ABB Installation Products R2T15J2-N0270 Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84 - 1.38…
UPC: 783786850266
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Designed for 15KV outdoor applications
- Accommodates cable insulation diameters from 0.84 to 1.38 inches
- Suitable for Concentric Neutral and Jacketed Concentric Neutral Cable
- Aluminum 2-hole spade connector
- Compatible with #2 AWG to 1250 kcmil conductors (stranded/compressed 4/0 AWG, compact/solid 250 kcmil)
Specifications
Application | Cable Termination, Outdoor Application, 15kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | 4/0 AWG , 250 kcmil |
Earthing | Products Includes Their Own Grounding System |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

PCT10270-3
15kV, Single Piece Terminator (Class 1), Two Hole Spade Lug. Power Cable Termination, Conductor Size - 4/0 Stranded/Compressed, Use for Insulation Diameter Range from .640 to 1.070 inches.
R2T15J2-N0300-B2
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84-1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed 350 /Compact or Solid 400. Plated Mild Steel Mounting Bracket 1.10 inch - 1.50 inch (28-38mm)
R2T15J1-T1240
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum Barrel For AL Conductor only w/copper wire lead #2 to 4/0. 1/0 Stranded or 2/0 Solid
R2T15J1-T1220
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum Barrel For Aluminum Conductor only with copper wire lead #2-4/0, Stranded or Compressed #2 /Compact or Solid #1.
R2T15J1-T0230-B1
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed #1 /Compact or Solid 1/0. Stainless Steel Mounting Bracket .80 inch - 1.25 inch (20-32mm)
R2T15J1-T0250-B2
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed 2/0 /Compact or Solid 3/0. Plated Mild Steel Mounting Bracket 1.10 inch - 1.50 inch (28-38mm)
R2T15J1-N0300
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 300 -Stranded or Compressed 350 Compact or Solid 400.
R2T15J1-T0220-B1
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed #2 /Compact or Solid #1. Stainless Steel Mounting Bracket .80 inch - 1.25 inch (20-32mm)Frequently Asked Questions
What cable sizes does the R2T15 termination cover?
The R2T15 termination covers cable sizes from #2 AWG through 1250 kcmil, accommodating insulation diameters from 0.64 inches to 2.10 inches.
What is the power system frequency range?
The R2T15 termination is designed for a power system frequency range of 48 to 62 Hz.
What is the IEEE classification for the R2T15?
The R2T15 termination has an IEEE Classification of Outdoor = Class 1A.
Where can I find installation instructions for R2T15?
Installation instructions are IS-1134 for R2T15J, IS-1135 for R2T15M, and IS-1136 for R2T15L.
What is the maximum design voltage to ground?
The maximum design voltage to ground for the R2T15 termination is 9.5 kV.
What are the available sizes for the R2T15 termination?
The R2T15 termination is available in sizes 1, 2, and 4.
What is the maximum altitude for R2T15 installation?
The R2T15 termination can be installed at a maximum altitude of 3300 feet (1005 m).
What is the operating temperature range for the R2T15?
The R2T15 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the voltage rating of the R2T15 termination?
The R2T15 termination has a voltage rating of 15 kV.
What is the lightning impulse withstand voltage?
The lightning impulse (BIL Dry 110 Withstand) voltage for the R2T15 is 110 kV Crest.
How to Install the R2T15J2-N0270 15kV Cable Termination
This guide provides step-by-step instructions for the indoor/outdoor installation of the R2T15J2-N0270 15kV Ranger 2 Cable Termination on concentric and jacketed concentric neutral cables. Ensure all apparatus are de-energized before starting.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Approved solvent applicator, Aluminum oxide abrasive (grit 120 or finer, if needed)
Supplies needed:
Silicone Rubber Termination (R2T15J2-N0270 kit), Lubricant (from kit), Grey Silicone Rubber Tape (from kit), Sealing Mastic (from kit), Gloves (from kit), Connector (optional, if not pre-installed), Cable Support Bracket (optional), Vinyl tape or binding wire, Silicone grease
- Perform Pre-Installation Checks and Ensure Safety
Verify that the cable size fits within the kit range as shown in the Termination Selection Chart. Check all package contents for completeness and damage, and ensure proper fit with the cable and mating products. Read all instructions thoroughly. Gather all required tools and maintain cleanliness. DANGER: All apparatus must be de-energized during installation. This product should only be installed by competent personnel trained in high voltage electrical equipment safety practices.
- Prepare the Cable
Train the cable into its final position and cut it to the required length, allowing sufficient neutral wire length for grounding. Prepare the cable using the dimensions provided in the document, accounting for the depth of the terminal lug and additional exposed conductor distance for aluminum lugs. Wrap one band of mastic around the cable jacket 1/4 inch (6mm) from the jacket end, stretching it to 50% and cutting it flush without overlap. Bend the neutral wires back over the mastic and secure them to the cable jacket 4-6 inches (100-150mm) from the cut edge using vinyl tape or binding wire. Apply a second mastic band over the neutral wires and the first mastic, stretching it to 50% and cutting it flush. Finally, wrap two half-lapped layers of vinyl tape around the mastic seal, carefully maintaining the 1/4 inch (6mm) dimension.
- Install the Lug or Connector
If using a lug that will not fit through the termination core, clean the insulation and slide the termination onto the cable before installing the lug (do not remove the core yet). Position the connector or lug and crimp it according to its directions, ensuring not to crimp the last 1/4 inch to 3/8 inch of the connector. After crimping, remove any excess oxide inhibitor and sharp crimp flashings.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with an approved solvent, taking care not to allow the solvent to touch the semi-con insulation shield. If abrasive cleaning is necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation, and be careful not to reduce the cable insulation diameter below the kit's allowed range. Do not use abrasive on the semi-con insulation shield.
- Install the Termination Body
Create a track-resistant moisture seal using gray silicone rubber tape around the base of the terminal lug. Apply two layers, or build up the tape to match the insulation diameter if the barrel is smaller. Apply a liberal coating of silicone grease to the semi-con insulation shield edge to fill the step. For lower terminations with a fold-down skirt, pull the removable core's loose end through the top until flush with the bottom. Slide the termination body onto the cable, aligning it with the mastic seal's forward edge. Carefully remove the core by unwinding it counter-clockwise from the loose end. Ensure the termination body butts the mastic seal; do not push or pull the assembly during core removal.
- Complete Moisture Seals and Grounding
Apply a thin film of silicone lubricant to the skirt and mastic seal area, but do not lubricate the skirt tabs. Carefully fold down the skirt over the mastic seal. With the termination installed, complete the lug area moisture seal using the remaining gray silicone rubber tape. Overlap the termination insulator by approximately 1 inch and extend the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration. Twist the concentric neutral wires together and connect them securely to the system ground. Finally, confirm that the High-K step does not exceed 1.5 inches.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.