ABB Installation Products K656CY-HP 15-25kV 600 Series Deadbreak Basic Housing Package Wye Joint with Test Point
UPC: 783786470471
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15-25kV Voltage Rating
- 600 Series Deadbreak Technology
- Wye Joint Configuration
- Integrated Test Point for Safe Testing
- ABB Installation Products Quality
Specifications
Amperage Rating | 600 A |
Application | Used to Join Cables in a Disconnectable 3-Way Joint, Suitable for Small Vaults and Manholes Due to its Compact Size |
Color | Black |
Connection Type | Deadbreak |
Current Rating | 600 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 33.72 in |
Length | 856.488 mm |
Material | Housing - EPDM-Rubber |
Series | 600 Series |
Special Features | Includes Integral Capacitive Test Point, Cold Shrinkable Seal with Copper Rod and Crimp Connector |
Standard | ANSI/IEEE Standard 386 |
Type | Deadbreak Separable Wye Joint with Test Point |
Voltage Rating | 15-25 kV |
Voltage Rating | 15 to 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 22.0000 L |
Package Weight (Metric) | 9.9790 kg |

168FLR1-B5220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Bi-Metal Conductor size 2 AWG Stranded/Compressed, 1 AWG Solid/Compact. no Sealing Kit
K675LR-M5380
900 Amp, 15/25kV, 600 Series Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.370 inch to 1.630 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
K656ETP-J0270-DRG
600 Amp, 25kV, Deadbreak Elbow, Test and Ground Replacement Kit with Test Point. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. With Insulated Cap.
K656ETP-N0410-DRG
600 Amp, 25kV, Deadbreak Elbow, Test and Ground Replacement Kit with Test Point. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000. With Insulated Cap.
K656ETP-M0330-DRG
600 Amp, 25kV, Deadbreak Elbow, Window Op Connector Kit with Test Point. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. With Insulated Cap.
K675LR-K2360-S
900 Amp, 15/25kV, 600 Series Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Compression Lug. Conductor Size Compressed Stranded 650 kcmil or Compacted Solid 750 kcmil. Cold-Shrinkable Jacket Seal Included.
K675LR-M-5360
900 Amp, 15/25kV, 600 Series Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.370 inch to 1.630 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400.Frequently Asked Questions
What is the voltage rating for the ABB K656CY-HP?
The ABB K656CY-HP has a voltage rating of 15-25kV.
What type of connection does the K656CY-HP offer?
The K656CY-HP is a 600 Series Deadbreak Basic Housing Package with a Wye Joint configuration.
Does the K656CY-HP include a test point?
Yes, the ABB K656CY-HP features an integrated test point for convenient circuit testing.
Who is the manufacturer of the K656CY-HP?
The K656CY-HP is manufactured by ABB - Installation Products.
How to Install K656/K676 Series Deadbreak Receptacles
This guide provides detailed instructions for installing K656 and K676 series deadbreak receptacles, including cable preparation, crimping, and final assembly for splicing and tapping solid dielectric cables. These instructions cover the installation of one leg; repeat for additional cables as needed.
Estimated time: 1h 30m
Tools needed:
Hex wrench (supplied), Torque wrench with 15/16" socket, Wire brush (for aluminum cable), Rags, Approved safety solvent, Cable stripping tools, Crimp tool (refer to connector instructions), 650ATY assembly tool OR 600RRT assembly tool
Supplies needed:
K656/K676 Deadbreak Receptacle Kit (housings, adapters, center sections, collars, bolts, crimp connectors, washers, venting rod), ELASTIMOLD approved lubricant (or supplied lubricant), No. 14 AWG copper wire (or equivalent) for grounding, Tape (for markers), Conductive copper strip (for flat metallic tape shielded cable, if applicable), ECS grounding device (if used)
- De-energize Apparatus and Inspect Components
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. Failure to follow instructions will result in serious injury. Inspect all parts for damage, proper rating, and compatibility with mating parts. Ensure all required tools and supplies are at hand and maintain cleanliness.
- Clean and Square Cable End
Wipe the outer jacket clean for a distance of 38 inches (96.5 cm) from the end. Cut the cable end squarely to ensure maximum available length for crimp growth.
- Slide ECS Grounding Device Tube (Optional)
If an ECS grounding device is being used, slide the tube onto the cable a distance of 38 inches (96.5 cm) from the end.
- Slide Receptacle Housing
Slide the receptacle housing onto the cable a distance of 30 inches (76.2 cm) from the end.
- Prepare Jacketed Concentric Neutral Cable (Part A)
Measure 13-3/4 inches (34.9 cm) from the cable end and remove the cable jacket with a straight, smooth cut, taking care not to damage neutral wires. Bend neutral wires back. Measure 10-1/4 inches (26 cm) from the cable end and remove the semi-con shield with a straight, smooth, squared cut, avoiding nicks to the insulation. At 1 inch (2.54 cm) from the end of the semi-con shield, wrap two turns of tape as a marker. Bevel the end of the insulation at a 45-degree angle, approximately 1/4 inch (0.64 cm) back. Thoroughly clean the insulation with an approved safety solvent, wiping from the cable end toward the outer jacket. Apply lubricant sparingly along the cable and inside the cable adapter. Slide the adapter, small end first, over the cable with a twisting motion until the end of the adapter is flush with the tape marker.
- Remove Protruding Cable Insulation
Remove any protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of exposed conductor should be 4 3/4 inches to 5 inches (12.07 cm to 12.7 cm). If not, redo the assembly.
- Assemble Aluminum Retaining Ring
Assemble the aluminum retaining ring over the conductor and snug it firmly against the cable adapter. Using the provided hex wrench, tighten the socket head screw hand tight. Confirm the exposed conductor measures 4 3/8 inches to 4 3/4 inches (11.11 cm to 12.07 cm). If not, redo the assembly.
- Prepare Crimp Connector
Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor and immediately insert it into the crimp connector, which contains inhibitor. Ensure the conductor is fully inserted into the crimp barrel. Measure the distance from the end of the connector to the holding collar; if it is over 7 inches (17.78 cm), do not proceed and recheck all previous work.
- Repeat for Additional Cables
Repeat Steps 5 through 8 for all remaining cables to be joined in the splice.
- Confirm Component Alignment Before Crimping
Prior to crimping, confirm that all components are positioned correctly and that the bolt holes in the crimp connectors are properly aligned with the bolt holes of the mating part.
- Crimp Connectors
Crimp the connectors following the instructions packaged with the connectors. Rotate each crimp 90 or 180 degrees. After crimping, measure the distance from the end of the connector to the holding collar; if it is over 7 inches (17.78 cm), do not proceed and redo all previous work.
- Assemble Washers and Bolt
Assemble the washers and bolt in the following order: flat washer against the spade contact, Belleville washer (concave side down), then the hex-head bolt. Hand tighten. Clean and lubricate the bolt and washer assembly area.
- Torque Tighten Bolts
Using a torque wrench with a 15/16 inch socket, tighten all bolts to 50 to 60 ft. lbs. The splice and cables are now in their final positions; do not attempt to move or reposition any part of the assembly after the bolts are tightened.
- Apply Lubricant for Assembly
Apply the supplied lubricant or ELASTIMOLD approved lubricant generously to the outside of the cable adapter, the area of the splice section as shown in the diagram, and the inside mating surface of the receptacle housing.
- Slide Receptacle Housing and Insert Venting Rod
Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the nylon venting rod (supplied).
- Use Assembly Tool to Complete Housing Slide
Attach the appropriate assembly tool (650ATY or 600RRT). If using the 650ATY, ensure the 'U' shaped yoke is over the splice section and the 'C' shaped yoke is over the receptacle housing, then slowly raise the handle to slide the housing over the splice section. If using the 600RRT, slide the housing over the interface by turning the hex nut on either side of the tool. WARNING: DO NOT place hand on threaded rod or guide shaft with the assembly tool in place. Remove the venting rod once the housing is fully seated.
- Repeat Housing Assembly for Remaining Cables
Repeat Steps 15 and 16 for all remaining cables to complete the housing assembly for the entire splice.
- Verify Cable Adapters and Remove Markers
Check all cable adapters to ensure they are located properly and remove all vinyl tape markers.
- Complete Grounding
If an ECS grounding device is used, complete its installation according to its specific instructions. Connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings. Make a small loop and twist tightly, taking care not to damage the eye, and connect to ground.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.