ABB Installation Products 162LR-C5270-S 200 Amp, 15kV, Loadbreak Elbow Connector, Cable Insulation Diameter 0.805 inch to 1.060…
UPC: 075114188074
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 200 Amp, 15kV loadbreak elbow connector for medium-voltage applications
- Accommodates cable insulation diameters from 0.805" to 1.060"
- Bi-metal compression lug for 4/0 AWG compressed stranded, 250 AWG solid, or 126.67 mm² conductors
- Includes 200ECS jacket seal for environmental protection
- Designed for hot-line maintenance and load switching operations
Specifications
Amperage Rating | 200 A |
Application | 15kV, 200 Amp |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Connection | Push-In |
Connection Type | Loadbreak Elbow |
Current Rating | 200 A |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Material | Bi-Metal Compression Lug |
Series | 162LR |
Size | 7.76 inch (197.1 mm) X 9.03 inch (229.4 mm), 2.92 inch (74.2 mm) Diameter |
Size | 0.805" - 1.060" |
Special Features | 15kV, 200 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for hot stick operation. Provision for ground wire connection. Wide cable range with minimum number of sizes. Long bi-metal compression lug is standard. Non-corrosive capacitive test point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Elbow Connector with Test Point |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

162LR-D5270-S
200 Amp, 15kV, Loadbreak Elbow Connector, Cable Insulation Diameter 0.890 inch to 1.220 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67. 200ECS Jacket Seal Included.
162LR-C5250
15kV 200 Amp, Loadbreak Elbow Connector with Test Point, .805 inch - 1.060 Inch Cable Insulation Diameter, 2/0 Stranded Wire Size, Bi-Metal Compression Lug
162LR-C5250-SG3
200 Amp, 15kV, Loadbreak Elbow Connector, Cable Insulation Diameter 0.805 inch to 1.060 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43. 200ECS-G3 Jacket Seal and Grounding Kit Included.
162LR-C5260
15kV 200 Amp, Loadbreak Elbow Connector with Test Point, .805 inch - 1.060 Inch Cable Insulation Diameter, 3/0 Stranded Wire Size, Bi-Metal Compression Lug
162LR-C5250-S
200 Amp, 15kV, Loadbreak Elbow Connector, Cable Insulation Diameter 0.805 inch to 1.060 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43. 200ECS Jacket Seal Included.
162LR-C5270-SG3
200 Amp, 15kV, Loadbreak Elbow Connector, Cable Insulation Diameter 0.805 inch to 1.060 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67. 200ECS-G3 Jacket Seal and Grounding Kit Included.
162LR-C5270
15kV 200 Amp, Loadbreak Elbow Connector with Test Point, .805 inch - 1.060 Inch Cable Insulation Diameter, 4/0 Stranded Wire Size, Bi-Metal Compression Lug
162LR-C5240
15kV 200 Amp, Loadbreak Elbow Connector with Test Point, .805 inch - 1.060 Inch Cable Insulation Diameter, 1/0 Stranded Wire Size, Bi-Metal Compression LugFrequently Asked Questions
What is the maximum operating voltage for this elbow connector?
The ABB 162LR-C5270-S is rated for 15kV operation.
What is the current rating of the 162LR-C5270-S connector?
This loadbreak elbow connector has a current rating of 200 Amps.
What cable insulation diameters can this connector accommodate?
The connector is designed for cable insulation diameters ranging from 0.805 inches to 1.060 inches.
What type of lug is included with this connector?
The 162LR-C5270-S features a bi-metal compression lug for secure conductor termination.
What conductor sizes are compatible with this connector?
It is compatible with compressed stranded conductors sized 4/0 AWG, solid conductors sized 250 AWG, or metric sizes up to 126.67 mm².
Does the connector come with a jacket seal?
Yes, the 200ECS jacket seal is included with the 162LR-C5270-S.
How to Install 161LR/162LR Loadbreak Elbow Connectors
This guide provides step-by-step instructions for preparing the cable, assembling the elbow connector, grounding, and connecting the 161LR or 162LR Loadbreak Elbow Connectors to a 15kV class bushing.
Estimated time: 1h 30m
Tools needed:
Probe Wrench, Wire brush, Crimp tool, Hotstick, Suitable sensing device (for 162LR only), Wire strippers, Cable cutting tool
Supplies needed:
Elbow Connector Housing (161LR or 162LR), Compression Lug, Probe, Lubricant (supplied, do not substitute), Copper grounding wire (No. 14 AWG / 2.5mm or equivalent), Appropriate neutral connector
- Initial Safety and Component Inspection
Before beginning, ensure all apparatus is de-energized. Inspect the elbow connector housing, compression lug, and probe for any damage and confirm compatibility with your cable and mating products. Thread the probe into the compression lug by hand to check for smooth operation. Gather all necessary tools and maintain a clean work area.
- Cable Training and Outer Jacket Preparation
Train the cable to allow sufficient slack for operation. Based on your cable type (non-jacketed concentric neutral, jacketed concentric neutral, jacketed with drain wires, or jacketed copper tape shield), follow the specific instructions in the documentation to remove the outer jacket and prepare the neutral or drain wires to the specified lengths. If using a cold shrink sealing kit, slide the cold shrink tube onto the cable at this stage.
- Conductor and Insulation Preparation
Remove the insulation shield and insulation 2-1/8” (55mm) from the cable end, ensuring a square cut without nicking the conductor. Wire brush bare aluminum conductors and immediately install the compression lug, rotating it to spread inhibitor. Align the lug's threaded hole with the bushing bore and crimp according to the lug's instructions, rotating 180 degrees for successive crimps. Carefully wipe excess inhibitor. Remove the insulation shield 6-7/8” (175mm) from the lug end and bevel the insulation end 1/8” (5mm) maximum. Thoroughly clean the insulation.
- Elbow Assembly
Lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant; do not substitute. Slide the elbow connector onto the cable using a back-and-forth twisting motion, then wipe off any excess lubricant. Align the elbow with the compression lug’s threaded hole. Thread the probe into the lug by hand, ensuring it turns freely for approximately four turns before becoming snug. Tighten the probe with the supplied wrench until the wrench bends.
- Grounding and Neutral Connection
Insert one end of a separate copper wire (No. 14 AWG / 2.5mm or equivalent) through the grounding eye on the elbow and twist tightly. Twist all concentric neutral wires together and connect them to ground using an appropriate connector, ensuring adequate slack for elbow operation. If using a cold shrink grounding kit, refer to its specific instructions.
- Connect Elbow to Bushing
CONFIRM THAT THE TRANSFORMER AND ELBOW ARE DE-ENERGIZED before proceeding. Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant. Securely fasten a hotstick to the loadbreak connector pulling eye. Insert the probe tip approximately 2” (50mm) into the bushing, then immediately push the elbow home with a fast, firm, straight motion to engage the internal lock. DO NOT OPERATE BY HAND.
- Perform Voltage Test (162LR only)
For 162LR models, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: Use a suitable sensing device designed for capacitive test points to determine if the cable is energized; do not use conventional voltage measuring equipment. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means. After testing, clean the inside surface of the cap, lubricate with silicone lubricant, and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.