Contact for Pricing
Overview
- Click-Fit design quickly installs into enclosure wall; no tools or screws required
- Opens with the flick of a finger for easy filter replacement
- Enclosure side wall mounting
- Reverse airflow option on HF13 models available to push/pull air through higher static pressure
- Standard rope gasket provides proper seal to the enclosure
- Similar cut-out sizes as other filter fan manufacturers
- Terminal block connections
- Optional thermostat available to save energy and extend service life
- Hinged grille remains attached after opening
- Size rage from 4 inch (102 mm) to 13 inch (325 mm)
Specifications
Airflow | 12 ft³/min |
Airflow | 20 m³/h |
Amperage Rating | 0.16/0.14 A |
Application | Controls and Drives;Power Distribution |
Color | Black |
Color | Graphite Black |
Color Code | RAL 9011 |
Depth | 3.98 in |
Depth | 101 mm |
Finish | Black;Smooth Matte |
Finish | Smooth Matte |
Flow Rate | 12 CFM |
Height | 6.15 in |
Height | 156 mm |
Housing Material | Non-metallic |
Material | Plastic |
Max Current | 0.16 A |
Nominal Voltage | 115 V |
Operating Temperature | -40 to 60 |
Operating Temperature | 14-131 °F |
Size | 6.15 x 6.16 x 3.98 in |
Type | Fans and Filter Fans |
Voltage AC | 100-100 V |
Voltage Rating | 115 VAC |
Weight | 2.1 lb |
Weight | 0.8 kg |
Width | 156 mm |
Width | 6.16 in |
Package Dimensions (L x W x H) | 8.3 IN x 8.3 IN x 8.5 IN |
Package Dimensions (L x W x H) | 21.082 cm x 21.082 cm x 21.59 cm |
Package Weight (Imperial) | 2.100 L |
Package Weight (Metric) | 0.953 kg |
How to Install the Side-Mount Filter Fans and Grilles
This guide provides step-by-step instructions for installing side-mount filter fans and grilles in an enclosure.
Estimated time: 45m
Tools needed:
Screwdriver, Wire strippers, Drill, Multimeter
Supplies needed:
Mounting screws, Terminal connectors, Cutout template
- Prepare the enclosure
Apply the cutout template to the desired location on the side of the enclosure.
- Cut the hole
Cut out the hole in the enclosure according to the appropriate size for the model you purchased.
- Deburr the edges
Deburr the cutting edge of the hole to ensure a smooth finish and prevent injury.
- Insert the fan or grille
Push the fan or grille into the opening until all four corners are snapped and locked in place.
- Install mounting fasteners
If the enclosure material thickness is between .10 (2.5 mm) and .14 (3.5 mm), install mounting fasteners. For thickness greater than .14 (3.5 mm), fasteners are required.
- Remove the grille for fastener installation
If necessary, remove the grille by pulling from the top at a 45° angle, then from the bottom.
- Drill mounting holes
Drill out the mounting holes in the filter housing using a 1/8 (3 mm) drill bit for model HF04 or a 5/32 (4 mm) drill bit for models HF05, HF09, HF10, and HF13.
- Torque fasteners
Torque the fasteners to 20-25 in-lbs (2.3-2.8 Nm) to secure the installation.
- Verify clearance
Ensure that the installed filter fan has a minimum clearance of 7.00 (178 mm) from any obstruction.
- Wire the filter fan
Follow the wire diagrams provided in the manual for the appropriate model to wire the filter fan correctly.
Frequently Asked Questions about nVent
What industries and applications are nVent products used for?
nVent products are engineered for critical infrastructure and industrial applications across multiple demanding sectors. Key markets include Construction, Data Centers, Defense, Healthcare, Mining, Oil & Gas Refineries, Power Plants, Rail/Transit, Renewable Energy, Security, Ship Building, Steel Mills, Telecom, and Utilities. Their solutions are designed to withstand extreme environmental conditions, with temperature ranges from -55°C to 105°C and specialized features like UV resistance, oil resistance, and flame resistance.
What environmental ratings do nVent products have?
nVent enclosures feature comprehensive environmental ratings, including UL 508A, CSA, and NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications. They are rated IEC 60529 IP66, providing robust protection against dust, water, and corrosion in both indoor and outdoor environments. These products operate effectively in temperatures ranging from -40°F to 266°F, with enhanced UV inhibitors for outdoor weathering and oil-resistant gaskets for superior sealing.
What accessories are available for nVent products?
nVent offers a comprehensive range of accessories across multiple product lines, including EMC accessories like bonding cable clamps and strain reliefs, inline accessories such as lock inserts and mounting brackets, CONCEPT accessories including panel conversion kits and rack-mount angles, and seismic accessories for specialized mounting requirements. Key accessory categories include grounding kits, DIN rail mounting solutions, panel supports, handles, and various mounting hardware compatible with different enclosure types.
What certifications and standards do nVent products comply with?
nVent products meet critical international certifications including UL (United States), CSA (Canada), CE (European Community), and EAC (Russia). Our products are designed to comply with rigorous industrial standards such as NEMA enclosure ratings, IEC 60529 IP ratings, and international safety standards across multiple industrial markets including oil & gas, power, manufacturing, and infrastructure.
What is nVent's warranty policy?
nVent offers a standard 18-month warranty from invoicing date for most automation products, covering defects in workmanship and materials. The warranty requires proper transportation, handling, storage, and installation within specified environmental conditions. Warranty coverage includes repair or replacement at nVent's discretion, with certain conditions such as authorized service repairs and operation within designed capacity limits.
What technical support does nVent offer?
nVent offers comprehensive technical support through multiple global contact centers across North America, South America, Europe, Middle East, India, and Asia. Customers can reach technical experts by phone at regional numbers, with the North American headquarters in Minneapolis, MN providing primary support at +1.763.421.2240. Additionally, nVent provides online support resources through their website, including CAD drawing downloads and an 'Ask The Expert' feature to assist with product technical inquiries.