Contact for Pricing
Overview
- Rated for 15/25 kV and 600 Amps continuous current
- EPDM rubber construction for environmental resistance
- Capacitive test point for voltage verification before grounding
- Meets ANSI/IEEE Standard 386 with 95/140 kV BIL ratings
- 25 kA symmetrical momentary rating (10 cycles) for fault handling
Specifications
Amperage Rating | 600 A |
Application | 15/25 kV, 600 Amps |
Conductor Material | Copper , EPDM Rubber |
Connection | Threaded |
Insulation | EPDM Rubber |
Length | 9.15 in |
Special Features | Fits 5/8-11 Threaded Stud |
Standard | ANSI/IEEE Standard 386 |
Type | Grounding Device Insulating Cap |
Voltage Rating | 15/25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

L70P-56GS
Copper Mechanical Lug with 5/16 Inch Bolt Hole, Wire Range 14-4 AWG, Green Slotted Screw, Tin Plated, 600 Volts, 100 Minimun
K475J3-5
25kV, 630 Amp Rated, Deadbreak, 3-Way Multi-Point Junction, 304 Stainless Steel Hold Down Bracket.
M676CHJK
38 kV, 4-Way, Bus Splice Jacket, 900 Amps, H-Splice Conductive Jacket. 21.1 kV L-G Deadbreak. Semi-Conductive EPDM Rubber.
KIT-LABEL2
Label with (CFE) this is used on a system that carries current. Dark Green Letters on White Background Label 4 inch wide x 3 inch tall. Letters 2.50 inch high. Heavy Duty Laminated Characters, Mylar Polyester Laminated Vinyl. Helvetica Font-Style Letters.
P24D40G
The Panduit™ G6 Monitored Input PDU features (20) C13 and (4) C19 outlets. It is a 16 amp, 230 V, single phase PDU with an IEC 60309 2P+E 6h 16A (IP44) input plug and a 10 foot (3m) power cord. The PDU is black.Frequently Asked Questions
Does the GAD eliminate temporary grounding adapters?
Yes, the Elastimold GAD eliminates the need to install temporary grounding adapters, saving time and resources.
Can the GAD be used with a hot-stick?
Yes, the GAD's removable protective cap with capacitive test point is designed to be hot-stick workable.
What material is the GAD constructed from?
The Elastimold GAD features full copper construction, making it ideal for 600 A and 900 A applications.
Is the GAD compatible with different ground clamp types?
Yes, the GAD is available for C and ball-stud grounding clamp types. Series GAD and GADDR are for C-clamp, while BGAD and BGADDR are for ball-stud connections.
Does the GAD include a test point?
Yes, the GAD includes an insulated cap with an integral capacitive test point. This allows easy access to check if the system is de-energized.
What system classes is the GAD available for?
The Elastimold grounding-aid device is available for 15, 25, and 35 kV system classes.
How is the Elastimold GAD installed?
The Elastimold GAD easily installs in the rear interface of a 600 A series elbow connector (T-body), providing a direct and permanent grounding connection.
What fault current can the GAD withstand?
The Elastimold GAD has a short circuit withstand rating of up to 25 kA. It is designed for 600 A and 900 A applications.
What is the Elastimold GAD used for?
The Elastimold grounding-aid device (GAD) provides a permanent, reliable, direct 600 A or 900 A, 25 kA rated ground connection in underground systems. It is used when available fault currents exceed 10 kA.
Does the GAD include a test point?
Yes, the GAD includes an insulated cap with an integral capacitive test point. This allows easy access to check if the system is de-energized.
How to Install the K671GAD Grounding Device and K676GADDR Insulated Cap
This guide provides step-by-step instructions for safely installing the K671GAD Deadbreak Grounding Device and the K676GADDR Insulated Cap with Test Point onto a 600Amp elbow, including wiring and lubrication procedures. Ensure all apparatus are de-energized before beginning.
Estimated time: 1h
Tools needed:
600ATM Assembly Tool, Torque Wrench, Hotstick (2 required), Voltage Sensing Device (for capacitive test points)
Supplies needed:
Lubricant (supplied with product), No. 14 AWG Copper Grounding Wire, Silicone Grease
- Prepare for Installation and Safety Check
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. Inspect all parts for damage, correct rating, and compatibility with mating parts. Read all instructions thoroughly before starting and ensure all required tools are at hand. Maintain cleanliness throughout the procedure.
- Install the K671GAD Grounding Connector
Install the 600Amp elbow onto the apparatus bushing following its specific instructions; do not install an insulating plug or cap. Clean and lubricate the K671GAD Grounding Connector interface and the 600Amp elbow interface using only the supplied lubricant. Insert the K671GAD Grounding Connector into the elbow and rotate clockwise to engage the stud. Insert the 600ATM assembly tool into the K671GAD and, using a torque wrench, continue rotating clockwise until it stops. Tighten to 55-60 foot-pounds torque. Remove the 600ATM tool.
- Connect K671GAD to System Ground
Using a separate No. 14 AWG (2.55mm) copper wire or equivalent, insert one end through the grounding eye on the K671GAD Grounding Connector. Twist the wire tightly, taking care not to damage the eye. Connect the free end of the grounding wire to the system ground.
- Prepare K676GADDR Insulating Cap Grounding Wire
Using a separate No. 14 AWG (2.55mm) copper wire or equivalent, insert one end through the grounding eye of the insulated cap. Make a small loop and twist tightly, ensuring not to damage the grounding eye. Connect the free end of this grounding wire to the system ground. The length of this wire should be sufficient to reach the grounding point and wrap around the insulated cap approximately 10 times (90 inches) during assembly.
- Install the K676GADDR Insulating Cap
Clean and lubricate the K676GADDR insulating cap and the K671GAD interface with the supplied lubricant; do not substitute. Attach the first hotstick tool to the insulated cap assembly/disassembly bail and push the receptacle onto the bushing interface until it stops. With a second hotstick, engage the grounding wire and establish slight tension, wrapping it loosely around the center of the insulated cap. While pushing with the first hotstick, rotate clockwise until the threads between the bushing and the cap engage. Discontinue pushing and continue turning until resistance is felt, applying a maximum torque of 15 ft-lb. DO NOT OVERTIGHTEN. Remove the second hotstick.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.