ABB Installation Products K676LR-G2230 900 Amp, 15/25kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug…
UPC: 783786960866
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 900 Amp, 15/25kV rating for medium voltage applications
- 600 Series Elbow Connector with integrated Test Point
- Accommodates cable insulation diameters from 0.760" to 0.950"
- Includes insulated plug, cap, stud, lug, and cable adapter
- Copper compression lug for secure conductor termination
Specifications
Amperage Rating | 900 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | #1 STR/COMPR AWG , 1/0 SOL/COMPT AWG |
Connection | Compression |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully Shielded, Fully Submersible Molded Rubber Housing, 100 Percent Peroxide-Cured Construction includes Insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and Equipment in a de-energized State. Non-Corrosive Capacitive Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 15 to 25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

755LR-H0230
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50.
262LR-D5270-SG3
200 Amp, 25kV, Loadbreak Elbow with Test Point, Cable Insulation Diameter 0.890 inch to 1.220 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67. 200ECS-G3 Jacket Seal and Grounding Kit Included.
K655LR-J0290-S
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size kcmil Compressed/Stranded 300 or Compact/Solid 350 or mm2 Compact 150. Includes Cold-Shrinkable Jacket Seal.
K676CH-BUS
15/25kV 900 Amp Series Deadbreak 4-Way Insulated Bus Bar Splice with Test Point. Plated Copper Components.
655CETP-L0320-DRG
600 Amp, 15kV, Combo T Deadbreak Elbow with 200 Amp Reducing Tap Plug with Stud, Cable Adapter, Aluminum Compression Lug and Insulated Cap Kit, No Test Point, Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size kcmil 450 Compressed/Stranded or 500/550 Compact/Solid. Includes Lubricant, Installation Instructions and Crimp Chart.
K655ETP-M0330-DRG-S
600 Amp, 25KV, DeadBreak, Elbow Connctor, Test and Ground Connector Kit, with Insulated Cap, Reducing Tap Plug, Elbow Housing, Cable Adapter, and Lug, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. Cold-Shrinkable Jacket Seal Included.
656ETP-L0330-DRG
600 Amp, Dead Break, Elbow Connector, Test and Ground Connector Kit with Capacitive Test Point, 15KV, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 500 /Solid 600 /mmSquared 250/300.
675ETPSP-L2380
900 Amp, DeadBreak, 15KV, Window-Op Elbow Kit, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.Frequently Asked Questions
What is the maximum operating voltage for this elbow connector?
The ABB K676LR-G2230 elbow connector is rated for 15/25kV, indicating its suitability for medium voltage applications within this range.
What cable insulation diameters can this connector accommodate?
This elbow connector is designed to fit cable insulation diameters ranging from 0.760 inches to 0.950 inches.
What type of lug is used for conductor connection?
The K676LR-G2230 utilizes a copper compression lug for a secure and reliable conductor connection.
What conductor sizes are compatible with this elbow connector?
It is compatible with AWG or kcmil compressed stranded conductors, 1/0 AWG compacted solid conductors, and 50 mm² compact conductors.
Does this elbow connector include a test point?
Yes, the ABB K676LR-G2230 is a 600 Series Elbow Connector that features a built-in test point.
How to Install 655/675LR and K655/K675LR Deadbreak Elbow Connectors
Install 600-ampere or 900-ampere deadbreak elbow connectors for 15kV and 25kV class systems. This guide covers cable preparation, connector assembly, and final connection to high voltage apparatus, ensuring fully shielded and submersible connections.
Estimated time: 1h 30m
Tools needed:
Hotstick, Capacitive voltage detector, Wire brush (for aluminum conductors), Crimping tool, Torque wrench, Cable stripping tools
Supplies needed:
Deadbreak Elbow Connector Kit (includes Elbow, Cable Adapter, Compression Lug, Insulating Plug, Lubricant, Threaded Stud), Grounding wire (No. 14 AWG Copper or equivalent), Suitable ground connector, Waterproofing material, Silicone lubricant
- De-energize and Inspect Apparatus
Ensure all apparatus are de-energized before beginning installation. Inspect all parts for damage, correct rating, and compatibility with mating components. Have all required tools ready and maintain a clean work area.
- Prepare Cable for Connection
Assemble the cable in its final position with sufficient slack. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable for 24 inches (610mm) or up to the bent back neutral wires. Remove the outer jacket (if applicable) and prepare the cable insulation and semi-con shield to the dimensions specified in the product diagrams.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor and Install Compression Lug
Trim the protruding cable insulation flush with the end of the cable adapter, ensuring the exposed conductor length is between 4-1/4 inches and 4-9/16 inches (108mm-116mm). For aluminum conductors, wire brush the conductor immediately before insertion. Fully insert the conductor into the compression lug. Measure the 'Check Dimension' (should be less than 6-3/8 inches) before crimping. Crimp the compression lug according to the lug's instructions. Wipe off any excess inhibitor and verify the final distance from the lug end to the cable adapter is between 6-3/8 inches and 7-1/8 inches (162mm-181mm).
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter, pushing until it cannot advance further. Confirm the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Prepare Mating Parts
Remove any protective caps from the elbow and the mating part. If the mating part lacks a stud, hand tighten the threaded stud supplied with the elbow into it. Clean and lubricate both the elbow and the mating part thoroughly with the provided lubricant, keeping surfaces clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, carefully aligning the hole in the compression lug with the stud on the mating part.
- Connect Opposite Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part to the specifications provided with that component.
- Install Insulating Plug (if used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap onto the elbow and push down firmly until it snaps into place.
- Ground the Cable Shield
Insert one end of a No. 14 AWG copper (or equivalent) wire through the grounding eye and form a small loop. Connect this wire to ground using a suitable connector. Ensure the cable shield is grounded, either via a grounding device or an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test
Remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Use a suitable capacitive sensing device (not conventional voltage equipment) to determine if the cable is energized. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.