Overview
- Designed for cables with 0.930 to 1.040 inches insulation diameter.
- Provides effective tape and lead shielding for cable protection.
- Manufactured by ABB - Installation Products.
- Essential cable accessory for industrial electrical installations.
- Ensures proper termination of shielded cables.
Specifications
Application | Used to Mate and Install the Cable to an Elastimold Product |
Connection | Slide-On |
Material | EPDM-Rubber |
Size | Cable Insulation Diameter .930 to 1.040 inches |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Shield Adapter |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 0.1500 L |
Package Weight (Metric) | 0.0680 kg |

150-TB-2
15/25kV, T-Splice 6-3/4 inch Long Bail Assembly, Made of Stainless Steel, Used for Assisting Cable to Transformer Connections. Non-Current Carrying. The 150TB2 bailing assembly kit consists of a modified hold down bail for securing Elastimold® tee splice K150T to a K150DP Deadbreak insulating plug. This assembly provides positive hold down force between the tee splice and the insulating plug.Frequently Asked Questions
What is the purpose of the 10TL-W product?
The 10TL-W is a shield adapter part number designed for Unishield Cables. The "W" code is determined by the cable's insulation diameter.
How do I select the correct 10TL-W adapter code?
The correct "W" letter code for the 10TL-W adapter is determined by the insulation diameter of your Unishield cable. Refer to the provided table for specific diameter ranges.
What insulation diameter does the 10TL-GH adapter fit?
The 10TL-GH adapter is suitable for Unishield cables with an insulation diameter between 0.930 and 1.040 inches (23.6 to 26.4 mm).
What is the purpose of the 10TL-W product?
The 10TL-W is a shield adapter part number designed for Unishield Cables. The "W" code is determined by the cable's insulation diameter.
How do I select the correct 10TL-W adapter code?
The correct "W" letter code for the 10TL-W adapter is determined by the insulation diameter of your Unishield cable. Refer to the provided table for specific diameter ranges.
What insulation diameter does the 10TL-GH adapter fit?
The 10TL-GH adapter is suitable for Unishield cables with an insulation diameter between 0.930 and 1.040 inches (23.6 to 26.4 mm).
What is the purpose of the 10TL-W product?
The 10TL-W is a shield adapter part number designed for Unishield Cables. The "W" code is determined by the cable's insulation diameter.
How do I select the correct 10TL-W adapter code?
The correct "W" letter code for the 10TL-W adapter is determined by the insulation diameter of your Unishield cable. Refer to the provided table for specific diameter ranges.
What insulation diameter does the 10TL-GH adapter fit?
The 10TL-GH adapter is suitable for Unishield cables with an insulation diameter between 0.930 and 1.040 inches (23.6 to 26.4 mm).
What is the part number for a cable with 0.865 to 0.950 inch insulation?
For a Unishield cable with an insulation diameter between 0.865 inches and 0.950 inches, the corresponding part number is 10TL-GB.
How to Install the 10TL Adapter for Flat Metallic Tape Shielded Cable
This guide details the installation of the 10TL adapter for cables with flat metallic tape insulation shields, preparing the cable and integrating the adapter with an Elastimold distribution product. Ensure all apparatus are de-energized before starting.
Estimated time: 1h
Tools needed:
Knife, Rag, Soldering iron, Wire strippers
Supplies needed:
10TL Adapter housing, Lubricant (DO NOT SUBSTITUTE), 3/4 inch (19mm) wide PVC insulating electrical tape, Vinyl plastic electrical tape, Approved safety solvent, #14 AWG (2.08mm²) wire, Grounding lead, Elastimold distribution product
- Prepare Cable Outer Jacket
De-energize all apparatus. Refer to the Elastimold product instructions for the semiconductive shield removal dimension. Remove the cable's outer jacket a distance of 2 inches (51mm) more than this specified dimension.
- Remove Metallic Tape
Carefully remove the metallic tape, ensuring it is cut back to a point 3/4 inch (19mm) from the edge of the remaining outer jacket.
- Remove Semiconducting Tape
Remove the semiconducting tape, cutting it back to a point 1 inch (25mm) from the edge of the outer jacket, exposing the insulation.
- Apply Retainer and Marker Tapes
Wrap 1.5 to 2 turns of 3/4 inch (19mm) wide PVC insulating electrical tape over the semiconducting and metallic tapes, 1/2 inch (13mm) from the outer jacket edge, to create a retainer. Then, wrap 2 turns of vinyl plastic electrical tape over the outer jacket, 1 inch (25mm) from its edge, to create a tape marker.
- Clean and Lubricate Cable and Adapter
Clean the outer jacket and thoroughly clean the cable insulation using a rag soaked with an approved safety solvent, wiping from the cable end towards the outer jacket. Ensure all semiconducting residue is removed. Lubricate the prepared cable section and the inside of the 10TL adapter with the supplied lubricant.
- Install the 10TL Adapter
Slide the 10TL adapter onto the cable using a forward side-to-side twisting motion. Continue until the adapter is flush with the previously applied tape marker. The adapter's step will serve as a guide for subsequent Elastimold product assembly.
- Install Elastimold Product
Install the specific ELASTIMOLD distribution product by following its dedicated installation instructions. After installation, verify that the gap between the Elastimold product and the step on the 10TL adapter is no more than 1/8 inch (3mm).
- Remove Tape Marker
Once the ELASTIMOLD product is fully assembled, carefully remove the vinyl plastic tape marker from the cable.
- Ground Metallic Shielding Tape
Approximately 2 inches (51mm) back from the end of the 10TL adapter, remove 1.5 inches (38mm) of the outer cable jacket. Use #14 AWG (2.08mm²) wire to make several wraps, fastening a grounding lead to the metallic shielding tape. Solder the grounding lead to the metallic tape, being careful to avoid excessive heat that could damage the cable. After soldering, wrap the soldered area with electrical insulating tape, overlapping each cable jacket by approximately 1.5 inches (38mm).
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.