Authorized ABB Distributor (Installation Products)
ABB - Installation Products 25PCJ1M1320 - 25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 450.

ABB Installation Products 25PCJ1M1320 25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…

UPC: 783786385287


Documents & Media
BrochureInstallation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB 25PCJ1M1320 is a 25kV power cable joint designed for medium-voltage distribution systems requiring reliable, long-term cable connections. This joint accommodates cable insulation diameters between 1.370 and 1.630 inches and supports 450 AWG stranded aluminum conductors, making it suitable for high-capacity power transmission applications. The single-piece housing design simplifies installation while ensuring consistent performance under operational stresses. This joint is engineered for use in utility, industrial, and commercial power distribution networks where 25kV-rated cable systems are deployed. The aluminum conductor compatibility aligns with common utility-grade installations, providing a cost-effective solution without compromising electrical integrity. Installation requires proper cable preparation, including stripping to the specified insulation diameter, conductor trimming, and application of the joint housing to encapsulate the connection. The joint’s design minimizes the risk of partial discharge and dielectric breakdown, critical for maintaining system reliability in medium-voltage networks. Compliance with industry standards for 25kV systems ensures compatibility with existing infrastructure, reducing the need for specialized tooling or additional components. This product is part of ABB’s Installation Products portfolio, a trusted manufacturer in electrical distribution and automation. The SKU 25PCJ1M1320 is optimized for applications such as substation feeder circuits, industrial power distribution, and renewable energy integration where medium-voltage cable joints are required. Ensure proper training and adherence to installation guidelines for optimal performance and safety.
  • Voltage rating: 25 kV for medium-voltage power distribution
  • Cable insulation diameter range: 1.370 to 1.630 inches
  • Conductor size: 450 AWG stranded aluminum
  • Single-piece housing design for simplified installation
  • Compatible with utility, industrial, and commercial power systems

Specifications

Application
For Direct Burial, Vault, Submersible and Other Severe Service Applications
Color
Black
Conductor Range
450 kcmil
Connection
Compression
Insulation
Yes
Material
EPDM Rubber
Number Of Conductors
2
Size
14-3/8 inch long
Special Features
Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable
Standard
IEEE Standard 404
Type
Power Cable Joint
Voltage Rating
25 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
2.5000 L
Package Weight (Metric)
1.1340 kg
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Conductor. Conductor Size AWG Stranded 500. Copper Conductor. Conductor Size AWG Stranded 450.

25PCJ1L2330-2320

25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Conductor. Conductor Size AWG Stranded 500. Copper Conductor. Conductor Size AWG Stranded 450.
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0.

35PCJ1K2250

35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0.
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0.

25PCJ1J1250

25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0.
28kV Power Cable Joint Style 1 with Single Piece Housing for Canada, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0.

28PCJ1H1230

28kV Power Cable Joint Style 1 with Single Piece Housing for Canada, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0.
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.

35PCJ1K1270

35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Conductor. Conductor Size AWG Stranded 550 /Solid 650.

15PCJ1L2340

15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Conductor. Conductor Size AWG Stranded 550 /Solid 650.
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded #2/Solid #1.

25PCJ2H1240-G1220

25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded #2/Solid #1.
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 750. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 450.

15PCJ2M1380-K1320

15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 750. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 450.

Frequently Asked Questions

Can copper connectors be used with aluminum conductors?

No, copper compression connectors are suitable for splicing copper conductors to copper conductors only and should not be used on aluminum conductors.

What is the short-time current rating for PCJ joints?

The short-time current rating for PCJ power cable joints is equal to that of the cable rating, up to 35 kA.

What is the continuous current rating of PCJ joints?

The continuous current rating for PCJ power cable joints is equal to that of the cable rating.

What safety standards do PCJ power cable joints meet?

The shield design of PCJ power cable joints meets the IEEE 592 standard, and the connectors meet ANSI 119.4 Class A and Class 3 ratings.

What is the difference between PCJ Style 1 and Style 2 joints?

Style 1 is for straight splicing of two similar cables. Style 2 includes separate cable adapters for transition splicing between two different cable sizes.

What conductor types and sizes are compatible with PCJ joints?

PCJ power cable joints are compatible with copper or aluminum conductors, supporting a wide range of sizes up to 1250 kcmil.

What voltage classes are PCJ power cable joints available in?

PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.

Where can Elastimold PCJ power cable joints be installed?

These joints can be installed in direct-burial, underground vault, and overhead applications, providing a permanent, fully shielded, and fully submersible splice.

What types of cable splicing can PCJ joints perform?

PCJ power cable joints can perform straight splicing of two similar cables or transition splicing of different cable sizes up to 1250 kcmil.

Can copper connectors be used with aluminum conductors?

No, copper compression connectors are suitable for splicing copper conductors to copper conductors only and should not be used on aluminum conductors.

How to Install the 15/25/35PCJ1 Series Cable Joint

This guide provides step-by-step instructions for the permanent, fully shielded, and submersible installation of the 15/25/35PCJ1 series straight joint for wire shielded cables.

Estimated time: 2h

Tools needed:

Wire brush, Crimping tool, Cable cutting tool, Cable jacket removal tool, Insulation removal tool, Measuring tape or ruler, T&B WT3D tool (recommended for 35kV cable ties)

Supplies needed:

Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Connector (for grounding wires), DELTECt Cable ties (TYD5135, for 35kV ONLY), #14 AWG copper wire or equivalent (if shield wires are smaller than #14 AWG), Inhibitor (if applicable)

  1. De-energize Apparatus

    Ensure all apparatus in the work area are de-energized before beginning installation. Verify with appropriate safety procedures and equipment.

  2. Prepare Cable Lengths

    Overlap both cables and cut them to 12 inches (305mm) from the joint's centerline. Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm). Fold back the shield wires and then cut both cables at the joint's centerline.

  3. Prepare Cable 1 and Store Housing

    Taper the edge of Cable 1's insulation shield from 1/2 inch to 1-1/2 inches (13mm to 38mm). Clean and lubricate the insulation shield. Lubricate the inside bore of the joint housing on both ends. Slide the housing onto Cable 1 up to its shield wires.

  4. Remove Cable Insulation and Shield

    Carefully remove the cable insulation and then the insulation shield from both cables according to the specified 'X' and 'Y' dimensions for your conductor size. Exercise extreme caution to avoid cutting or nicking the cable insulation or conductor.

  5. Install and Crimp Splice

    If conductors are aluminum, wire-brush them immediately before inserting into the splice. Insert conductors into the splice and check the 'Max Check Before' dimension; redo if it exceeds. Crimp the splice following its recommendations. Wipe off any excess inhibitor. Check the distance between cable insulations against the 'Max Check After' dimension; redo if it exceeds. Remove any sharp protrusions or burrs generated during crimping and ensure all metal chips/filings are removed from the splice and joint assembly area. Clean the cables where indicated and lubricate them to create a build-up at the edge of the insulation shield.

  6. Position Joint Housing

    Slide the joint housing into its final position. Ensure proper placement by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield.

  7. Install 35kV Cable Ties (If Applicable)

    For 35kV installations only, install two DELTECt Cable ties on each end of the cable entrance. Position the outer ties approximately 1/4 inch (6mm) from the splice edge, and the second ties approximately 1/4 inch (6mm) from the first, with an offset of their locking heads. Use the T&B WT3D tool (not included) for tightening and trimming.

  8. Prepare Grounding Eye (If Applicable)

    For 35kV installations only, remove and discard the yellow pin from the joint grounding eye.

  9. Connect Grounding Wires

    Retrain the shield wires and secure them to the ends of the joint. Insert one shield wire from Cable 1 (if #14 AWG or larger) through the joint grounding eye, and repeat for Cable 2. If shield wires are smaller than #14 AWG, use a separate #14 AWG copper wire or equivalent. Connect the joint grounding wires and the remaining shield wires using an appropriate connector.

  10. Reconstruct Cable Jacket

    Reconstruct the cable jacket (where applicable) over both cables and the joint housing to complete the installation.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.