ABB Installation Products K656LR-M0320 15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud…
UPC: 783786585533
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV voltage rating
- 600 Amp continuous current rating
- Test point for diagnostics
- Accommodates 1.370" - 1.630" cable insulation diameter
- Suitable for 450 kcmil (compressed/stranded) or 500/550 kcmil (compact/solid) conductors
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amp Deadbreak Elbow Connection |
Color | Black |
Conductor Range | 450 kcmil , 500 to 550 kcmil |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully Shielded, Fully Submersible Molded Rubber Housing. 100 percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected using Standard Hand Tools and Equipment in a De-Energized State. Non-Corrosive, Capacitive Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655YSR-K2320
600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550.
K656LR-H0230
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded #1 or Compact/Solid 1/0 or mm2 Compact 50.
K655LR-M0410
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size kcmil Compressed/Stranded 1000.
K655LR-P0410-S
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.725 inch to 1.935 inch. Conductor Size kcmil Compressed/Stranded 1000. Cold-Shrinkable Jacket Seal Included.
K655LR-N0380
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size kcmil Compressed/Stranded 700/750 or Compact/Solid 900.
K656LR-F0220
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.640 inch to 0.820 inch. Conductor Size Compressed/Stranded #2 or Compact/Solid #1
K655LR-N0240
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG Compressed Stranded 1/0 or Compacted Solid 2/0.
K656LR-H0220
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded #2 or Compact/Solid #1 or mm2 Compact 35.Frequently Asked Questions
What is the maximum operating voltage for the K656LR elbow connector?
For the 15kV voltage class, the maximum operating voltage is 8.3kV phase-to-ground. For the 28kV voltage class, it is 16.2kV phase-to-ground.
What conductor sizes can the K656LR handle?
It can be used with conductor sizes from #2 AWG to 1250 kcmil for both aluminum and copper conductors.
What is the continuous current rating for this elbow connector?
The K656LR elbow connector has a continuous current rating of 600 Amps.
What is the impulse withstand rating for the 28kV voltage class?
The impulse withstand rating for the 28kV voltage class is 140kV BIL for a 1.2 x 50 microsecond wave.
What is the AC one-minute withstand voltage for the 15kV class?
The AC one-minute withstand voltage for the 15kV voltage class is 34kV.
What is the insulation diameter range for the K656LR?
The K656LR can accommodate insulation diameters ranging from 0.640 inches to 1.935 inches.
What standards does the K656LR meet?
The K656LR meets ANSI/IEEE Standard 386, Latest Revision.
What is the purpose of the test point on the K656LR?
The test point is a non-corrosive capacitive test point, allowing for testing capabilities.
Are accessories available for the K656LR?
Yes, optional accessories are available for visible external separation, by-pass, isolation, dead-ending, grounding, testing, and adding taps.
What is recommended for safety when using on metallic tape shield or drain wire cable?
For safety purposes, an ECS cable seal grounding device is highly recommended when used on metallic tape shield or drain wire cable.
How to Install 655/675LR and K655/K675LR Deadbreak Elbow Connectors
A comprehensive guide for the safe and correct installation of 600-ampere or 900-ampere deadbreak elbow connectors on 15kV and 25kV class systems. This guide covers cable preparation, connector assembly, and initial voltage testing.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Wire brush (for aluminum conductors), Hotstick, Suitable voltage sensing device, Torque wrench
Supplies needed:
655/675LR or K655/K675LR Elbow Connector, Cable Adapter, Compression Lug, Insulating Plug (if applicable), Lubricant (silicone type for test point cap), Threaded Stud (from Stud Prepack), Grounding wire (at least No. 14 AWG Copper), Suitable grounding connector, Waterproofing material (for cable jacket), HV insulated cap(s) or connector(s) (if replacing shipping covers)
- De-energize Apparatus and Inspect Parts
DANGER: Ensure all apparatus is de-energized during installation or removal of part(s). Do not touch or move energized products in the work area. Inspect parts for damage, rating and compatibility with mating parts. If this product is supplied with a protective shipping cover(s), remove this shipping cover(s) and replace with the appropriate HV insulated cap(s) or connector(s) before submerging or energizing the circuit.
- Prepare Cable for Assembly
Assemble the cable in its final assembled position with enough slack to provide adequate clearance for removing the elbows. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable a distance of 24 inches (610mm) or up to the bent back concentric neutral wires.
- Perform Cable Preparation
Follow the specific cable preparation steps (A, B, or C) that apply to your cable type. This may involve removing the outer jacket, preparing the semi-con shield, and marking specific lengths (e.g., 9-3/4 inches, 10-3/4 inches, 12-3/4 inches) as shown in the diagrams for non-jacketed, jacketed, Unishield, or lead sheath cables. Refer to separate instructions for grounding devices (20MA/21MA), jacket cable seals (600ECS), or cable shield adapters (10TL) if used.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor Length
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of the exposed bare conductor must be between 4-1/4 inches and 4-9/16 inches (108mm-116mm). If the length is outside this range, redo the assembly.
- Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the compression lug. Measure the 'Check Dimension' before crimping; this dimension should be less than 6-3/8 inches. Crimp the compression lug following the crimping instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. The distance from the end of the compression lug to the cable adapter after crimping should be between 6-3/8 inches to 7-1/8 inches (162mm-181mm). If dimensions are incorrect, redo the assembly.
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until the elbow cannot advance further. Make sure the cable adapter is still flush with the tape marker. If not, reposition the cable adapter. Remove the tape marker.
- Prepare Mating Products
DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud supplied with the elbow into the mating part, if the mating part is not equipped with a stud. Clean and lubricate both the elbow and the mating part with lubricant supplied, keeping surfaces clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, lining up the hole in the compression lug with the stud on the mating part.
- Connect Opposite Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert the mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to the instructions supplied with the mating part. CAUTION: When constructing 600-amp L-Kits, be sure to tighten each component to specified torque per instructions provided.
- Install Insulating Plug and Cap (if applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place on the elbow. Push down hard until the cap snaps into place.
- Ground the Cable Shield
Insert one end of a piece of wire with ampacity at least equivalent to No. 14 AWG Copper through the grounding eye and twist to make a small loop. Do not damage the eye. Connect wire to ground using a suitable connector. The shield of the cable must be grounded; ground according to the instructions supplied with the grounding device. If no grounding device is used, the shield must be grounded through an alternate method. It is also recommended that the jacket of the cable be waterproofed at this point to prevent moisture from entering the cable.
- Perform Voltage Test
WARNING: The voltage test point is a capacitance device; it is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the meter that is used. Test with a suitable sensing device, made for use with separable connectors manufactured with capacitive test points, to determine if the cable is energized. Contamination, moisture, dirt, etc. around the test point or use of the wrong measuring equipment can provide a false 'no voltage' indication on an energized elbow. To prevent serious or fatal injury, treat the elbow as energized until the 'no voltage' test point indication is confirmed by other means. After voltage detection has been made, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.