ABB Installation Products 35PCJ1K1260 35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786641093
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Rated for 35kV class systems with 35,000V capacity
- Single-piece housing for simplified installation and consistent performance
- Accommodates aluminum conductors: 3/0 AWG stranded to 4/0 AWG solid
- Insulation diameter range: 1.090 inch to 1.310 inch
- Part of ABB Installation Products series for medium-voltage applications
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 3/0 STR AWG , 4/0 SOL AWG |
Connection | Compression |
Insulation | Yes |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Size | 14-3/8 inch long |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.7500 L |
Package Weight (Metric) | 0.7940 kg |

25PCJ1J1260
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 3/0 /Solid 4/0.
15PCJ1G1250
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0.
35PCJ1M1270
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.
15PCJ1J1300
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 350.
15PCJ2G1230-F1220
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Conductor. Conductor Size AWG Stranded #2/Solid #1.
25PCJ1J1240
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.Frequently Asked Questions
Can copper connectors be used with aluminum conductors?
No, copper compression connectors are suitable for copper-to-copper connections only and should not be used on aluminum conductors.
What types of cable splicing can PCJ joints perform?
PCJ power cable joints can perform straight splicing of two similar cables or transition splicing of different cable sizes.
Where can PCJ power cable joints be installed?
PCJ power cable joints can be installed in direct-burial, underground vault, and overhead applications. They provide a permanent, fully shielded, fully submersible splice.
What voltage classes are available for PCJ joints?
PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
What conductor materials are compatible with PCJ joints?
PCJ power cable joints are compatible with copper or aluminum conductors. They support a wide range of sizes up to 1250 kcmil.
Do PCJ joints require taping at the cable entrance?
No, the cable entrance engages the insulation shielding of the cable, eliminating the need for taping.
What pull force can the pin-and-socket interlock withstand?
The pin-and-socket interlock in PCJ joints can withstand a pull force of up to 500 lb.
How is the molded conductive shield grounded?
A grounding eye provides a convenient point to connect a ground wire to the molded conductive shield, placing it at ground potential.
What safety standards do PCJ joints meet?
The shield design meets IEEE 592 standard, and the connectors meet ANSI 119.4 Class A and Class 3 ratings.
What is the continuous current rating of PCJ joints?
The continuous current rating of PCJ power cable joints is equal to that of the cable rating.
How to Install the 35PCJ1 Series Straight Joint
This guide provides detailed instructions for installing the 35PCJ1 Series Straight Joint, a permanent, fully shielded, and submersible joint for wire shielded cables. It covers essential cable preparation, splicing, and housing assembly. Always ensure all apparatus are de-energized before beginning installation and maintain cleanliness throughout the procedure.
Estimated time: 2h
Tools needed:
Wire strippers, Safety knife, Wire brush (for aluminum conductors), Crimping tool (for splice), T&B WT3D tool (recommended for 35kV cable ties)
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Appropriate connector (for grounding wires), DELTECt Cable ties TYD5135 (for 35kV only), #14 AWG copper wire (if shield wires are smaller)
- Safety First and Initial Inspection
De-energize all apparatus and verify the circuit is dead before starting any work. Read these instructions completely, inspect all components for damage, proper rating, and compatibility with mating parts. Ensure all required tools are at hand and maintain cleanliness throughout the procedure.
- Prepare Cables for Joint Centerline
Overlap both cables and cut them to 12 inches (305mm) from the intended centerline of the joint. Where applicable, remove the cable jacket for Cable 1 to 37 inches (940mm) and for Cable 2 to 21 inches (530mm). Fold back the shield wires. Finally, cut both cables precisely at the joint centerline.
- Prepare Cable 1 and Store Housing
Taper the edge of Cable 1 insulation from at least 1/2 inch to no greater than 1-1/2 inches (13mm to 38mm). Clean and lubricate the insulation shield. Lubricate the inside bore of the joint housing on both ends. Carefully slide the housing onto Cable 1, positioning it up to the shield wires.
- Prepare Cables for Splice Installation
Carefully remove the cable insulation and then the insulation shield from both cables. Exercise extreme caution to avoid cutting or nicking the cable insulation or conductor, as this can lead to product failure and serious injury.
- Install and Crimp the Splice
If conductors are aluminum, wire-brush them thoroughly and immediately insert them into the splice. Check the dimension against the 'Max Check Before' table provided with the splice; redo assembly if it exceeds. Crimp the splice following the manufacturer's recommendations. Wipe off any excess inhibitor. Check the distance between cable insulations against the 'Max Check After' table; redo assembly if it exceeds. Remove any sharp protrusions or burrs generated during crimping and ensure all metal chips/filings are cleared from the splice and joint assembly area.
- Clean and Lubricate Cables for Housing
Clean the cables where indicated in the diagrams. Apply lubricant in the direction of the arrows to create a build-up or ramp of lubricant at the edge of the insulation shield, ensuring proper sealing and insulation.
- Position Joint Housing
Slide the joint housing into its final position over the spliced conductors. Proper positioning is ensured by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield.
- Grounding and Jacket Reconstruction
Retrain the shield wires and secure them to the ends of the joint as shown in the diagrams. Insert one of the shield wires from Cable 1 (if #14 AWG or larger) through the joint grounding eye, and repeat for Cable 2. If shield wires are smaller than #14 AWG, use separate #14 AWG copper wire or equivalent. Connect the joint grounding wires and remaining shield wires using an appropriate connector. Reconstruct the cable jacket (where applicable) over both cables and the joint housing.
- Install DELTECt Cable Ties (35kV ONLY)
For 35kV installations ONLY: Install two DELTECt Cable ties (TYD5135) on each end of the cable entrance. Begin by installing the outer ties approximately 1/4 inch (6mm) from the edge of the splice, then install the second ties approximately 1/4 inch (6mm) from the first with an offset of the locking heads. The T&B WT3D tool (not included) is recommended to tighten and trim the ties. Remove and discard the yellow pin from the joint grounding eye.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.