ABB Installation Products 15PCJ1L2340 15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786404636
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV Power Cable Joint Style 1
- Single Piece Housing Design
- For Copper Conductors (AWG 550 Stranded / 650 Solid)
- Cable Insulation Diameter: 1.180" to 1.465"
- Manufacturer: ABB - Installation Products
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 550 kcmil , 650 kcmil |
Connection | Compression |
Insulation | Yes |
Material | Copper |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Series | 15PCJ1L2340 |
Size | 14-3/8 inch long |
Size | 1.180 inch to 1.465 inch |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.7500 L |
Package Weight (Metric) | 0.7940 kg |

15PCJ1M2400
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Conductor. Conductor Size AWG Solid 1000.
25PCJ2H1240-G1220
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0. Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded #2/Solid #1.
15PCJ2M1380-K1320
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 750. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 450.
15PCJ1N2410
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.515 inch to 1.780 inch. Copper Conductor. Conductor Size AWG Stranded 1000.
25PCJ1G2250
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Copper Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0.
25PCJ2J1240
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
15PCJ2K1300
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 350.Frequently Asked Questions
What is the insulation diameter range for this cable joint?
The ABB 15kV Power Cable Joint Style 1 is designed for cable insulation diameters ranging from 1.180 inches to 1.465 inches.
What conductor sizes does this joint accommodate?
This joint is suitable for copper conductors sized AWG 550 stranded or AWG 650 solid.
What is the voltage rating of this ABB cable joint?
The product is a 15kV Power Cable Joint, indicating its suitability for 15,000-volt applications.
Who manufactures this 15kV power cable joint?
This 15kV Power Cable Joint Style 1 is manufactured by ABB - Installation Products.
How to Install a Single Core Cable Joint (15PCJ1L2340)
This guide provides step-by-step instructions for the permanent installation of a fully screened, submersible single core joint for extruded solid dielectric cables. It covers cable preparation, connector installation, and final joint assembly.
Estimated time: 2h
Tools needed:
Wire brush, Crimping tool, Cleaning solvent, Clean cloth, Soldering iron (optional, or constant force spring tool), Heat gun, Sanding tool
Supplies needed:
Joint Housing, Copper or aluminum compression connector, PVC tape, Lubricant, Flat copper braid, Constant force spring (optional, alternative to soldering), Mastic tape, Heat shrink
- Prepare for Installation and Ensure Safety
Ensure all apparatus in the work area are de-energized before beginning installation or removal of any parts. Do not touch or move energized products. This product must be installed only by competent personnel trained in high voltage electrical equipment safety practices. Inspect all parts for damage, correct rating, and compatibility with mating parts.
- Gather Tools and Supplies
Check the package contents to ensure completeness and no damage. Verify all components fit properly with the cable and/or mating products. Read the entire installation instructions thoroughly before starting. Have all required tools readily available and maintain cleanliness throughout the procedure.
- Prepare Cables - Remove Jacket and Metallic Shield
Train both cables into their final position and square cut them, leaving approximately 5mm between the cable ends. Store the heat shrink component onto either cable. Remove the jackets of both cables to the dimensions specified in the provided table. Carefully remove the cable metallic tape screen for the specified distance and secure the ends with PVC tape. Ensure the PVC tape is applied only to the copper tape and does not overlap onto the non-metallic screen.
- Prepare Cables - Remove Non-Metallic Screen and Cut Insulation
Carefully remove the cable non-metallic screen from both cables to the point specified in the table, taking extreme caution not to nick, cut, or damage the insulation surface or conductor strands. Bevel the edge of Cable 1. Cut the insulation to the conductor to dimension 'E' from the end of both cables, but DO NOT remove the insulation. Install a PVC tape marker on Cable 2 to dimension 'B' to locate the splice later.
- Temporarily Store the Joint Housing
Beginning at the jacket and extending 10mm beyond the end of the metallic screen, apply one layer (half-lapped) of PVC tape over the metallic screen on Cable 1. Install a different color PVC tape marker on Cable 1 to dimension 'B' to locate the splice later. Lubricate both cable entrances of the splice housing. Clean and lubricate the insulation, cable non-metallic screen, and the PVC taped portion of the cable metallic tape screen on Cable 1. Store the housing onto Cable 1 up to the jacket. DO NOT store the splice housing on the exposed metallic tape shield. Ensure the forward edge and any other sharp edges of the metallic screen are covered with PVC tape to prevent damage to the joint housing.
- Remove Cable Insulation
Remove the cable insulation from both cables to dimension 'E' from the end of the cable. Exercise extreme care to avoid cutting or nicking the cable insulation or conductor during this step.
- Install the Conductor Connector
Wire brush the exposed conductors of both cables thoroughly. Immediately insert both conductors into the conductor splice, ensuring they are fully seated. DO NOT CRIMP at this stage. Check the distance between the insulations; if it exceeds the 'Before' dimension in the table, review instructions and redo the assembly. Crimp the conductor splice according to the provided crimp chart. Remove any sharp protrusions or burrs and ensure all metal chips or filings are cleared from the splice joint assembly area. Wipe off all excess inhibitor. Recheck the distance between cable insulations; if it exceeds the 'After' dimension in the table, review instructions and redo the assembly.
- Clean and Lubricate the Core
Clean the conductor, connector, and Cable 2 insulation surfaces using cleaning solvent and a clean cloth. Always wipe towards the screen end to remove all contaminants. Lubricate the cable insulation surfaces using the supplied lubricant, wiping towards the screen end to create a build-up or ramp of lubricant at the edge of the non-metallic screen.
- Position the Joint Housing
Slide the joint housing over the crimp connector into its final position. Measure the distance 'X' between the joint housing and the PVC tape marker on each side. Ensure that the distance 'X' is equal on both sides of the joint housing. Remove the PVC tape applied in Step C to expose 25mm of copper tape.
- Restore the Screen
Wrap flat copper braid around each joint housing, extending the ends over the metallic tape screen for 20mm on each side. Attach each end of the copper braid to the metallic tape screen by either soldering or using a constant force spring.
- Restore the Outer Jacket
Lightly sand the outer surface of the jacket of both cables for a distance of 130mm. Heat both sanded areas for approximately 15 seconds, being careful not to burn the cables. Wrap two layers of mastic tape at the edge of the jacket on both cables. Position the heat shrink from Cable 1 over the center of the assembly and shrink it, starting at the center and working towards the ends.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.