ABB Installation Products 274FLR3-C0250 Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 17.2kV, Fuse Test Port…
UPC: 783786445042
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Nominal fuse voltage rating: 17.2kV for medium-voltage protection
- Two capacitive test ports enable safe, non-invasive fuse testing
- Cable insulation diameter compatibility: 0.805in–1.060in (20–27mm)
- Aluminum lug accepts 2/0 AWG stranded compressed or 3/0 AWG solid compact conductors
- Aluminum Lug for 2/0 AWG Stranded Compressed / 3/0 AWG Solid Compact Conductors
Specifications
Amperage Rating | 200 A |
Application | Protect Light Duty Underground Distribution Systems |
Color | Black |
Conductor Range | 2/0 STR/COMPR AWG , 3/0 SOL/COMPT AWG |
Connection Type | Aluminum Lug |
Insulation | True |
Length | 21.12 in |
Length | 536.448 mm |
Material | Molded |
Material | EPDM-Rubber |
Series | 274FLR3 |
Size | Large Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm |
Special Features | Full-Range Current-Limiting Fusing with 50kA Interrupting Capability. Hotstick Operable 25/28kV Loadbreak Elbow Switching |
Standard | IEEE 386, ANSI C37.40, ANSI C37.41, ANSI C37.47 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Fused Elbow Connector with Test Point |
Voltage Rating | 15.5 to 16.2 kV |
Voltage Rating | 17.2 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

168FLR3B0250
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Large Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 2/0 AWG Stranded/Compressed, 3/0 AWG Solid/Compact.
168FLR1-D0220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.890 inch - 1.220 inch / 25-31mm, Aluminum Conductor size 2 AWG Stranded Compressed, 1 AWG Solid/Compact.
274FLR3-C0240
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 17.2kV, Fuse Test Port - Two Capactive Test Ports, Large Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm, Aluminum Conductor size 1/0 AWG Stranded Compressed, 2/0 AWG Solid Compact
168FLR1-B0220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 2 AWG Stranded/Compressed, 1 AWG Solid/Compact.
168FLR1-B0230
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 1 AWG Stranded/Compressed, 1/0 AWG Solid/Compact.
168FLR1-A0210
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.575 inch - 0.740 inch / 15-19mm, Aluminum Conductor size 2 AWG Solid/Compact.
168FLR1-B0250
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 2/0 AWG Stranded/Compressed, 3/0 AWG Solid/Compact.
168FLR1-D0270
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.890 inch - 1.220 inch / 25-31mm, Aluminum Conductor size 4/0 AWG Stranded/Compressed.Frequently Asked Questions
Are sealing and grounding kits recommended?
Yes, for safety purposes, a sealing and grounding kit is highly recommended with the loadbreak elbow. Specific kits are available for different cable types.
How is the W code determined for the catalog number?
The W code is determined by the cable's insulation diameter. Select the letter code that best straddles the insulation diameter from the W table.
How do I select the correct housing size?
Housing size is selected based on the desired fuse size and voltage. For example, Housing 1 is for 3-45A 8.3kV or 6-20A 15.5kV fuses.
How is fuse replacement handled?
The 274FLR features a split center section designed for easy fuse replacement.
Is the fuse included with the 274FLR?
No, the fuse for the 274FLR must be ordered separately.
Does the 274FLR have a test point?
Yes, it has built-in voltage test points for quick and convenient blown fuse indication.
Is the 274FLR submersible?
Yes, the 274FLR is fully sealed and submersible when used with ECS series sealing kits.
What is the current rating range?
The current rating for the 274FLR is 6-20 Amps.
What is the symmetrical interrupting capability?
The 274FLR has a symmetrical interrupting capability of 50,000 Amps.
What industry standards does the 274FLR meet?
The 274FLR meets IEEE 386, ANSI C37.40, ANSI C37.41, and ANSI C37.47 standards.
How to Install the 274FLR Loadbreak Fused Elbow Connector
This guide provides step-by-step instructions for the installation and initial setup of the 274FLR Loadbreak Fused Elbow Connector, including cable preparation, assembly, and neutral connection. Ensure all apparatus are de-energized before starting.
Estimated time: 1h
Tools needed:
Probe Wrench, Special Torque Limiting Allen Wrench (supplied), Wire brush, Crimp tool (refer to lug chart), Hotstick (for final connection and operation)
Supplies needed:
Cable Half Housing, Elbow Half Housing, Fuse, Compression Lug, Probe, Probe Connector, Hose Clamp, Lubricant (supplied), Optional 200ECS Cold Shrink Cable Seal, Copper wire (No. 14 AWG / 2.5mm) or equivalent, Appropriate connector (for grounding neutral wires), HV insulated cap(s) or connector(s) (if replacing shipping covers)
- Prepare for Installation and Safety Checks
De-energize all apparatus in the work area. Inspect all parts for damage, proper rating, and compatibility with mating components. Check the package contents to ensure completeness. Thread the probe into the compression lug to check threads; replace any damaged components if resistance is encountered. Have all required tools at hand and maintain cleanliness throughout the procedure. If the product was supplied with shipping covers, remove them and replace with appropriate HV insulated caps or connectors before energizing.
- Prepare the Cable for Termination
Using the bushing centerline as a reference, cut excess cable off, leaving a minimum of 20 inches beyond the bushing. If using, slide the optional 200ECS Cold Shrink Cable Seal onto the cable. Remove the jacket from the excess cable length and an additional distance of 'A' (fuse body length) plus 7-3/8 inches from the bushing centerline. If a Cable Seal kit is used, follow its instructions. Otherwise, unwrap and fold the concentric neutral wires back over the jacket and bind them. Squarely cut off the cable a distance of 'A' from the bushing centerline, leaving a minimum of 7-3/8 inches of cable to terminate.
- Prepare the Cable End and Install Compression Lug
Cut 1-1/8 inches from the cable end, ensuring the cut is square and does not nick the conductor. Wire brush the bare aluminum conductors thoroughly and immediately install the compression lug. Rotate the lug to spread the inhibitor. Crimp the unthreaded end of the compression lug to the conductor, referring to the crimp chart provided with the lug for tool information. Start the crimp at the crimp line mark and rotate 180 degrees for each successive crimp. Carefully wipe any excess inhibitor from the outside of the lug and cable. Remove the insulation shield 5-1/2 inches from the end of the lug and bevel the insulation end by a maximum of 1/8 inch. Thoroughly clean the insulation to remove all traces of conductive residue.
- Lubricate and Assemble Cable Half Housing
Apply the supplied lubricant to the outside of the connector, the cable insulation, the conductive shield, and the cable entrance end of the Fused Elbow's cable half. Insert the prepared connector and cable into the cable half of the Fused Elbow until the top end of the connector protrudes beyond surface 'A'. This allows the fuse to be tightened before bottoming on the rubber.
- Install Fuse and Probe Connector
Insert the threaded terminal end of the fuse into the cable half of the Fused Elbow and thread it into the cable connector. HAND TIGHTEN the fuse; do not over-torque as the fuse stud will fracture. Pull the housing up against the bottom of the tightened fuse. Assemble the probe connector to the fuse terminal. Rotate the probe connector so that its flats are perpendicular to the bushing with which it will mate. Lock the probe connector in position and tighten the setscrews using the special torque limiting allen wrench supplied in the fuse kit. Rotate the cable half of the Fused Elbow so that its test point is perpendicular to the flats on the probe connector.
- Assemble Elbow Halves and Secure Probe
Apply the supplied lubricant to the elbow half of the fused elbow and assemble it to the cable half. The cuff of the cable half will overlap the elbow half by 3/4 inch. Ensure that the probe connector faces the opening of the fused elbow half and that the two test points are in line with each other. Insert the probe into the probe connector; it may be necessary to push on the cable to align the probe with the fuse. Start the threads by hand, taking care not to cross-thread the probe. To tighten, use the special torque limiting allen wrench supplied by inserting the short end into the hole in the probe and tightening until the wrench bends and remains bent. Position the hose clamp as shown in the diagram and tighten it, but DO NOT OVERTIGHTEN.
- Connect Concentric Neutral Wires
Using a separate copper wire (No. 14 AWG / 2.5mm) or equivalent, insert one end through each grounding eye on the elbow housing and cable housings. Twist tightly, taking care not to damage the eyes. If used, finish installing the 200ECS jacket seal. Twist all neutral wires together, exercising care not to damage the grounding eyes, and connect them to ground using an appropriate connector. Provide adequate slack in the wires to allow for elbow operation.
- Connect Elbow to Bushing Plug
Lubricate the receptacle portion of the elbow connector and the mating bushing with the lubricant supplied. ONLY LUBRICATE IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE-ENERGIZED. Operate the connection using a full insulated hotstick type tool; DO NOT OPERATE BY HAND. Refer to the operating instructions for proper loadmake or loadbreak procedures.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.