Weight (Metric) | 1.3790 kg |

35PCJ1K1260
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 3/0 /Solid 4/0.
15PCJ1G2270
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Copper Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.
15PCJ1M1410Z
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 1000. Tin, Thin Walled, Connector
25PCJ2J1230-G1230
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0.
15PCJ1G2240
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Copper Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
15PCJ1G2230
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Copper Conductor. Conductor Size AWG Stranded #1/Solid 1/0.
15PCJ1H1230
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0.
25PCJ1H1260
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 3/0 /Solid 4/0.Frequently Asked Questions
What voltage rating does this cable joint support?
This cable joint is rated for 35kV medium-voltage applications.
What is the insulation diameter range for this joint?
The joint accommodates cable insulation diameters from 1.090 inch to 1.310 inch.
What conductor sizes are compatible with this joint?
The joint supports 3/0 AWG compressed stranded, 4/0 AWG compacted solid, or 95 mm² compact conductors.
Is a jacket seal included with this joint?
Yes, a cold shrinkable jacket seal is included for watertight and corrosion-resistant protection.
What material is the lug made of?
The lug is made of aluminum for secure, low-resistance connections.
Does this joint require heat for installation?
No, this joint uses a cold shrinkable design and does not require heat for installation.
How to Install the 35PCJ1K1260-S Straight Joint
This guide provides step-by-step instructions for the permanent installation of the 35PCJ1K1260-S straight joint on aluminum or copper conductor, wire shielded cables. Ensure all safety precautions are followed for high voltage electrical equipment.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Utility knife, Wire brush
Supplies needed:
35PCJ1K1260-S Joint Housing (kit contents), Splice (Conductor Contact), Lubricant (provided with kit), Appropriate electrical connector, #14 AWG copper wire (if needed), Cable jacket restoration kit (if applicable)
- De-energize and Inspect Apparatus
DANGER: De-energize all apparatus before beginning installation or removal of any parts. Inspect all components for damage, proper rating, and compatibility with mating parts. This product must be installed by competent personnel trained in high voltage electrical equipment safety practices.
- Prepare Cable Lengths
Overlap both cables and cut them to 12 inches (305mm) from the joint centerline. Where applicable, remove the cable jacket of Cable 1 to 34 inches (865mm) and Cable 2 to 20 inches (510mm). Fold back the shield wires, then cut both cables at the joint centerline.
- Prepare Cable 1 and Store Housing
Taper the edge of Cable 1's insulation from 1/2 inch to 1-1/2 inches (13mm to 38mm). Clean and lubricate the insulation shield of Cable 1. Lubricate the inside bore of the joint housing on both ends, then slide the housing onto Cable 1 up to the shield wires.
- Prepare Cables for Splice
Using the stripping guide, carefully remove the cable insulation and then the insulation shield from both Cable 1 and Cable 2. WARNING: Do not cut or nick the cable insulation or conductor, as this could lead to assembly failure.
- Install the Splice
If using aluminum conductors, wirebrush them immediately before insertion into the splice. Insert conductors into the splice, ensuring the 'Check' dimension does not exceed 5 inches (127mm). Crimp the splice following its recommendations. Wipe off any excess inhibitor, then verify the distance between cable insulations does not exceed 5-1/4 inches (133mm). Remove any sharp protrusions or burrs generated during crimping, and clean all metal chips/filings from the splice and joint assembly area. Clean the cables where indicated, then lubricate in the direction of arrows to create a lubricant build-up at the edge of the insulation shield.
- Complete Joint Assembly
Slide the joint housing into its final position, ensuring proper placement by equalizing the deformation of the joint ends caused by the underlying cable insulation shield. Reshape and secure the shield wires to the ends of the joint. Insert one shield wire from Cable 1 (if #14 AWG or larger) through the joint grounding eye, and repeat for Cable 2. If shield wires are smaller than #14 AWG, use separate #14 AWG copper wire or equivalent. Connect the joint grounding wires and remaining shield wires using an appropriate connector. Reconstruct the cable jacket (if applicable) over both cables and the joint housing.
- Seal Cable Jacket
WARNING: If one or both cables are jacketed, it is critical to seal the ends of the jacket or completely restore the jacket across the joint. Follow standard operating procedures or instructions provided with compatible jacket sealing or restoration kits to ensure appropriate seals or restoration.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.