ABB Installation Products 168FLR1-C0210 Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port…
UPC: 783786818914
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Molded Current Limiting Fuse Housing
- Nominal Fuse Voltage Rating: 8.3 kV
- Two Capacitive Test Ports for easy testing
- Accommodates Cable Insulation Diameter: 0.805 - 1.060 inch (20-27mm)
- Designed for 2 AWG Aluminum Conductor (Solid/Compact)
Specifications
Amperage Rating | 200 A |
Application | Protect Light Duty Underground Distribution Systems |
Color | Black |
Conductor Range | #3 STR/COMPR AWG , #2 SOL/COMPT AWG |
Insulation | True |
Length | 16.87 in |
Length | 428.498 mm |
Material | Aluminum |
Material | EPDM-Rubber |
Series | 168FLR1 |
Size | 0.805-1.060 inch / 20-27mm (cable insulation diameter), 2 AWG (conductor size) |
Special Features | Full-Range Current-Limiting Fusing with 50kA Interrupting Capability. Hotstick Operable 15kV Loadbreak Elbow Switching |
Standard | IEEE 386, ANSI C37.40, ANSI C37.41, ANSI C37.47 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Fused Elbow Connector |
Voltage Rating | 8.3 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

168FLR3-A0210
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Large Housing, Cable Insulation Diameter 0.575 inch - 0.740 inch / 15-19mm, Aluminum Conductor size 2 AWG Solid/Compact.
274FLR3-C0230
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 17.2kV, Fuse Test Port - Two Capactive Test Ports, Large Housing, Cable Insulation Diameter 0.805 inch - 1.060 inch / 20-27mm, Aluminum Conductor size 1 AWG Stranded Compressed, 1/0 AWG Solid Compact
274FLR3-D0220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 17.2kV, Fuse Test Port - Two Capactive Test Ports, Large Housing, Cable Insulation Diameter 0.890 inch - 1.220 inch / 25-31mm, Aluminum Conductor size 2 AWG Stranded Compressed, 1 AWG Solid Compact
168FLR3-B0210
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Large Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 2 AWG Solid/Compact.
168FLR1-A0270
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.575 inch - 0.740 inch / 15-19mm, Aluminum Conductor size 4/0 AWG Stranded/Compressed.
K655LR-M0390
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size kcmil Compressed/Stranded 800.
K655LR-M0380
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size kcmil Compressed/Stranded 700/750 or Compact/Solid 900.
K655LR-M0360
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size kcmil Compressed/Stranded 650 or Compact/Solid 750 or mm2 Compact 400.Frequently Asked Questions
What is the voltage rating of this fuse housing?
The ABB 168FLR1-C0210 molded current limiting fuse housing has a nominal fuse voltage rating of 8.3 kV.
What cable insulation diameters can this housing accommodate?
This housing is designed to accommodate cable insulation diameters ranging from 0.805 inch to 1.060 inch, which is equivalent to 20-27mm.
What size aluminum conductor is compatible with this housing?
The housing is compatible with 2 AWG aluminum conductors, available in solid or compact configurations.
Does this fuse housing have test ports?
Yes, the ABB 168FLR1-C0210 features two capacitive test ports for convenient fuse testing.
Who is the manufacturer of this fuse housing?
This molded current limiting fuse housing is manufactured by ABB - Installation Products.
How to Install the 168FLR/274FLR Loadbreak Fused Elbow Connector
This guide provides step-by-step instructions for the safe and proper installation of the 168FLR or 274FLR Loadbreak Fused Elbow Connector, including cable preparation, component assembly, and neutral grounding.
Estimated time: 1h 30m
Tools needed:
Probe Wrench, Torque Limiting Allen Wrench, Wire Brush, Crimp Tool, Hotstick
Supplies needed:
Cable Half Housing, Elbow Half Housing, Fuse, Compression Lug, Probe, Probe Connector, Hose Clamp, Lubricant, No. 14 AWG Copper Wire, 200ECS Cold Shrink Cable Seal (optional)
- Prepare for Installation and Safety Check
Ensure all apparatus is de-energized before beginning installation to prevent serious injury. Inspect all package contents for completeness and damage. Verify all components fit properly with the cable and mating products. Read all instructions thoroughly and have all required tools ready, maintaining cleanliness throughout the procedure.
- Train the Cable
Using the bushing centerline as a reference, cut excess cable at least 20 inches beyond the bushing. If using, slide the optional 200ECS Cold Shrink Cable Seal onto the cable. Remove the cable jacket for a length of 'A' + 7-3/8 inches from the bushing centerline. If not using a cable seal kit, unwrap and fold the concentric neutral wires back over the jacket and bind them. Squarely cut the cable a distance of 'A' from the bushing centerline, leaving a minimum of 7-3/8 inches of cable to terminate.
- Prepare the Cable End
Cut 1-1/8 inches squarely from the cable end, taking care not to nick the conductor. Wire brush the bare aluminum conductors and immediately install the compression lug. Rotate the lug to spread the inhibitor. Crimp the unthreaded end of the compression lug to the conductor, following the crimp chart and rotating 180 degrees for each successive crimp. Carefully wipe any excess inhibitor from the lug and cable. Remove the insulation shield 5-1/2 inches from the end of the lug and bevel the insulation end by a maximum of 1/8 inch. Thoroughly clean the insulation to remove all traces of conductive residue.
- Lubricate and Insert Cable Half Housing
Apply the supplied lubricant to the outside of the connector, the cable insulation, the conductive shield, and the cable entrance end of the Fused Elbow cable half. Insert the connector and cable into the cable half of the Fused Elbow until the top end of the connector protrudes beyond surface 'A'.
- Install and Tighten the Fuse
Insert the threaded terminal end of the fuse into the cable half of the Fused Elbow and thread it into the cable connector. Hand tighten the fuse; do not overtighten as the fuse stud will fracture. Pull the cable half housing up against the bottom of the tightened fuse.
- Assemble and Lock the Probe Connector
Assemble the probe connector to the fuse terminal. Rotate the probe connector so its flats are perpendicular to the bushing with which it will mate. Lock the probe connector in position and tighten the setscrews using the special torque limiting allen wrench supplied in the fuse kit. Rotate the cable half of the Fused Elbow so that the test point is perpendicular to the flats on the probe connector.
- Assemble Elbow Half and Probe
Apply lubricant to the elbow half of the fused elbow and assemble it to the cable half, ensuring the cuff of the cable half overlaps the elbow half by 3/4 inch. Verify the probe connector faces the opening of the fused elbow half and that the two test points are in line. Insert the probe into the probe connector, pushing on the cable if necessary to align it with the fuse. Start the threads by hand, avoiding cross-threading. Tighten the probe using the special torque limiting allen wrench, inserting the short end into the hole in the probe and tightening until the wrench bends and remains bent. Position the hose clamp as shown in the diagram and tighten it, but do not overtighten.
- Connect Concentric Neutral Wires
Using a separate No. 14 AWG (2.5mm) copper wire or equivalent, insert one end through each grounding eye on the elbow housing and cable housings. Twist the wire tightly, being careful not to damage the eyes. If used, finish installing the 200ECS jacket seal. Twist all neutral wires and connect them to ground using an appropriate connector, ensuring adequate slack for elbow operation.
- Make Final Connection to Bushing
Lubricate the receptacle portion of the elbow connector and the mating bushing ONLY if the transformer and elbow are confirmed to be de-energized. Use a full insulated 'hotstick' type live-line tool to connect the elbow to the bushing. DO NOT operate by hand.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.