ABB Installation Products K656CETP-K0300-DRGS 25kV, 600 Amp, Combo T Elbow Reducing Tap Plug with Test Point, includes Stud, Cable…
UPC: 075114324366
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 25kV Voltage Rating
- 600 Amp Current Rating
- Combo T Elbow Reducing Tap Plug with Test Point
- Universal Aluminum Connector
- Includes Stud, Cable Adapter, Lug, and Insulated Cap Kit
Specifications
Amperage Rating | 600 A |
Application | 600 Amps, 25kV Connector |
Color | Black |
Conductor Range | 350 kcmil , 400 kcmil |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Special Features | Reducing Tap Plug with Stud, Cable Adapter, Lug and Insulated Cap |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | ComboT Elbow with Test Point |
Voltage Rating | 25 kV |
Width | 13.31 in |
Width | 338.074 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655LR-K0300-SG1
600 Series Elbow with insulated plug, cap, stud, lug and cable adapter, 15/25KV, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185. 200ECS-G1 Jacket Seal and Grounding Kit Included.
K151SP-B0250-S
15/25kV, 200 Amp, Deadbreak Straight Plug without Test Point, Cable Insulation Diameter 0.635 to 0.905 inches, Aluminum, Conductor Size 250 - 2/0 Stranded/Compressed or 3/0 Solid/Compact. S - Cold-Shrinkable Jacket Seal
655CETP-K0300
15kv 600 Amp Dead Break Combo T Elbow with 200 Amp Reducing Tap Plug, Stud, Cable adapter and Lug Kit without Test Point. Cable Insulation Diameter 1.090 inch to 1.310 inch. Universal Aluminum Compression Lug. Conductor Size Compressed Stranded 350 kcmil or Solid Compact 400 kcmil.
655CETP-M0380-SG3
600 Amp, 15kV, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Lug, No Test Point, Aluminum, Cable Insulation Diameter 1.370 inch to 1.630 inch. Sealing Kit - Cold Shrinkable Seal with Copper Braid and Constant Force Spring.
168ELR-7495-5270-S
15kV, 200 Amp, Loadbreak Repair Elbow with Test Point, Cable Insulation Diameter 0.740 to 1.100 inches, Bi-Metal, Conductor Size 240 - 4/0 Stranded/Compressed or 250 Solid/Compact. S - Cold-Shrinkable Jacket Seal
655CETP-H0270-DRG-S
15kV, 600 Series ComboT Elbow with 200 Amp Reducing Tap Plug, Stud, Cable Adapter, Lug and Insulated Cap Kit, without Test Point, with Sealing Kit. Cable Insulation Diameter Range 0.850 to 1.050 inches, Aluminum Lug, 4/0 Stranded/Compressed or 250 Solid/Compact.
K656CETPM0380DRGS
15/25kV, 600 Amp Base Aluminum, includes test point, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Lug and Insulated Cap Kit. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. S - Cold Shrinkable Jacket Seal.
655CETP-L0330-DRG
600 Amp, 15kV, Combo T Elbow Reducing Tap Plug with Stud, Cable Adapter, Lug and Insulated Cap Kit, No Test Point, Aluminum, Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.Frequently Asked Questions
What is the voltage rating of this ABB tap plug?
The ABB K656CETP-K0300-DRGS has a voltage rating of 25 kV.
What is the current rating for this elbow connector?
This ABB tap plug is rated for 600 Amps.
What cable insulation diameters does this tap plug support?
It supports cable insulation diameters from 1.090 to 1.050 inches (27.7-33.3 mm).
What conductor sizes are compatible with this connector?
It is compatible with 350 kcmil stranded/compressed or 400 kcmil solid/compact aluminum conductors, and 185 mm² compact aluminum conductors.
Does this tap plug come with a grounding kit?
No, this specific model does not include a grounding or sealing kit.
What components are included with this tap plug kit?
The kit includes a stud, cable adapter, lug, and an insulated cap kit.
What is the connector type of this ABB product?
The connector type is a Combo T Elbow Reducing Tap Plug.
How to Install 655/656/675/676CETP Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 655/656/675/676CETP deadbreak elbow connectors, ensuring fully shielded and submersible cable connections for 15kV class systems. Always de-energize apparatus before installation.
Estimated time: 2h
Tools needed:
Wire strippers, Wire brush (for aluminum conductor), Crimping tool (per lug instructions), Torque wrench (600AT or 600ATM assembly tool), Hotstick, Suitable sensing device (for capacitive test points)
Supplies needed:
Cable adapter, Compression lug, Lubricant (supplied), Vinyl plastic tape, Tape retainer (if applicable), Tape marker (if applicable), Grounding wire (minimum No. 14 AWG Copper), Silicone grease (for test point cap)
- Prepare the Cable Position
Position the cable in its final assembled location, ensuring enough slack for elbow removal. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent back concentric neutral wires.
- Prepare Cable Jacket and Shield
Remove the outer jacket to the dimension shown in the product documentation (typically 9 3/4 or 10 3/4 inches). Fold back shield wires. Depending on your cable type (Flat Metallic Tape, Fabric Tape, Longitudinally Corrugated, Semi-con), remove the shield and secure it with vinyl plastic tape, or install a tape retainer and tape marker as specified. If using UNISHIELD® or lead sheath cable, refer to the 10TL cable shield adapter instructions. Do not cut or nick the cable insulation.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor and Install Compression Lug
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Ensure the exposed conductor length is 4 3/8 to 4 11/16 inches (111mm to 119mm); redo if incorrect. For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it. Measure the 'Check Dimension' before crimping (must be less than 6 1/2 inches (165mm)). Crimp the compression lug following the instructions supplied with the lug, locating the first crimp on the end towards the cable adapter. Wipe off all excess inhibitor. Verify the distance from the end of the compression lug to the cable adapter is 6 1/2 to 7 1/4 inches (165mm to 184mm); redo if incorrect.
- Install Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance with the supplied lubricant. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Connect Elbow to Mating Product
WARNING: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. Install the stud into the apparatus by hand until it is fully seated. Clean and lubricate both the elbow and the mating part with the supplied lubricant. Push the elbow onto the mating part. Use the appropriate assembly tool (600AT for products dated Sep 30, 2013 or earlier, or 600ATM for products dated Oct 1, 2013 or later) to engage the hex broach in the contact assembly. Insert the contact assembly into the elbow interface to engage the stud. Torque the contact assembly to 19-25 ft/lbs (600AT) or 50-60 ft/lbs (600ATM), ensuring not to exceed 60 ft/lbs.
- Ground the Cable Shield
Insert one end of a grounding wire (with ampacity at least equivalent to No. 14 AWG Copper) through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded according to the instructions supplied with any grounding device used, or via an alternate method if no device is present. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Verify Seating and Perform Voltage Test (656CETP only)
Confirm complete assembly by ensuring no portion of the colored interface sleeve is visible when viewed from the side. For 656CETP connectors, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device; do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points to determine if the cable is energized. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone grease and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.