ABB Installation Products 15PCJ2J1240 15kV, Power Cable Joint, Style 2 with Universal Housing and Separate Cable Adapters that…
UPC: 075114307147
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV Voltage Rating
- Style 2 Power Cable Joint
- Universal Housing with Separate Cable Adapters
- Insulation Diameter: .980 - 1.180 inches
- For Aluminum Conductors: 1/0 Stranded/Compressed or 2/0 Solid/Compact
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 1/0 STR AWG , 2/0 SOL AWG |
Connection | Compression |
Insulation | Yes |
Material | Aluminum |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Size | 16-3/8 inch long |
Size | Insulation Diameter 0.980-1.180 inches |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

15PCJ1M2400
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Conductor. Conductor Size AWG Solid 1000.
15PCJ2J2290-H2270
15kV, Power Cable Joint, with Universal Housing and separate Cable Adapters that can be varied with the cable application, Cable Insulation .980-1.180 inches, Copper Compression Lug, Conductor Size 350 Compact/Solid to Cable Insulation .850-1.050 inches, Copper Compression Lug, Conductor Size 4/0 Stranded/Compressed or 250 Compact/Solid
15PCJ1N1410
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Conductor. Conductor Size AWG Stranded 1000.
15PCJ1M1400
15 kV, Power Cable Joint, Style 1 - 14-3/8 X 2-25/32 inches, Cable Insulation Diameter - 1.370-1.630 inches, Aluminum Connector, Conductor Size - 1000 kcmil.
25PCJ1H1280
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 250
35PCJ1-H
35kV, PCJ - Power Cable Joint, with Single Piece Housing, Cable Insulation Diameter .850 - 1.050 inches, Housing Only
35PCJ1K1330
35kV Power Cable Joint Style 1, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 500 /Solid 600 /mmSquared 250/300.
35PCJ1H1280
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Compressed Stranded 250 /Solid 300.Frequently Asked Questions
What voltage classes are available for PCJ joints?
Elastimold PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
What type of connector is included for aluminum-to-copper splicing?
Kits for aluminum-to-aluminum or aluminum-to-copper splicing include an aluminum compression connector.
Can copper connectors be used with aluminum conductors?
No, copper compression connectors are suitable for copper-to-copper connections only and should NOT be used on aluminum conductors.
How are transition joints catalog numbers constructed?
When constructing a catalog number for a transition joint, the larger connector is listed first, followed by the smaller connector.
What standards do PCJ joint connectors meet?
PCJ joint connectors meet ANSI 119.4 Class A and Class 3 ratings. The shield design meets IEEE 592 standard.
What is the phase-to-ground voltage for a 35 kV class joint?
For a 35 kV class PCJ joint, the phase-to-ground voltage is 20.2 kV.
What is the BIL impulse withstand for a 15 kV class joint?
A 15 kV class PCJ joint has a BIL impulse withstand of 110 kV with a 1.2 x 50 μsec. wave.
What is the short-time current rating for PCJ joints?
The short-time current rating for PCJ power cable joints is equal to that of the cable rating, up to 35 kA.
What is the continuous current rating of PCJ joints?
The continuous current rating for PCJ power cable joints is equal to that of the cable rating.
Do PCJ joints require taping for cable entrance?
No, the cable entrance engages the insulation shielding of the cable, which eliminates the need for taping during installation.
How to Install the 15PCJ2J1240 Cable Joint
This guide provides step-by-step instructions for the permanent, fully shielded, and submersible installation of the 15PCJ2J1240 straight joint for aluminum and/or copper conductor, wire shielded cables. It covers cable preparation, adapter and collar installation, splicing, and final assembly.
Estimated time: 3h
Tools needed:
Stripping guide, Circular cutting tool or glass scraper, Wirebrush, Hex wrench, Crimping tool, Wire strippers, Multimeter
Supplies needed:
Joint Housing, Splice (Conductor Contact), Cable Adapters, Lubricant, Retaining Collars, Hose Clamp, Electrical tape, Appropriate electrical connector (for grounding wires), #14 AWG copper wire or equivalent (if needed), Heat/cold shrink material (for cable jacket reconstruction), Bonding cable(s), insulating and sealing tapes, solder, CNW’s connectors (if needed for lead sheath and/or neutral wires/tapes)
- Initial Safety and Cable Preparation
DANGER: Ensure all apparatus is de-energized before starting installation. Inspect all components for damage, proper rating, and compatibility with mating parts. Using the stripping guide, carefully remove the cable jacket of both cables for a distance of 11-1/4” (285.7mm). Fold back the shield wires and tape the end of the wires on Cable 1 to the jacket, allowing enough extra length to rejoin later. Clean the surface of the insulation shield, shield wires, and jacket for a distance of 30” (760mm). Slide the joint housing onto Cable 1 to a distance of 30” (760mm). Lubricate 11-1/4” (285.7mm) of the cable.
- Prepare Cable Insulation
Using the stripping guide, carefully remove the insulation shield and cable insulation. CAUTION: DO NOT CUT OR NICK THE INSULATION, as this could result in failure of the assembly. Wrap two turns of electrical tape 1” (25mm) from the edge of the insulation shield on both cables to serve as a marker. Clean the cable insulation, then lubricate it to provide a build-up or ramp of lubricant at the edge of the insulation shield.
- Install Cable Adapters and Retaining Collars
Take one cable adapter and lubricate the inside of both ends. Install the cable adapter onto the cable until it meets the tape marker. Repeat this process for the other cable adapter. Select the appropriate retaining collar and partially thread the setscrews (refer to instructions packaged with the collars). Position the retaining collar over the insulation and flush against the cable adapter. Using the supplied hex wrench, tighten each set screw only one or two turns at a time to keep the collar centered over the insulation. Continue to tighten the set screws until they are below the surface of the collar. Repeat this entire process for Cable 2.
- Splice Installation
Thoroughly clean the ends of the cable adapters and the cable where shown. Install the hose clamp around the adapter on the opposite side of the splice from where the housing is stored, to hold the adapter in place during final assembly. Tape over the hose clamp to form a smooth surface. Wirebrush the exposed conductors of both cables and immediately insert them into the splice. Ensure the “Check” dimension does not exceed 8-1/2” (215mm); if it does, redo the assembly. Crimp the splice following the recommendations provided with it. Wipe off all excess inhibitor, then check the distance between the cable adapters. If it exceeds 8-3/4” (222mm), redo the assembly. Clean and lubricate the outside surface of the cable adapters before sliding the housing into its final position.
- Complete Joint Assembly and Grounding
Slide the housing into its final position, centering it over the cable adapters. Remove all tape, ensuring that no cable or adapter insulation is exposed after positioning the joint. Reshape the shield wires and secure them to the ends of the joint as shown. Insert one of the shield wires from Cable 1 (if #14 AWG or larger) through the joint grounding eye. Repeat this for Cable 2. If shield wires are smaller than #14 AWG, use a separate #14 AWG copper wire or equivalent. Connect the joint grounding wires and the remaining shield wires using an appropriate connector. Reconstruct the cable jacket (where applicable) over both cables and also over the joint housing, using user-supplied heat or cold shrink material.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.