ABB Installation Products 168FLR1-B0230 Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port…
UPC: 783786454884
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Nominal fuse voltage rating: 8.3kV
- Cable insulation diameter range: 0.635"–0.905" (16–23mm)
- Supports 1 AWG stranded/compressed and 1/0 AWG solid/compact aluminum conductors
- Two capacitive test ports for safe diagnostic testing
- Compact molded housing for space-constrained installations
Specifications
Amperage Rating | 200 A |
Application | Protect Light Duty Underground Distribution Systems |
Color | Black |
Conductor Range | #1 STR/COMPR AWG , 1/0 SOL/COMPT AWG |
Insulation | True |
Length | 16.87 in |
Length | 428.498 mm |
Material | Aluminum |
Material | EPDM-Rubber |
Series | 168FLR1 |
Size | Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm |
Special Features | Full-Range Current-Limiting Fusing with 50kA Interrupting Capability. Hotstick Operable 15kV Loadbreak Elbow Switching |
Standard | IEEE 386, ANSI C37.40, ANSI C37.41, ANSI C37.47 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Fused Elbow Connector |
Voltage Rating | 8.3 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 7.7000 L |
Package Weight (Metric) | 3.4930 kg |

168FLR1-C0230
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm, Aluminum Conductor size 1 AWG Stranded/Compressed, 1/0 AWG Solid/Compact.
168FLR1-A0210
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.575 inch - 0.740 inch / 15-19mm, Aluminum Conductor size 2 AWG Solid/Compact.
168FLR1-B0250
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 2/0 AWG Stranded/Compressed, 3/0 AWG Solid/Compact.
168FLR1-D0270
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.890 inch - 1.220 inch / 25-31mm, Aluminum Conductor size 4/0 AWG Stranded/Compressed.
168FLR1-B0260
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 3/0 AWG Stranded/Compressed, 4/0 AWG Solid/Compact.
168FLR1-A0240
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.575 inch - 0.740 inch / 15-19mm, Aluminum Conductor size 1/0 AWG Stranded/Compressed, 2/0 AWG Solid/Compact.
168FLR3-B0240
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Large Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 1/0 AWG Stranded/Compressed, 2/0 AWG Solid/Compact.Frequently Asked Questions
What is included in each 168FLR kit?
Each kit contains an elbow connector housing, a crimp connector, a probe lug, four tubes of lubricant, installation instructions, and a crimp chart.
What types of conductors are compatible with the lugs?
Copper compression lugs are suitable for all copper conductors only. Bi-metal compression lugs with a universal aluminum barrel are suitable for both copper or aluminum conductors.
What standards does the 168FLR meet?
The 168FLR meets applicable portions of IEEE, ANSI, and other industry standards. Specifically, it meets IEEE 386, ANSI C37.40, ANSI C37.41, and ANSI C37.47.
Does this product have a test point?
Yes, the 168FLR Fused Elbow includes built-in voltage test points. These allow for quick and convenient indication of a blown fuse.
Is the fused elbow submersible?
Yes, the Elastimold Fused Elbow is fully sealed and submersible. It also insulates, shields, and eliminates exposed live parts.
What is the current rating range for this product?
The current rating for the 168FLR Loadbreak Fused Elbow is 3-80 Amps. It also has a 50,000 Amp symmetrical interrupting capability.
What voltage class is this fused elbow designed for?
The fused elbow is designed for the 15kV voltage class. It has an 8.3kV nominal fuse voltage and a 10kV maximum rated fuse voltage.
What is the primary application of this product?
The Elastimold 168FLR improves distribution system reliability by protecting light duty underground distribution systems, including sub-loops and radial taps. It replaces existing 200 Amp loadbreak tap elbows.
What is the current rating range for this product?
The current rating for the 168FLR Loadbreak Fused Elbow is 3-80 Amps. It also has a 50,000 Amp symmetrical interrupting capability.
What is included in each 168FLR kit?
Each kit contains an elbow connector housing, a crimp connector, a probe lug, four tubes of lubricant, installation instructions, and a crimp chart.
How to Install the 168FLR/274FLR Loadbreak Fused Elbow Connector
This guide provides step-by-step instructions for the safe installation and initial setup of the 168FLR or 274FLR Loadbreak Fused Elbow Connector, including cable preparation and assembly.
Estimated time: 1h 30m
Tools needed:
Wire brush, Crimp tool, Hotstick, Probe Wrench, Torque-limiting Allen Wrench
Supplies needed:
Lubricant, No. 14 AWG / 2.5mm Copper wire, Grounding connector, Optional 200ECS Cold Shrink Cable Seal
- Perform Pre-Installation Checks and Safety Review
Before beginning, ensure all apparatus is de-energized. Inspect all parts for damage, correct rating, and compatibility. Read the entire instructions. Check package contents for completeness and damage. Verify proper fit of components with cable and/or mating products. Thread the probe into the compression lug to check threads; replace damaged components if resistance is encountered. Have all required tools at hand and maintain cleanliness throughout the procedure. This product must be installed only by competent personnel trained in high voltage electrical equipment safety practices. Failure to follow instructions will result in damage and serious injury.
- Prepare Cable for Termination
Using the bushing centerline as reference, cut excess cable, leaving 20 inches minimum beyond the bushing. Remove the jacket for the specified length (A + 7-3/8 inches from bushing centerline). If using a cable seal kit, follow its instructions; otherwise, unwrap and fold concentric neutral wires back over the jacket and bind them. Squarely cut off the cable a distance of 'A' from the bushing centerline, leaving 7-3/8 inches minimum for termination. Cut 1-1/8 inches from the cable end, taking care not to nick the conductor.
- Install Compression Lug and Prepare Insulation
Wire brush bare aluminum conductors and immediately install the compression lug. Rotate the lug to spread inhibitor. Crimp the unthreaded end of the compression lug to the conductor, referring to the crimp chart for tool information. Start crimping at the crimp line mark, rotating 180 degrees for each successive crimp. Carefully wipe excess inhibitor from the outside of the lug and cable. Remove the insulation shield 5-1/2 inches from the end of the lug and bevel the insulation end 1/8 inch maximum. Thoroughly clean the insulation to remove all traces of conductive residue.
- Assemble Cable Half and Fuse
Apply the supplied lubricant to the outside of the connector, cable insulation, conductive shield, and the cable half of the Fused Elbow cable entrance end. Insert the connector and cable into the cable half of the Fused Elbow until the top end of the connector protrudes beyond surface 'A'. Insert the threaded terminal end of the fuse into the cable half and hand tighten it into the cable connector. CAUTION: Fuse stud will fracture if over-torqued. Pull the housing up against the bottom of the tightened fuse.
- Attach Probe Connector and Align Test Point
Assemble the probe connector to the fuse terminal. Rotate the probe connector so that its flats are perpendicular to the bushing with which it will mate. Lock the probe connector in position and tighten the setscrews using the special torque-limiting allen wrench supplied in the fuse kit. Rotate the cable half of the Fused Elbow so that the test point is perpendicular to the flats on the probe connector.
- Join Elbow Halves and Secure Probe
Apply lubricant to the elbow half of the fused elbow and assemble it to the cable half. The cuff of the cable half will overlap the elbow half by 3/4 inch. Ensure the probe connector faces the opening of the fused elbow half and that the two test points are in line. Insert the probe into the probe connector, pushing on the cable if necessary to align it with the fuse. Start threads by hand, avoiding cross-threading. Use the special torque-limiting allen wrench supplied; insert the short end into the hole in the probe and tighten until the wrench bends and remains bent. Position the hose clamp as shown in the diagram and tighten it, but DO NOT OVERTIGHTEN.
- Connect Concentric Neutral Wires
Using a separate copper wire (No. 14 AWG / 2.5mm) or equivalent, insert one end through each grounding eye on the elbow housing and cable housings. Twist tightly, taking care not to damage the eye. If used, finish installing the 200ECS jacket seal. Twist all neutral wires, exercising care not to damage grounding eyes, and connect to ground using an appropriate connector. Provide adequate slack in the wires for elbow operation.
- Final Connection to Bushing (De-energized)
Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant. LUBRICATE ONLY IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE-ENERGIZED. Do not operate by hand. This connection should be made using a hotstick tool following proper operating instructions for loadmake operation.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.