ABB Installation Products 168FLR1B0180 Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port…
UPC: 783786782826
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Nominal Fuse Voltage Rating: 8.3kV
- Features Two Capacitive Test Ports for easy fuse testing
- Accommodates Cable Insulation Diameters from 0.635 to 0.905 inches (16-23mm)
- Designed for 6 AWG Stranded/Compressed Aluminum Conductors
- Compact molded housing from ABB - Installation Products
Specifications
Amperage Rating | 200 A |
Application | Protect Light Duty Underground Distribution Systems |
Color | Black |
Conductor Range | #6 STR/COMPR AWG |
Insulation | True |
Length | 16.87 in |
Length | 428.498 mm |
Material | Aluminum |
Material | EPDM-Rubber |
Size | Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 6 AWG Stranded/Compressed |
Special Features | Full-Range Current-Limiting Fusing with 50kA Interrupting Capability. Hotstick Operable 15kV Loadbreak Elbow Switching |
Standard | IEEE 386, ANSI C37.40, ANSI C37.41, ANSI C37.47 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Fused Elbow Connector |
Voltage Rating | 8.3 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

168FLR1-A5180
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.575 inch - 0.740 inch / 15-19mm, Bi-Metal, Conductor size 180 - 6 AWG Stranded/Compressed
274FLR3-D0260
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 17.2kV, Fuse Test Port - Two Capactive Test Ports, Large Housing, Cable Insulation Diameter 0.890 inch - 1.220 inch / 25-31mm, Aluminum Conductor size 3/0 AWG Stranded Compressed, 4/0 AWG Solid Compact
168AFLR3-D0270
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Direct Test Ports, Large Housing, Cable Insulation Diameter 0.890 inch - 1.220 inch / 25-31mm, Aluminum Conductor size 4/0 AWG Stranded Compressed.
168FLR1-C0220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm, Aluminum Conductor size 2 AWG Stranded/Compressed, 1 AWG Solid/Compact.
168FLR1-C0210
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm, Aluminum Conductor size 2 AWG Solid/Compact.
274FLR3-C0230
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 17.2kV, Fuse Test Port - Two Capactive Test Ports, Large Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm, Aluminum Conductor size 1 AWG Stranded Compressed, 1/0 AWG Solid Compact
274FLR3-D0220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 17.2kV, Fuse Test Port - Two Capactive Test Ports, Large Housing, Cable Insulation Diameter 0.890 inch - 1.220 inch / 25-31mm, Aluminum Conductor size 2 AWG Stranded Compressed, 1 AWG Solid CompactFrequently Asked Questions
What is the product's primary application?
The Elastimold 168FLR improves distribution system reliability by protecting light duty underground systems, sub-loops, and radial taps. It replaces existing 200 Amp loadbreak tap elbows.
How is a blown fuse indicated on this product?
The product has built-in voltage test points for quick and convenient blown fuse indication.
What is the frequency rating of the device?
The device is rated for a frequency of 50/60 Hz.
What cable insulation diameters are supported?
Supported cable insulation diameters range from 0.575 in to 1.220 in, depending on the specific letter code (A, B, C, or D).
How do I select the correct housing size?
Select the housing size based on the desired fuse size and voltage. Housing 1 is for 3-45A 8.3kV or 6-20A 15.5kV, and Housing 3 is for 65-80A 8.3kV or 3-45A 17.2kV.
What items are included in each kit?
Each kit contains an elbow connector housing, a crimp connector, a probe lug, lubricant tubes, installation instructions, and a crimp chart.
What types of conductors are compatible with the lugs?
Copper compression lugs are suitable for copper conductors only. Bi-metal compression lugs work with copper or aluminum conductors.
Is the fused elbow suitable for submersible applications?
Yes, the fused elbow is fully sealed and submersible.
Can this fused elbow be operated with a hotstick?
Yes, the 15kV Loadbreak Elbow switching is hotstick operable.
What industry standards does the product meet?
The product meets IEEE 386, ANSI C37.40, ANSI C37.41, and ANSI C37.47 standards.
How to Install the 168FLR/274FLR Loadbreak Fused Elbow Connector
This guide provides step-by-step instructions for the safe installation, detailed cable preparation, and complete assembly of the 168FLR or 274FLR Loadbreak Fused Elbow Connector, including critical safety precautions and component integration.
Estimated time: 1h 30m
Tools needed:
Cable cutting tool, Wire strippers, Wire brush, Crimp tool, Probe Wrench (supplied), Allen Wrench (special torque limiting, supplied), Hotstick tool
Supplies needed:
168FLR or 274FLR Loadbreak Fused Elbow Connector kit (includes Cable Half Housing, Elbow Half Housing, Fuse, Compression Lug, Probe, Probe Connector, Hose Clamp, Lubricant), Optional 200ECS Cold Shrink Cable Seal, Copper wire (No. 14 AWG / 2.5mm) or equivalent, HV insulated cap(s) or connector(s) (if replacing shipping covers)
- Perform Initial Inspection and Ensure Safety
Ensure all apparatus is de-energized during installation or removal of parts. Inspect all components for any damage, verify correct ratings, and confirm compatibility with mating parts. Check the package contents for completeness and proper fit with the cable and/or mating products. If the product was supplied with a protective shipping cover, remove it and replace it with the appropriate HV insulated cap(s) or connector(s) before submerging or energizing the circuit. This product must be installed only by competent personnel trained in high voltage electrical equipment safety practices.
- Perform Cable Training
Using the bushing centerline as a reference, cut any excess cable off, ensuring a minimum of 20 inches beyond the bushing. If using an optional 200ECS Cold Shrink Cable Seal, slide it onto the cable now. Remove the jacket from the excess cable length remaining AND the distance of 'A' (11-1/2 inches for FLR-1, 15-3/4 inches for FLR-3) plus 7-3/8 inches from the bushing centerline. If a Cable Seal kit is used, follow its specific instructions. Otherwise, unwrap and fold the Concentric Neutral wires back over the jacket and bind them. Squarely cut off the cable a distance of 'A' from the bushing centerline, leaving a minimum of 7-3/8 inches of cable to terminate.
- Prepare the Cable End
Cut 1-1/8 inches from the cable end, ensuring a square cut and taking extreme care not to nick the conductor. Immediately wire brush the bare aluminum conductors and install the compression lug. Rotate the lug to spread the inhibitor. Crimp the unthreaded end of the compression lug to the conductor, referring to the crimp chart packaged with the compression lug for tool information. Start the crimp at the crimp line mark and rotate 180 degrees for each successive crimp. Carefully wipe any excess inhibitor from the outside of the lug and cable. Remove the insulation shield 5-1/2 inches from the end of the lug. Bevel the insulation end a maximum of 1/8 inch. Thoroughly clean the insulation to remove all traces of conductive residue.
- Lubricate and Assemble Cable Half Housing
Apply the supplied lubricant to the outside of the connector, the cable insulation, the conductive shield, and the cable entrance end of the Fused Elbow cable half. DO NOT SUBSTITUTE the lubricant. Insert the connector and cable into the cable half of the Fused Elbow until the top end of the connector protrudes beyond surface 'A'. This positioning is crucial to allow the fuse to be tightened before it bottoms out on the rubber.
- Install the Fuse
Insert the threaded terminal end of the fuse into the cable half of the Fused Elbow and thread it into the cable connector. HAND TIGHTEN the fuse. CAUTION: The fuse stud will fracture if over-torqued. After hand tightening, pull the housing up against the bottom of the tightened fuse.
- Assemble the Probe Connector
Assemble the probe connector to the fuse terminal. Rotate the probe connector so that its flats are perpendicular to the bushing with which it will mate. Lock the probe connector in position by tightening the setscrews using the special torque-limiting allen wrench supplied in the fuse kit. Rotate the cable half of the Fused Elbow so that the test point is perpendicular to the flats on the probe connector.
- Assemble Elbow Half Housing and Probe
Apply lubricant to the elbow half of the fused elbow and assemble it to the cable half. The cuff of the cable half will overlap the elbow half by 3/4 inch. Ensure the probe connector faces the opening of the fused elbow half and that the two test points are in line with each other. Insert the probe into the probe connector; it may be necessary to push on the cable to get the probe to line up with the fuse. Start the threads by hand, taking care not to cross-thread the probe. To tighten, use the special torque-limiting allen wrench supplied; insert the short end of the wrench into the hole in the probe and tighten until the wrench bends and remains bent. Position the hose clamp as shown in the product diagram and tighten it, but DO NOT OVERTIGHTEN.
- Connect Concentric Neutral Wires
Using a separate copper wire (No. 14 AWG / 2.5mm) or equivalent, insert one end through each grounding eye on the elbow housing and cable housings. Twist tightly, taking care not to damage the grounding eyes. If used, finish installing the 200ECS jacket seal. Twist all neutral wires, exercising care not to damage grounding eyes, and connect them to ground using an appropriate connector. Provide adequate slack in the wires to allow for elbow operation.
- Connect Elbow to Bushing Plug (De-energized)
Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant. IMPORTANT: Lubricate ONLY if the transformer and elbow are known to be de-energized. Operate the connection using a full insulated hotstick tool; DO NOT OPERATE BY HAND. Ensure the area is clear of obstructions or contaminants. Securely fasten a hotstick to the loadbreak connector pulling eye. Place the elbow connector receptacle area over the bushing plug, inserting the elbow male contact (arc follower portion) into the bushing until the first slight resistance is felt. Immediately push the elbow home with a fast, firm, straight motion, applying sufficient force to engage the internal lock on the elbow connector and bushing interface.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.