ABB - Installation Products K656LR-J0230 - 15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size Compressed/Stranded #1 or Compact/Solid 1/0 or mm2 Compact 50.

ABB Installation Products K656LR-J0230 15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud…

UPC: 783786969456


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call (262) 252-1600 or email [email protected] for pricing and availability.

Overview

The ABB K656LR-J0230 Series Deadbreak Elbow is a 15/25 kV, 600 Amp rated deadbreak connector designed for reliable medium-voltage cable terminations in industrial and utility applications. This deadbreak elbow features a deadbreak interface, allowing for safe and efficient connections under load without de-energizing the system. The unit includes an insulated plug, cap, stud, lug, and cable adapter, ensuring full system integrity and personnel safety during installation and operation. Constructed from high-strength aluminum with an aluminum compression lug, the K656LR-J0230 accommodates cable insulation diameters ranging from 0.980 inch to 1.180 inch. It supports conductor sizes including compressed/stranded #1 or compact/solid 1/0 AWG, as well as compact 50 mm². The deadbreak design eliminates the need for hot stick operations, reducing installation time and improving worker safety. This elbow is part of the ABB K656LR series, a trusted line of medium-voltage connectors known for durability and compliance with industry standards. It is ideal for use in switchgear, transformers, and other medium-voltage distribution equipment where reliable, maintenance-free connections are critical. The product’s compact design and robust construction make it suitable for both indoor and outdoor installations, including harsh environmental conditions. Key applications include utility substations, industrial plants, commercial buildings, and renewable energy installations. The K656LR-J0230 ensures long-term performance with minimal maintenance, providing a cost-effective solution for medium-voltage cable terminations. ABB’s engineering expertise and rigorous testing standards guarantee reliable operation in demanding electrical environments.
  • Voltage Rating: 15/25 kV
  • Current Rating: 600 Amp
  • Conductor Size: #1/0 or 50 mm² (compressed/stranded or compact/solid)
  • Cable Insulation Diameter: 0.980 inch to 1.180 inch
  • Includes insulated plug, cap, stud, lug, and cable adapter

Specifications

Amperage Rating
600 A
Application
15/25kV, 600 Amp Deadbreak Elbow Connection
Color
Black
Conductor Range
#1 STR/COMPR AWG , 1/0 SOL/COMPT AWG
Environmental Conditions
Fully Submersible
Insulation
True
Length
13 in
Length
330.2 mm
Material
Housing - EPDM-Rubber
Special Features
Fully Shielded, Fully Submersible Molded Rubber Housing. 100 percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected using Standard Hand Tools and Equipment in a De-Energized State. Non-Corrosive, Capacitive Test Point
Standard
ANSI/IEEE Standard 386
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Deadbreak Elbow Connector with Test Point
Voltage Rating
25 kV
Width
10.36 in
Width
263.144 mm
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
6.6100 L
Package Weight (Metric)
2.9980 kg
600 Amp, 15/25kV, Deadbreak, Straight Receptacle with Test Point, Cable Insulation Diameter .850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded #1 or Compacted Solid 1/0.

K656YSR-H0230

600 Amp, 15/25kV, Deadbreak, Straight Receptacle with Test Point, Cable Insulation Diameter .850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded #1 or Compacted Solid 1/0.
6MM2 BLACK CABLE FOR DISTRIBUTION BLOCK ROW TYPE LENGTH 320MM

54211116

6MM2 BLACK CABLE FOR DISTRIBUTION BLOCK ROW TYPE LENGTH 320MM
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Bi-Metal Compression Lug. Cable Insulation Diameter 0.640 inch to 0.820 inch. Conductor Size Compressed/Stranded 2/0 or Compact/Solid 3/0 or mm2 Compact 70. Cold-Shrinkable Jacket Seal Included.

K656LR-F5250-S

15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Bi-Metal Compression Lug. Cable Insulation Diameter 0.640 inch to 0.820 inch. Conductor Size Compressed/Stranded 2/0 or Compact/Solid 3/0 or mm2 Compact 70. Cold-Shrinkable Jacket Seal Included.
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Copper Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size kcmil Compressed/Stranded 700/750 or Compact/Solid 900.

K655LRM2380

600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Copper Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size kcmil Compressed/Stranded 700/750 or Compact/Solid 900.
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size kcmil Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300. Cold-Shrinkable Jacket Seal Included.

K655LR-N0330-S

600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size kcmil Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300. Cold-Shrinkable Jacket Seal Included.
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.760 inch to 0.950 inch. Conductor Size Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185.

K656LR-G0300

15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.760 inch to 0.950 inch. Conductor Size Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185.
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.640 inch to 0.820 inch. Conductor Size Compressed/Stranded 1/0 or Compact/Solid 2/0. No Sealing Kit

K656LR-F0240

15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.640 inch to 0.820 inch. Conductor Size Compressed/Stranded 1/0 or Compact/Solid 2/0. No Sealing Kit
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.640 inch to 0.820 inch. Conductor Size Compact/Solid #2. No Sealing Kit.

K656LR-F0210

15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.640 inch to 0.820 inch. Conductor Size Compact/Solid #2. No Sealing Kit.

Frequently Asked Questions

What is the maximum operating voltage for the K656LR-J0230?

The K656LR-J0230 can be used through 28kV. For the 15kV voltage class, the max operating voltage is 8.3kV phase-to-ground and 14.4kV phase-to-phase.

What conductor sizes are compatible with the K656LR-J0230?

It is compatible with conductor ranges from #2 AWG to 1250 kcmil for both aluminum and copper conductors.

What is the insulation diameter range for this elbow connector?

The K656LR-J0230 is designed for insulation diameters ranging from 0.640 inches to 1.935 inches.

What is the continuous current rating for this deadbreak elbow?

The K656LR-J0230 has a continuous current rating of 600 Amps.

What is the momentary current withstand rating?

The momentary current withstand rating is 25kA Sym for 10 Cycles.

What is the impulse withstand voltage rating?

For the 15kV class, it is 95kV BIL. For the 28kV class, it is 140kV BIL.

What is the AC one-minute withstand voltage rating?

For the 15kV voltage class, it is 34kV AC. For the 28kV voltage class, it is 45kV AC.

What is the DC fifteen-minute withstand voltage rating?

For the 15kV voltage class, it is 53kV DC. For the 28kV voltage class, it is 84kV DC.

What is the corona extinction rating?

For the 15kV voltage class, it is 11kV AC. For the 28kV voltage class, it is 21.5kV AC, both at 3pC sensitivity.

Are there any recommended safety accessories for this product?

Yes, when used on metallic tape shield or drain wire cable, an ECS cable seal grounding device for safety is highly recommended.

How to Install Deadbreak Elbow Connectors (655/675LR and K655/K675LR)

This guide provides step-by-step instructions for the safe installation and connection of 600-ampere or 900-ampere deadbreak elbow connectors on 15kV and 25kV class systems. It covers cable preparation, lug crimping, and final assembly.

Estimated time: 2h

Tools needed:

Wire strippers, Crimping tool, Wire brush, Hotstick, Suitable sensing device, Torque wrench, Measuring tape or ruler

Supplies needed:

Deadbreak Elbow Connector, Cable Adapter, Compression Lug, Insulating Plug (if applicable), Lubricant, Threaded Stud (if mating part not equipped), Tape marker, Grounding wire (No. 14 AWG Copper or equivalent), Suitable connector (for grounding wire), Waterproofing material (for cable jacket)

  1. De-energize Apparatus and Ensure Safety

    Ensure all apparatus is de-energized before beginning installation. Do not touch or move energized products in the work area. This product should only be installed by competent personnel trained in good safety practices involving high voltage electrical equipment.

  2. Inspect Components

    Check the package contents to ensure they are complete and undamaged. Verify all components for proper fit with the cable and/or mating products.

  3. Prepare Cable Slack and Cut

    Assemble the cable in its final position with enough slack to provide adequate clearance for removing the elbows. Unwind the concentric neutral wires if applicable. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product.

  4. Clean Cable Outer Surface

    Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent-back concentric neutral wires.

  5. Bevel, Clean, and Lubricate Cable Insulation

    Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and lubricate the cable insulation, always working toward the semi-con shield.

  6. Install Cable Adapter

    Install the cable adapter, small end first, until it is flush with the edge of the tape marker.

  7. Expose Conductor and Verify Length

    Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of exposed conductor must be between 4-1/4 inches and 4-9/16 inches (108mm-116mm); otherwise, redo the assembly.

  8. Crimp Compression Lug

    For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it. Measure the 'Check Dimension' before crimping; it must be less than 6-3/8 inches. Crimp the compression lug following its supplied instructions. Wipe all excess inhibitor from the lug and cable adapter surface. The distance from the end of the lug to the cable adapter after crimping must be between 6-3/8 inches to 7-1/8 inches (162mm-181mm); otherwise, redo the assembly.

  9. Install Elbow onto Cable Adapter

    Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter is still flush with the tape marker; if not, reposition it. Remove the tape marker.

  10. Prepare Mating Products for Connection

    Remove protective caps from the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud supplied with the elbow into the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean. DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED.

  11. Connect Elbow to Mating Part

    Push the elbow onto the mating part, lining up the hole in the compression lug with the stud on the mating part.

  12. Connect Opposite Mating Part (if applicable)

    Clean and lubricate the mating part for the opposite end of the elbow. Insert the mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to the instructions supplied with it. CAUTION: When constructing 600amp L-Kits, ensure each component is tightened to specified torque per instructions provided.

  13. Install Insulating Plug (if used)

    If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow. Push down hard until the cap snaps into place.

  14. Ground the Cable Shield

    Insert one end of a wire with ampacity at least equivalent to No. 14 AWG Copper through the grounding eye and twist to make a small loop. Do not damage the eye. Connect the wire to ground using a suitable connector. The cable shield must be grounded according to the instructions supplied with the grounding device, or through an alternate method if no device is used.

  15. Waterproof Cable Jacket

    Waterproof the jacket of the cable at this point to prevent moisture from entering the cable.

  16. Perform Voltage Test

    Remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Use a suitable sensing device made for capacitive test points to determine if the cable is energized. Do not use conventional voltage measuring equipment. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means to prevent serious or fatal injury. After voltage detection, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.