ABB Installation Products 25PCJ1J1300 25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786437450
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 25 kV Voltage Rating for medium-voltage applications
- Accommodates cable insulation diameters from 0.980" to 1.180"
- Designed for 350 AWG stranded aluminum conductors
- Single-piece housing for simplified installation
- ABB Installation Products quality and reliability
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 350 kcmil |
Connection | Compression |
Insulation | Yes |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Size | 14-3/8 inch long |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.7500 L |
Package Weight (Metric) | 0.7940 kg |

25PCJ1K1290
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Solid 350.
15PCJ1L2380
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Conductor. Conductor Size AWG Stranded 750.
15PCJ1H1270-1260
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
25PCJ1-M2310
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Conductor. Conductor Size AWG Solid 500.
25PCJ2N1410-L1330
25kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Conductor. Conductor Size AWG Stranded 1000. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded 500.
35PCJ1Q
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.900 inch to 2.120 inch.
15PCJ1LM1380
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.280 inch to 1.430 inch. Aluminum Conductor. Conductor Size AWG Stranded 750.
15PCJ1H2240
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Copper Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.Frequently Asked Questions
What conductor types are compatible with PCJ joints?
The joints can be used with copper or aluminum conductors, supporting a wide range of sizes up to 1250 kcmil.
What are the two styles of PCJ power cable joints?
Style 1 is for straight splicing of two similar cables. Style 2 uses separate cable adapters for transition splicing between different cable sizes.
What is the continuous current rating for PCJ joints?
The continuous current rating for PCJ power cable joints is equal to that of the cable rating.
What is the short-time current rating for PCJ joints?
The short-time current rating is equal to that of the cable rating, up to 35 kA.
What voltage classes are available for PCJ joints?
Elastimold PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
What is the phase-to-ground voltage for the 15 kV class?
For the 15 kV class, the phase-to-ground voltage is 8.7 kV.
What is the BIL impulse withstand for the 35 kV class?
The 35 kV class has a BIL impulse withstand of 300 kV (1.2 x 50 μsec. wave).
What is the corona extinction voltage for the 25 kV class?
For the 25 kV class, the corona extinction voltage is 22 kV with 3 pC sensitivity.
What cable types are compatible with PCJ power cable joints?
They are designed for UD cable with concentric neutral and extruded insulation shielding. They also work with fabric-tape shielded or lead-jacketed cables using proper adapters.
Can copper connectors be used on aluminum conductors?
No, copper compression connectors are suitable for copper-to-copper connections only and should not be used on aluminum conductors.
How to Install the 15/25/35PCJ1 Series Cable Joint
This guide provides detailed instructions for the permanent installation of a fully shielded, fully submersible straight joint for aluminum to aluminum and/or aluminum to copper wire shielded cables. Ensure all apparatus are de-energized before starting.
Estimated time: 2h
Tools needed:
Cable cutting tool, Wire strippers, Wire brush, Crimping tool, T&B WT3D tool (for 35kV only)
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Connector (user supplied, for conductor), DELTECt Cable ties TYD5135 (for 35kV only), No. 14 AWG copper wire or equivalent (for grounding), Appropriate connector (for grounding wires), Cable jacket reconstruction material
- De-energize Apparatus and Inspect Parts
DANGER: Ensure all apparatus are de-energized during installation or removal. Do not touch or move energized products. Inspect all parts for damage, rating, and compatibility with mating parts and cables. Read entire instructions before starting.
- Overlap and Cut Cables to Length
Overlap both cables and cut them to 12 inches (305mm) from the center line of the joint. This ensures sufficient length of shield wires to rejoin over the joint.
- Remove Cable Jacket and Fold Shield Wires
Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm). Fold back the shield wires on both cables.
- Cut Cables at Joint Centerline
Cut both cables precisely at the center line of the joint.
- Taper, Clean, and Lubricate Cable 1 Insulation Shield
Taper the edge of Cable 1 at least 1/2 inch to no greater than 1-1/2 inches (13mm to 38mm). Clean and lubricate the insulation shield. Lubricate the inside bore of the joint housing on both ends.
- Slide Joint Housing onto Cable 1
Slide the joint housing onto Cable 1, moving it up to the shield wires. This procedure will not contaminate electrical interfaces.
- Carefully Remove Cable Insulation and Insulation Shield
Carefully remove the cable insulation and then the insulation shield from both cables according to dimensions 'X' and 'Y' in the diagram. WARNING: DO NOT CUT OR NICK THE CABLE INSULATION OR CONDUCTOR.
- Prepare and Insert Conductors into Splice
If conductors are aluminum, wire-brush them thoroughly. Immediately insert the prepared conductors into the splice. Check the dimension against the 'Max Check Before' table; redo assembly if it exceeds the maximum.
- Crimp the Splice
Crimp the splice following the recommendations provided with the splice. Wipe off all excess inhibitor where applicable. Check the distance between cable insulations against the 'Max Check After' table; redo assembly if it exceeds the maximum.
- Clean Splice and Cables
Remove any sharp protrusions or burrs generated during crimping. Ensure all metal chips or filings are removed from the splice and joint assembly area. Clean the cables where indicated and lubricate in the direction of the arrows to build up a ramp of lubricant at the edge of the insulation shield.
- Slide Housing into Final Position
Slide the joint housing into its final position. Ensure proper positioning by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield.
- Install Cable Ties and Remove Pin (35kV Only)
For 35kV ONLY: Install two DELTECt Cable ties (TYD5135) on each end of the cable entrance, 1/4 inch from the edge of the splice and 1/4 inch from the first tie with offset locking heads. Use a T&B WT3D tool to tighten and trim ties. Remove and discard the yellow pin from the joint grounding eye.
- Retrain and Secure Shield Wires
Retrain the shield wires and secure them to the ends of the joint as shown in the diagram.
- Connect Joint Grounding Wires
Insert one shield wire from Cable 1 (if #14 AWG or larger) through the joint grounding eye; repeat for Cable 2. If shield wires are smaller than #14 AWG, use separate #14 AWG copper wire or equivalent. Connect joint grounding wires and remaining shield wires using an appropriate connector.
- Reconstruct Cable Jacket
Reconstruct the cable jacket (where applicable) over both cables and the joint housing to complete the installation.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.