ABB Installation Products 25PCJ1J1250 25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786391288
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 25kV voltage rating for medium-voltage applications
- Single-piece housing for simplified installation
- Accommodates cable insulation diameter: 0.980" - 1.180"
- Suitable for aluminum conductors: 2/0 AWG Stranded / 3/0 AWG Solid
- ABB Installation Products quality and reliability
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 2/0 STR AWG , 3/0 SOL AWG |
Connection | Compression |
Insulation | Yes |
Material | Aluminum |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Series | 25kV Power Cable Joint Style 1 |
Size | 14-3/8 inch long |
Size | 0.980 inch to 1.180 inch |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

25PCJ1G2250
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Copper Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0.
28PCJ1H1230
28kV Power Cable Joint Style 1 with Single Piece Housing for Canada, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0.
35PCJ1K1270
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.
15PCJ1L2340
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Conductor. Conductor Size AWG Stranded 550 /Solid 650.
25PCJ2H1240-G1220
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded #2/Solid #1.
15PCJ2M1380-K1320
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 750. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 450.
15PCJ1N2410
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.515 inch to 1.780 inch. Copper Conductor. Conductor Size AWG Stranded 1000.Frequently Asked Questions
What are the available voltage classes?
Elastimold PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
Can aluminum connectors be used with copper cables?
Aluminum compression connectors are suitable for splicing aluminum to aluminum or aluminum to copper conductors.
What material is the housing made from?
The housing is made from pre-molded ethylene propylene diene monomer (EPDM) rubber, offering exceptional protection and long service life.
Can copper connectors be used with aluminum cables?
Copper compression connectors are for copper-to-copper connections only and should not be used on aluminum conductors.
How is a transition joint catalog number constructed?
When constructing a catalog number for a transition joint, list the larger connector first and the smaller connector second.
What standards do the joints meet?
The shield design meets IEEE 592 standard, and the connectors meet ANSI 119.4 Class A and Class 3 ratings. Electrical ratings meet IEEE 404.
What is the pull force withstand capability?
The pin-and-socket interlock of the PCJ power cable joints can withstand a pull force of up to 500 lb.
What is the short-time current rating?
The short-time current rating is equal to that of the cable rating, up to 35 kA.
What is the continuous current rating?
The continuous current rating of the PCJ power cable joint is equal to that of the cable rating.
What is the difference between Style 1 and Style 2?
Style 1 is for straight splicing of two similar cables. Style 2 includes separate cable adapters for transition splicing between two different cable sizes.
How to Install the 15/25/35PCJ1 Straight Joint
This guide provides step-by-step instructions for installing the 15/25/35PCJ1 straight joint, a permanent, fully shielded, and submersible joint for wire shielded cables. Ensure all apparatus is de-energized before beginning installation.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Wire brush, Crimping tool, T&B WT3D tool (for 35kV only)
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Grounding connector (user supplied), DELTECt Cable ties (for 35kV only), No. 14 AWG copper wire (if shield wires are smaller than #14 AWG)
- Prepare Cables for Joint
Overlap both cables and cut them to 12 inches (305mm) from the centerline of the joint. This ensures sufficient length for shield wires to rejoin. Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm). Fold back the shield wires. Cut both cables at the centerline of the joint.
- Prepare Cable 1 and Position Joint Housing
Taper the edge of Cable 1 at least 1/2 inch (13mm) to no greater than 1-1/2 inches (38mm). Clean and lubricate the insulation shield. Lubricate the inside bore of the joint housing on both ends. Slide the housing onto Cable 1 up to the shield wires.
- Remove Cable Insulation and Shield
Carefully remove the cable insulation and then the insulation shield from both Cable 1 and Cable 2. Ensure not to cut or nick the cable insulation or conductor during this process. Refer to the dimension table for 'X' and 'Y' measurements based on conductor size (e.g., 500-750 MCM: X=2 1/2" (64mm), Y=6 1/4" (159mm); 1000 MCM: X=2 3/8" (68mm), Y=6 3/8" (162mm)).
- Install the Conductor Splice
If conductors are aluminum, wire-brush them thoroughly and immediately insert them into the splice. Check the dimension against the 'Max Check Before' table (e.g., 500-750 MCM: 6" (152mm); 1000 MCM: 6 7/8" (156mm)). If it exceeds this, redo the assembly. Crimp the splice following the manufacturer's recommendations provided with the splice. Wipe off any excess inhibitor. Check the distance between cable insulations against the 'Max Check After' table (e.g., 500-750 MCM: 6 1/4" (159mm); 1000 MCM: 6 1/2" (165mm)). If it exceeds this, redo the assembly. Remove any sharp protrusions or burrs generated during crimping. Ensure all metal chips or filings are removed from the splice and joint assembly area before sliding the joint. Clean cables where indicated and lubricate in the direction of the arrows to create a build-up or ramp of lubricant at the edge of the insulation shield.
- Finalize Joint Housing and Grounding
Slide the joint housing into its final position. Ensure proper positioning by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield. For 35kV ONLY: Install two DELTECt Cable ties on each end of the cable entrance. Install the outer ties approximately 1/4 inch (6mm) from the edge of the splice, then install the second ties approximately 1/4 inch (6mm) from the first with an offset of the locking heads. Use the T&B WT3D tool to tighten and trim the ties. Remove and discard the yellow pin from the joint grounding eye. Retrain the shield wires and secure them to the ends of the joint as shown in the diagram. Insert one of the shield wires from Cable 1 (if #14 AWG or larger) through the joint grounding eye, and repeat for Cable 2. If shield wires are smaller than #14 AWG, use a separate #14 AWG copper wire or equivalent. Connect the joint grounding wires and remaining shield wires using an appropriate connector. Reconstruct the cable jacket (where applicable) over both cables and the joint housing.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.