ABB Installation Products 168FLR1-C0220 Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port…
UPC: 783786796885
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Nominal voltage rating: 8.3kV
- Cable insulation diameter range: 0.805"–1.060" (20–27mm)
- Supports 2 AWG stranded/compressed and 1 AWG solid/compact aluminum conductors
- Two capacitive test ports for safe diagnostic access
- Compact molded housing for space-constrained installations
Specifications
Amperage Rating | 200 A |
Application | Protect Light Duty Underground Distribution Systems |
Color | Black |
Conductor Range | #2 STR/COMPR AWG , #1 SOL/COMPT AWG |
Insulation | True |
Length | 16.87 in |
Length | 428.498 mm |
Material | EPDM-Rubber |
Special Features | Full-Range Current-Limiting Fusing with 50kA Interrupting Capability. Hotstick Operable 15kV Loadbreak Elbow Switching |
Standard | IEEE 386, ANSI C37.40, ANSI C37.41, ANSI C37.47 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Fused Elbow Connector |
Voltage Rating | 8.3 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

168FLR1-B5220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Bi-Metal Conductor size 2 AWG Stranded/Compressed, 1 AWG Solid/Compact. no Sealing Kit
168FLR1-C0210
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm, Aluminum Conductor size 2 AWG Solid/Compact.
274FLR3-C0230
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 17.2kV, Fuse Test Port - Two Capactive Test Ports, Large Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm, Aluminum Conductor size 1 AWG Stranded Compressed, 1/0 AWG Solid Compact
274FLR3-D0220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 17.2kV, Fuse Test Port - Two Capactive Test Ports, Large Housing, Cable Insulation Diameter 0.890 inch - 1.220 inch / 25-31mm, Aluminum Conductor size 2 AWG Stranded Compressed, 1 AWG Solid Compact
168FLR3-B0210
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Large Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 2 AWG Solid/Compact.
168FLR1-A0270
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.575 inch - 0.740 inch / 15-19mm, Aluminum Conductor size 4/0 AWG Stranded/Compressed.
K655LR-M0390
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size kcmil Compressed/Stranded 800.
K655LR-M0380
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size kcmil Compressed/Stranded 700/750 or Compact/Solid 900.Frequently Asked Questions
What voltage rating does this fuse housing support?
The fuse housing is rated for a nominal voltage of 8.3kV.
What cable insulation diameters fit this housing?
The housing accommodates cable insulation diameters from 0.805 inch to 1.060 inch (20-27mm).
What conductor sizes are compatible with this housing?
It supports 2 AWG stranded/compressed and 1 AWG solid/compact aluminum conductors.
Does this housing include test ports?
Yes, it features two capacitive test ports for safe diagnostic access.
What is the material of the fuse housing?
The housing is constructed from aluminum for corrosion resistance.
How to Install the 168FLR/274FLR Loadbreak Fused Elbow Connector
This guide provides step-by-step instructions for preparing the cable, assembling the 168FLR or 274FLR Loadbreak Fused Elbow Connector, and connecting it to a mating bushing.
Estimated time: 1h 30m
Tools needed:
Cable cutter, Wire brush, Crimp tool, Probe wrench, Torque-limiting Allen wrench, Hotstick
Supplies needed:
168FLR/274FLR Loadbreak Fused Elbow Connector kit (includes Cable Half Housing, Elbow Half Housing, Fuse, Compression Lug, Probe, Probe Connector, Hose Clamp, Lubricant), UD cable (concentric neutral, extruded insulation shielding), Optional 200ECS Cold Shrink Cable Seal, 14 AWG / 2.5mm copper wire (for neutral connection), Ground connector, Mating loadbreak bushing or accessory device, Cleaning solution or wipes
- Perform Pre-Installation Checks and Ensure Safety
Before starting, ensure all apparatus are de-energized to prevent serious or fatal injury. This product should only be installed by competent personnel trained in high voltage electrical equipment safety practices. Inspect all components of the 168FLR/274FLR kit for damage, verify ratings, and confirm compatibility with the cable and mating bushing. Read all instructions thoroughly and have all required tools ready.
- Prepare the Cable for Termination
Cut excess cable and remove the jacket according to the specified lengths (refer to the 'Cable Cut Back Diagram' for precise measurements, noting 'A' for fuse body length). If using a cable seal kit, follow its instructions; otherwise, unwrap and bind the concentric neutral wires. Squarely cut the cable end, wire brush bare aluminum conductors, and immediately crimp the compression lug to the conductor, rotating 180 degrees for successive crimps. Remove the insulation shield 5-1/2 inches from the lug end, bevel the insulation 1/8 inch max, and thoroughly clean the insulation to remove all traces of conductive residue.
- Lubricate and Assemble Cable Half with Fuse
Apply the supplied lubricant to the outside of the connector, cable insulation, conductive shield, and the cable entrance end of the Cable Half Housing. Insert the connector and cable into the Cable Half Housing until the top of the connector protrudes beyond surface 'A'. Insert the threaded terminal end of the fuse into the Cable Half Housing and hand-tighten it into the cable connector. CAUTION: Do not overtighten the fuse stud to prevent fracture. Pull the housing up against the bottom of the tightened fuse.
- Attach and Secure the Probe Connector
Assemble the Probe Connector to the fuse terminal. Rotate the Probe Connector so its flats are perpendicular to the mating bushing. Lock the Probe Connector in position by tightening the setscrews using the supplied torque-limiting Allen wrench. Rotate the Cable Half Housing so its test point is perpendicular to the flats on the Probe Connector.
- Assemble Elbow Half and Insert Probe
Apply lubricant to the Elbow Half Housing and assemble it to the Cable Half Housing, ensuring a 3/4-inch overlap and that the Probe Connector faces the opening of the Elbow Half. The two test points should align. Insert the Probe into the Probe Connector, pushing the cable if necessary for alignment. Hand-start the threads carefully to avoid cross-threading. Tighten the Probe using the supplied torque-limiting Allen wrench until the wrench bends and remains bent. Position and tighten the hose clamp, but do not overtighten.
- Connect Concentric Neutral and Ground
Using a separate No. 14 AWG (2.5mm) copper wire, insert one end through each grounding eye on the elbow and cable housings and twist tightly. If used, finish installing the 200ECS jacket seal. Twist all neutral wires together and connect them to ground using an appropriate connector, ensuring adequate slack in wires for elbow operation.
- Connect the Fused Elbow to the Mating Bushing
Lubricate the receptacle portion of the assembled fused elbow connector and the mating bushing with the lubricant supplied. WARNING: Only lubricate if the transformer and elbow are known to be de-energized. Use a fully insulated 'hotstick' type live-line tool for operation; do not operate by hand. Carefully connect the elbow to the bushing following safe operating practices for high voltage electrical equipment.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.