ABB Installation Products K656I-M0330 15-25kV 600 Series Deadbreak Separable Straight Joint Package (2-Way) with Test Point.…
UPC: 783786616060
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15-25kV voltage rating for medium voltage applications
- 2-Way deadbreak separable straight joint configuration
- Integrated test point for safe voltage detection
- Aluminum compression lugs for conductor sizes 500-600 kcmil / 250-300 mm²
- Accommodates cable insulation diameters from 1.370" to 1.630"
Specifications
Amperage Rating | 600 A |
Application | Compact Design is suitable for small vaults and manholes |
Color | Black |
Conductor Range | 500 kcmil , 600 kcmil |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Length | 37.27 in |
Length | 946.658 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully Shielded, Fully Submersible, 100 percent Peroxide cured Molded EODM Rubber |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Separable Straight Joint |
Voltage Rating | 15 to 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655LR-J0330
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size kcmil Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300.
655LR-H0270
600 Amps, 15/25kV, Deadbreak, Elbow, Current Carrying over 1000 Volts. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed/ Stranded 4/0 or Compacted/Solid 250 kcmil or mmSquared Compact 125.
K656I-M0380
15-25kV 600 Series Deadbreak Separable Straight Joint Package (2-Way) with Test Point. Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
K655YSR-J0270
600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.
K675SR-N2380
900 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring, Cable Insulation Diameter 1.515 inch to 1.780 inch. Copper Compression Lug. Conductor Size kcmil Compressed Stranded 700/750 or Solid Compact 900.
K656CYP0410P0410P041
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, with 3 X ( Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000. )
K655YSR-J0300-S
600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185. Cold-Shrinkable Jacket Seal Included.
K656CY-K0330
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.Frequently Asked Questions
How do I choose the correct compression lug code?
Select the proper compression lug code from table 2 according to the conductor size (AWG or kcmil, mm2).
How is the cable insulation diameter code selected?
Determine the cable's insulation diameter, then select the letter code from the W table that best straddles that diameter.
What items are included in a complete K656I package?
A complete K656I joint package includes an insulated bus bar, straight receptacle housing, retaining rings, cable size adapters, lugs, bolts, and washers.
Does the K656I joint include a test point?
Yes, the K656I joint includes an integral capacitive test point.
Can the K656I joint be used in direct-buried applications?
Yes, the K656I cable joint can be used in direct-buried applications.
What is the continuous current rating of the K656I?
The K656I joint has a continuous current rating of 600 Amps for both 15kV and 25kV voltage classes.
What are the voltage ratings for the 25kV class?
For the 25kV class, the maximum phase-to-ground operating voltage is 16.2kV and phase-to-phase is 28kV.
What are the voltage ratings for the 15kV class?
For the 15kV class, the maximum phase-to-ground operating voltage is 8.3kV and phase-to-phase is 14.4kV.
What is the K656I cable joint used for?
The K656I cable joint is used to join cables in a disconnectable 2-way joint. It is suitable for small vaults, manholes, and direct-buried applications.
How do I choose the correct compression lug code?
Select the proper compression lug code from table 2 according to the conductor size (AWG or kcmil, mm2).
How to Install K656I Deadbreak Receptacles
This guide provides step-by-step instructions for installing K656I, K656CY, and K656CH Deadbreak Receptacles, including cable preparation, connector crimping, and final assembly for 15kV and 25kV solid dielectric type cables. These instructions cover the installation of one leg of the connector.
Estimated time: 45m
Tools needed:
Hex wrench, Torque wrench with 15/16 inch socket, Wire brush, Assembly tool (650ATY or 600RRT), Rag, Approved safety solvent, Wire strippers, Crimping tool
Supplies needed:
Receptacle housings, Cable adapters, Center sections (I, Wye, or H), Aluminum holding collars, Lubricant, Hex-head bolts, Crimp connectors, Belleville washers, Flat washers, Nylon venting rod, Electrical tape, ECS grounding device (optional), No. 14 AWG copper wire
- Ensure Safety and Inspect Components
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. Inspect all package contents for completeness and damage. Check all components for proper fit with the cable and mating parts. Verify threads by threading a probe into the compression lug; replace damaged components if resistance is encountered. Have all required tools at hand and maintain cleanliness.
- Prepare Cable Jacket and Slide Housing
Wipe the outer jacket of the cable clean for a distance of 38 inches (96.5 cm) from the end. Cut the cable end squarely to ensure maximum length for crimp growth. If using an ECS grounding device, slide its tube onto the cable for a distance of 38 inches (96.5 cm). Slide the receptacle housing onto the cable for a distance of 30 inches (76.2 cm).
- Prepare Concentric Neutral Cable
Measure 13-3/4 inches (34.9 cm) from the cable end and remove the cable jacket with a straight, smooth cut, taking care not to damage neutral wires. Bend neutral wires back and out of the way. Measure 10-1/4 inches (26.0 cm) from the cable end and remove the semi-con from the insulation with a straight, smooth, squared cut, avoiding nicks to the insulation. At 1 inch (2.5 cm) from the end of the semi-con shield, wrap two turns of tape as a marker. Bevel the end of the insulation at a 45-degree angle, approximately 1/4 inch (0.6 cm) back. Thoroughly clean the insulation with an approved safety solvent, wiping from the cable end toward the outer jacket. Apply lubricant sparingly along the cable and inside the cable adapter. Slide the adapter, small end first, over the cable with a twisting motion until its end is flush with the tape marker.
- Expose Conductor and Secure Retaining Ring
Remove any protruding cable insulation by cutting it even with the end of the cable adapter, being careful not to cut or nick the adapter or conductor. The exposed conductor length should be 4 3/4 to 5 inches (12.1 to 12.7 cm); if not, redo the assembly. Assemble the aluminum retaining ring over the conductor and snug it firmly against the cable adapter. Using the provided hex wrench, tighten the socket head screw hand tight. Confirm the exposed conductor measures 4 3/8 to 4 3/4 inches (11.1 to 12.1 cm); if not, redo the assembly.
- Prepare and Crimp Connector
Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor and immediately fully insert it into the crimp connector, which contains inhibitor. Measure the distance from the end of the connector to the holding collar; if it is over 7 inches (17.8 cm), redo all previous work. Confirm components are positioned as shown in the instructions and that bolt holes in the crimp connectors align with the mating part. Crimp the connectors following the instructions packaged with them, rotating each crimp 90 or 180 degrees. After crimping, re-measure the distance from the end of the connector to the holding collar; if over 7 inches (17.8 cm), redo all previous work.
- Assemble and Torque Bolts
Assemble the washers and bolt in the following order: flat washer against the spade contact, Belleville washer (concave side down), then the hex-head bolt. Hand tighten the assembly. Clean and lubricate the area. Using a torque wrench with a 15/16 inch socket, tighten all bolts to 50 to 60 ft. lbs. (67.8 to 81.3 Nm). Do not attempt to move or reposition any part of the assembly after the bolts are tightened.
- Lubricate and Position Receptacle Housing
Apply the supplied lubricant or an ELASTIMOLD approved lubricant generously to the outside of the cable adapter, the area of the splice section, and the inside mating surface of the receptacle housing. Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the nylon venting rod (supplied).
- Complete Housing Assembly with Tool
Attach the appropriate assembly tool (650ATY or 600RRT) as shown in the specific instructions. Slowly raise the handle (for 650ATY) or turn the hex nut (for 600RRT) to slide the receptacle housing completely over the splice section. WARNING: DO NOT place hand on threaded rod or guide shaft with the assembly tool in place. Remove the venting rod once the housing is fully seated.
- Perform Final Checks and Grounding
Check all cable adapters to ensure they are located properly and remove all vinyl tape markers. Complete the installation of any ECS grounding device according to its specific instructions. Connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings. Make a small loop and twist tightly, taking care not to damage the eye, and connect to ground.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.