ABB Installation Products 274FLR1-C0260 Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 15.5kV, Fuse Test Port…
UPC: 075114245845
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Nominal fuse voltage rating: 15.5kV
- Two capacitive test ports for non-intrusive fuse testing
- Cable insulation diameter range: 0.805" to 1.060" (20-27mm)
- Supports aluminum conductors: 3/0 AWG stranded compressed or 4/0 AWG solid compact
- Temperature rise: 55°C with 105°C insulation system
Specifications
Amperage Rating | 200 A |
Application | Protect Light Duty Underground Distribution Systems |
Color | Black |
Conductor Range | 3/0 STR/COMPR AWG , 4/0 SOL/COMPT AWG |
Insulation | True |
Length | 16.87 in |
Length | 428.498 mm |
Material | EPDM-Rubber |
Size | Small Housing |
Special Features | Full-Range Current-Limiting Fusing with 50kA Interrupting Capability. Hotstick Operable 25/28kV Loadbreak Elbow Switching |
Standard | IEEE 386, ANSI C37.40, ANSI C37.41, ANSI C37.47 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Fused Elbow Connector with Test Point |
Voltage Rating | 15.5 kV |
Voltage Rating | 15.5 to 16.2 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

376LR-J-5260
200 Amp, 35kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.
274FLR1-C0230
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 15.5kV, Fuse Test Port - Two Capactive Test Ports, Small Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm, Aluminum Conductor size 1 AWG Stranded Compressed, 1/0 AWG Solid Compact
274AFLR1-D0240
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 15.5kV, Fuse Test Port - Two Direct Test Ports, Small Housing, Cable Insulation Diameter 0.890 inch - 1.220 inch / 25-31mm, Aluminum Conductor size 1 AWG Stranded Compressed, 1/0 AWG Solid/Compact.
274AFLR1-D0220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 15.5kV, Fuse Test Port - Two Direct Test Ports, Small Housing, Cable Insulation Diameter 0.890 inch - 1.220 inch / 25-31mm, Aluminum Conductor size 2 AWG Stranded Compressed, 1 AWG Solid/Compact.
274AFLR1-C0240
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 15.5kV, Fuse Test Port - Two Direct Test Ports, Small Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm, Aluminum Conductor size 1 AWG Stranded Compressed, 1/0 AWG Solid/Compact.
168FLR3B0270
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Large Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 4/0 AWG Stranded/Compressed.
168FLR3A0220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Large Housing, Cable Insulation Diameter 0.575 inch - 0.740 inch / 15-19mm, Aluminum Conductor size 2 AWG Stranded Compressed, 1 AWG Solid/Compact.
274AFLR1-C0230
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 15.5kV, Fuse Test Port - Two Direct Test Ports, Small Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm, Aluminum Conductor size 1/0 AWG Stranded Compressed, 2/0 AWG Solid/Compact.Frequently Asked Questions
What is the product's primary application?
The Elastimold 274FLR protects light duty underground distribution systems, including sub-loops and radial taps, by replacing existing 200 Amp loadbreak tap elbows.
Does the product include a fuse?
No, the fuse for the 274FLR is ordered separately.
What sealing kit is for jacketed concentric neutral cables?
For jacketed concentric neutral cables, use the 200ECS sealing kit or add suffix "-S" for cables with nominal O.D. within 0.80-1.50 inches.
Are sealing and grounding kits recommended?
Yes, a sealing and grounding kit with the loadbreak elbow is highly recommended for safety purposes.
What items are included in the 274FLR kit?
Each kit contains an elbow connector housing, a crimp connector, a probe lug, lubricant tubes, installation instructions, a crimp chart, and a V.D Cap-Peroxide.
What standards does the 274FLR meet?
The 274FLR meets IEEE 386, ANSI C37.40, ANSI C37.41, and ANSI C37.47, Latest Revision.
Is the fused elbow submersible?
Yes, the Elastimold 274FLR is fully sealed and submersible when used with ECS series sealing kits.
What is the current rating range for the fuse?
The current rating for the fuse is 6-20 Amps.
What is the interrupting capability?
The fused elbow has a symmetrical interrupting capability of 50,000 Amps. It features full-range current-limiting fusing.
What is the nominal fuse voltage?
The nominal fuse voltage for the 274FLR is 16.2kV (Phase to Ground).
How to Install the 274FLR Loadbreak Fused Elbow Connector
This guide provides detailed instructions for the safe installation and assembly of the 274FLR Loadbreak Fused Elbow Connector, including cable preparation, component assembly, and neutral connections. Ensure all safety precautions are followed.
Estimated time: 2h
Tools needed:
Probe Wrench, Torque-limiting Allen Wrench, Wire brush, Crimp tool, Hotstick tool
Supplies needed:
Cable Half Housing, Elbow Half Housing, Fuse, Compression Lug, Probe, Probe Connector, Hose Clamp, Lubricant, No. 14 AWG Copper Wire, Grounding Connector, 200ECS Cold Shrink Cable Seal (optional)
- Prepare the Cable for Termination
De-energize all apparatus before starting. Cut excess cable 20 inches minimum beyond the bushing. Remove the jacket for the specified length and prepare the concentric neutral wires by folding and binding them. Cut 1-1/8 inches squarely from the cable end, taking care not to nick the conductor. Wire brush bare aluminum conductors and immediately install the compression lug, crimping it securely according to the crimp chart. Remove the insulation shield 5-1/2 inches from the lug end and bevel the insulation 1/8 inch maximum. Thoroughly clean the insulation to remove all traces of conductive residue.
- Assemble the Cable Half Housing and Fuse
Apply the supplied lubricant to the outside of the connector, cable insulation, conductive shield, and the cable entrance end of the Fused Elbow cable half housing. Insert the connector and cable into the cable half housing until the top end of the connector protrudes beyond surface 'A'. Insert the threaded terminal end of the fuse into the cable half housing and hand-tighten it into the cable connector. CAUTION: The fuse stud will fracture if over-torqued. Pull the housing up against the bottom of the tightened fuse.
- Install the Probe Connector
Assemble the probe connector to the fuse terminal. Rotate the probe connector so that its flats are perpendicular to the bushing with which it will mate. Lock the probe connector in position by tightening the setscrews using the special torque-limiting allen wrench supplied in the fuse kit. Rotate the cable half of the Fused Elbow so that its test point is perpendicular to the flats on the probe connector.
- Assemble the Elbow Half Housing and Probe
Apply lubricant to the elbow half of the fused elbow and assemble it to the cable half, ensuring the cuff of the cable half overlaps the elbow half by 3/4 inch. Verify that the probe connector faces the opening of the fused elbow half and that the two test points are in line with each other. Insert the probe into the probe connector, pushing on the cable if necessary to align it with the fuse. Start the threads by hand, taking care not to cross-thread. Tighten the probe using the special torque-limiting allen wrench supplied until the wrench bends and remains bent. Position and tighten the hose clamp, but DO NOT OVERTIGHTEN.
- Connect Concentric Neutral Wires
Using a separate copper wire (No. 14 AWG / 2.5mm or equivalent), insert one end through each grounding eye on the elbow housing and cable housings. Twist tightly, taking care not to damage the eyes. If a 200ECS jacket seal is used, finish its installation. Twist all neutral wires, exercising care not to damage grounding eyes, and connect them to ground using an appropriate connector. Provide adequate slack in the wires for elbow operation.
- Connect the Elbow to the Bushing Plug
Lubricate the receptacle portion of the elbow connector and the mating bushing with the lubricant supplied. LUBRICATE ONLY IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE-ENERGIZED. Securely fasten a hotstick to the loadbreak connector pulling eye. Place the elbow connector receptacle over the bushing plug, inserting the elbow male contact until the first slight resistance is felt. Immediately push the elbow home with a fast, firm, straight motion to apply sufficient force to engage the internal lock on the elbow connector and bushing interface. DO NOT OPERATE BY HAND.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.