ABB Installation Products K656I-M0380 15-25kV 600 Series Deadbreak Separable Straight Joint Package (2-Way) with Test Point.…
UPC: 783786625833
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15-25kV voltage class with 600A continuous current rating
- Deadbreak separable interface for safe, de-energized installations
- Integrated test point for diagnostic testing without circuit shutdown
- Accommodates cable insulation diameters 1.370" to 1.630"
- Supports compressed stranded (700/750 kcmil) and compacted solid (900 kcmil) conductors
Specifications
Amperage Rating | 600 A |
Application | Compact Design is suitable for small vaults and manholes |
Color | Black |
Conductor Range | 700 to 750 kcmil , 900 kcmil |
Connection | Compression |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Length | 37.27 in |
Length | 946.658 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully Shielded, Fully Submersible, 100 percent Peroxide cured Molded EODM Rubber |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Separable Straight Joint |
Voltage Rating | 15 to 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 16.0000 L |
Package Weight (Metric) | 7.2580 kg |

K656CY-L0380
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
K655YSR-J0270
600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.
K675SR-N2380
900 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring, Cable Insulation Diameter 1.515 inch to 1.780 inch. Copper Compression Lug. Conductor Size kcmil Compressed Stranded 700/750 or Solid Compact 900.
K656CYP0410P0410P041
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, with 3 X ( Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000. )
K655YSR-J0300-S
600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185. Cold-Shrinkable Jacket Seal Included.
K656CY-K0330
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
K656I-N0410
15-25kV 600 Series Deadbreak Separable Straight Joint Package (2-Way) with Test Point. Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 1000.
K656CH-L0320-SG1
600 Amp, 15/25kV, Separable H Joint Kit, 4-Way with Test Point. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550. Cold Shrinkable Seal with Copper Rod and Crimp Connector Included.Frequently Asked Questions
What is the momentary current rating of the joint?
The momentary current rating for the K656I-W0X is 25kA Symmetrical for 10 Cycles for both voltage classes.
What components are included in a complete K656I-W0X joint package?
A complete joint package includes an insulated bus bar, straight receptacle housing, retaining rings, cable size adapters, lugs, bolts, and washers.
Can I add grounding or sealing kits to the joint?
Yes, you can add a suffix symbol to the catalog number to include a cable shield grounding kit and/or a cable jacket sealing kit.
What is the BIL impulse withstand for the 15kV class?
For the 15kV voltage class, the BIL impulse withstand is 95kV.
What is the BIL impulse withstand for the 25kV class?
For the 25kV voltage class, the BIL impulse withstand is 140kV.
What industry standards does the K656I-W0X meet?
The K656I-W0X meets ANSI/IEEE Standard 386, Latest Revision.
What is the K656I-W0X product used for?
The K656I-W0X is a deadbreak separable straight joint used to join cables in a disconnectable 2-way joint. It is suitable for small vaults, manholes, and direct-buried applications.
What voltage classes does the K656I-W0X support?
The K656I-W0X supports both 15kV and 25kV voltage classes.
What is the maximum operating voltage for the 15kV class?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV and maximum phase-to-phase is 14.4kV.
What is the maximum operating voltage for the 25kV class?
For the 25kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV and maximum phase-to-phase is 28kV.
How to Install K656I Deadbreak Receptacles
This guide provides detailed instructions for the safe installation and assembly of K656I Deadbreak Receptacles, including cable preparation, crimping, and final connection for high voltage applications.
Estimated time: 2h
Tools needed:
Hex wrench, Torque wrench with 15/16” socket, Wire brush, Assembly tool (650ATY or 600RRT), Rag, Wire strippers, Safety solvent
Supplies needed:
K656I Receptacle housing, Cable adapter, I Center section, Aluminum holding collar, Lubricant (supplied or ELASTIMOLD approved), Hex-head bolts, Crimp connector, Belleville washer, Flat washer, Nylon venting rod, Jacketed Concentric Neutral Cable, Electrical tape, ECS grounding device (optional), No. 14 AWG copper wire
- Ensure Safety and Inspect Components
DANGER: De-energize all apparatus before beginning installation. This product must be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. Inspect all package contents for completeness and damage. Verify all components are rated and compatible with mating parts and cable. Check threads by threading a probe into the compression lug; replace damaged components if resistance is encountered.
- Prepare Cable Jacket and Position Initial Components
Wipe the cable's outer jacket clean for a distance of 38 inches from the end, ensuring the cable end is cut squarely. If an ECS grounding device is being used, slide its tube 38 inches onto the cable. Next, slide the receptacle housing 30 inches onto the cable. For jacketed concentric neutral cable, measure 13-3/4 inches from the cable end and remove the cable jacket with a straight, smooth cut, taking care not to damage the neutral wires. Bend the neutral wires back and out of the way.
- Remove Semi-con Shield and Bevel Insulation
From the end of the cable, measure 10-1/4 inches and remove the semi-con shield from the insulation with a straight, smooth, 'squared' cut, ensuring not to cut or nick the insulation. At a point 1 inch from the end of the semi-con shield, wrap two turns of tape to serve as a marker. Bevel the end of the insulation at a 45-degree angle, approximately 1/4 inch back.
- Clean Insulation and Install Cable Adapter
Thoroughly clean the insulation to remove all traces of semi-conducting residue by wiping with a rag soaked with an approved safety solvent. Always wipe from the end of the cable toward the outer jacket. Apply supplied lubricant sparingly along the cable as shown in the documentation. Lubricate the inside of the cable adapter. Slide the adapter, small end first, over the cable with a twisting motion until the end of the adapter is flush with the tape marker.
- Prepare Conductor and Secure Retaining Ring
Remove any protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of exposed conductor should be 4 3/4 to 5 inches; if not, redo the assembly. Assemble the aluminum retaining ring over the conductor and snug it firmly against the cable adapter. Using the provided hex wrench, tighten the socket head screw hand tight. Confirm the exposed conductor measures 4 3/8 to 4 3/4 inches; if not, redo the assembly.
- Install and Crimp the Connector
Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor and immediately fully insert it into the crimp connector, which contains inhibitor. Measure the distance from the end of the connector to the holding collar; if it is over 7 inches, do not proceed and redo all previous work. Prior to crimping, confirm components are positioned correctly and bolt holes in the crimp connectors align with the mating part. Crimp the connectors following their specific instructions, rotating each crimp 90 or 180 degrees. After crimping, re-measure the distance from the end of the connector to the holding collar; if over 7 inches, redo previous work.
- Assemble Washers and Torque Bolts
Assemble the washers and bolt in the following order: flat washer against the spade contact, Belleville washer (concave side down), then the hex-head bolt. Hand tighten the bolt. The splice and cables are now in their final positions; do not attempt to move or reposition any part of the assembly after bolts are tightened. Using a torque wrench with a 15/16 inch socket, tighten all bolts to 50 to 60 ft. lbs.
- Lubricate and Fully Install Receptacle Housing
Apply supplied lubricant or ELASTIMOLD approved lubricant generously to the outside of the cable adapter, the area of the splice section, and the inside mating surface of the receptacle housing. Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the nylon venting rod. Using either the 650ATY or 600RRT assembly tool, slowly slide the receptacle housing completely over the splice section. Remove the venting rod. WARNING: DO NOT place hand on threaded rod or guide shaft with the assembly tool in place.
- Complete Grounding Connections
Complete the installation of any ECS grounding device according to its included instructions. Connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings. Make a small loop and twist tightly, taking care not to damage the eye, and connect it to ground.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.