ABB - Installation Products K655YSR-M0320 - 600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size Compressed Stranded 450 kcmil or Compacted Solid 550 kcmil. Includes Cable Adapter, Lug and Retaining Ring.

ABB Installation Products K655YSR-M0320 600 Amp, 15-25kV, 600 Series Deadbreak Straight Receptacle. Cable Insulation Diameter…

UPC: 075114424288


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB 600 Series Deadbreak Straight Receptacle, SKU K655YSR-M0320, is designed for reliable electrical connections in medium voltage applications. This receptacle operates at 600 Amps and is rated for 15-25kV systems, providing a secure interface for power distribution. It accommodates cable insulation diameters ranging from 1.370 inches to 1.630 inches, ensuring compatibility with a defined range of cable sizes. The included aluminum compression lug is suitable for compressed stranded conductors up to 450 kcmil or compacted solid conductors up to 550 kcmil, facilitating robust and secure conductor termination. This unit comes complete with a cable adapter, the aluminum compression lug, and a retaining ring, offering a comprehensive solution for deadbreak connections. The 600 Series design emphasizes straightforward installation and dependable performance in electrical infrastructure. UNSPSC Code: 39121421.
  • 600 Amp current rating
  • 15-25kV voltage class
  • 600 Series Deadbreak Straight Receptacle
  • Accommodates cable insulation 1.370" - 1.630"
  • Includes aluminum compression lug for 450 kcmil (stranded) or 550 kcmil (solid) conductors

Specifications

Amperage Rating
600 A
Application
Designed to provide a fully shielded, submersible cable connection on 15/25kV high-voltage “I”, “Y”, or “H” Bus
Color
Black
Conductor Range
450 COMPR/STR kcmil , COMPT/SOL 550 kcmil
Connection
Compression
Connection Type
Deadbreak Straight Receptacle
Current Rating
600 A
Insulation
True
Length
17 in
Length
431.8 mm
Material
EPDM-Rubber
Material
Aluminum
Series
600 Series
Size
Cable Insulation Diameter 1.370 inch to 1.630 inch
Standard
ANSI/IEEE Standard 386
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Straight Receptacle
Voltage Rating
15/25 kV
Voltage Rating
15-25 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
6.4900 L
Package Weight (Metric)
2.9440 kg
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size kcmil Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300.

K655LR-J0330

600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size kcmil Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300.
Single cable clamp 150-300mm2 for power terminal type 5

45000034

Single cable clamp 150-300mm2 for power terminal type 5
600 Amp, 15/25kV, 600 Series Spiking Elbow wih Spiking Contact, Insulating Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000.

K655SELRN0410

600 Amp, 15/25kV, 600 Series Spiking Elbow wih Spiking Contact, Insulating Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000.
600 Amp, 25kV, Deadbreak Stick-Op Replacement Connector Kit. FB - Fixed Bolt.

K655RLRTP-FB

600 Amp, 25kV, Deadbreak Stick-Op Replacement Connector Kit. FB - Fixed Bolt.
600 Amp, 15/25kV, 600 Series Spiking Elbow wih Spiking Contact, Insulating Plug, Cap, Stud, Lug and Cable Adapter.

K655SELR

600 Amp, 15/25kV, 600 Series Spiking Elbow wih Spiking Contact, Insulating Plug, Cap, Stud, Lug and Cable Adapter.
RetroFit Cam-Op Connector Kit, 25kv, 600 Amp, Cable Insulation Diameter 1.180-1.465 inches, Conductor Size 500 Stranded/Compressed, SwitchGear

K655LINKCLR-L0330SWG

RetroFit Cam-Op Connector Kit, 25kv, 600 Amp, Cable Insulation Diameter 1.180-1.465 inches, Conductor Size 500 Stranded/Compressed, SwitchGear
RetroFit Cam-Op Connector Kit, 25kv, 600 Amp, Cable Insulation Diameter 1.090-1.310 inches, Conductor Size 350 Stranded/Compressed, SwitchGear

K655LINKCLR-K0300SWG

RetroFit Cam-Op Connector Kit, 25kv, 600 Amp, Cable Insulation Diameter 1.090-1.310 inches, Conductor Size 350 Stranded/Compressed, SwitchGear
25kv, 600 Amp, Direct Test Straight Receptacle Elbow, Deadbreak, Cable Insulation Diameter 1.180-1.465. Aluminum Lug, Conductor Size 500 Stranded/Compressed or 600 Compact/Solid. 17 inches long. Mates with K650SRA.

K655DSR-L0330

25kv, 600 Amp, Direct Test Straight Receptacle Elbow, Deadbreak, Cable Insulation Diameter 1.180-1.465. Aluminum Lug, Conductor Size 500 Stranded/Compressed or 600 Compact/Solid. 17 inches long. Mates with K650SRA.

Frequently Asked Questions

What is the K655YSR designed for?

It provides a fully shielded, submersible cable connection on 15/25kV high-voltage “I”, “Y”, or “H” Bus. It allows a straight cable connection on switchgear or electrical apparatus with 600 Amp bushings.

What is the momentary current rating?

The momentary current rating for both 15kV and 25kV voltage classes is 25kA Symmetrical for 10 cycles.

How do I select the correct catalog number?

First, determine the cable insulation diameter to select the 'W' code. Then, choose the proper compression lug 'X' code based on the conductor size.

What items are included in the K655YSR kit?

Each kit contains the receptacle housing, lubricant, installation instructions, cable adapter, aluminum compression lug, adapter retaining ring, crimp chart, instruction sheet, and bolts and washers.

How is the K655YSR connected or disconnected?

It can be easily connected or disconnected using standard hand tools and equipment, but only in a de-energized state.

Is the K655YSR submersible?

Yes, the K655YSR features a fully shielded, fully submersible molded rubber housing.

What is the continuous current rating?

The continuous current rating for both 15kV and 25kV voltage classes is 600 Amps.

What are the operating voltage limits for 25kV class?

For the 25kV class, the maximum phase-to-ground operating voltage is 16.2kV, and phase-to-phase is 28kV.

What are the operating voltage limits for 15kV class?

For the 15kV class, the maximum phase-to-ground operating voltage is 8.3kV, and phase-to-phase is 14.4kV.

What cable sizes are compatible with K655YSR?

The K655YSR supports #2 AWG to 1250 kcmil for aluminum and copper conductors. Insulation diameters range from 0.640 in to 1.935 in.

How to Install K656/K676 Series Deadbreak Receptacles

This guide provides detailed instructions for the safe installation and wiring of K656/K676 series deadbreak receptacles for 600 ampere, 15kV and 25kV solid dielectric cables. These instructions cover the installation of one leg of the connector.

Estimated time: 1h 30m

Tools needed:

Cable cutting tool, Wire strippers, Rag, Approved safety solvent, Hex wrench, Wire brush (for aluminum cable), Torque wrench with 15/16” socket, 650ATY assembly tool (or 600RRT assembly tool)

Supplies needed:

Receptacle housings, Cable adapters, I, Wye or H Center sections, Aluminum holding collars, Lubricant (supplied or ELASTIMOLD approved), Hex-head bolts, Crimp connectors, Belleville washers, Flat washers, Nylon venting rod, Tape (for marker), No. 14 AWG copper wire (or equivalent), ECS grounding device (if used), Appropriate HV insulated cap(s) or connector(s)

  1. Ensure Safety and Inspect Components

    DANGER: All apparatus must be de-energized during installation or removal. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. Inspect all parts for damage, proper rating, and compatibility with mating parts. Remove any protective shipping covers and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit. Check contents of package to ensure they are complete and undamaged.

  2. Clean and Cut Cable End

    Wipe the outer jacket clean for a distance of 38 inches (96.5 cm) from the end. Cut the cable end squarely to ensure maximum available length for crimp growth, with respect to the interface.

  3. Install ECS Grounding Device Tube (if applicable)

    If an ECS grounding device is being used, slide the tube onto the cable a distance of 38 inches (96.5 cm) from the end.

  4. Slide Receptacle Housing onto Cable

    Slide the receptacle housing onto the cable a distance of 30 inches (76.2 cm) from the end.

  5. Prepare Jacketed Concentric Neutral Cable

    Refer to the special cable preparation supplement for your specific cable type (e.g., Jacketed Concentric Neutral Cable or Flat Metallic Tape Shielded Cable). For Jacketed Concentric Neutral Cable: Measure 13-3/4 inches (34.9 cm) from the cable end and remove the cable jacket with a straight, smooth cut, taking care not to damage neutral wires. Bend neutral wires back and out of the way. Measure 10-1/4 inches (26 cm) from the cable end and remove the semi-con from the insulation with a straight, smooth, 'squared' cut, taking care not to cut or nick the insulation. At 1 inch (2.54 cm) from the end of the semi-con shield, wrap two turns of tape to serve as a marker. Bevel the end of the insulation at a 45-degree angle, approximately 1/4 inch (0.64 cm) back. Thoroughly clean the insulation with an approved safety solvent, wiping from the cable end toward the outer jacket. Apply supplied lubricant sparingly along the cable and inside the cable adapter. Slide the adapter, small end first, over the cable with a twisting motion until the end of the adapter is flush with the tape marker.

  6. Remove Protruding Insulation and Verify Conductor Length

    Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of the exposed conductor should be 4-3/4 inches to 5 inches (12.07 cm - 12.7 cm). If not, redo the assembly.

  7. Assemble Aluminum Retaining Ring

    Assemble the aluminum retaining ring over the conductor and snug it firmly against the cable adapter. Using the provided hex wrench, tighten the socket head screw hand tight. Confirm the exposed conductor measures 4-3/8 inches to 4-3/4 inches (11.11 cm - 12.07 cm). If not, redo the assembly.

  8. Prepare and Insert Crimp Connector

    Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor and immediately insert it into the crimp connector, which contains inhibitor. Ensure the conductor is fully inserted into the crimp barrel. Measure the distance from the end of the connector to the holding collar. If the distance is over 7 inches (17.78 cm), do not proceed; recheck all previous work.

  9. Confirm Component Alignment

    Prior to crimping the connector, confirm that all components (receptacle housing, cable adapter, crimp connector) are positioned correctly. Ensure the bolt holes in the crimp connectors are positioned properly to align with the bolt holes of the mating part.

  10. Crimp Connectors

    Crimp the connectors following the instructions packaged with the connectors. Rotate each crimp 90 or 180 degrees. After crimping, measure the distance from the end of the connector to the holding collar. If the distance is over 7 inches (17.78 cm), do not proceed; redo all previous work.

  11. Assemble Washers and Bolt

    Assemble the washers and bolt in the following order: flat washer against the spade contact, Belleville washer (concave side down), then the hex-head bolt. Hand tighten. The splice and cables are now in their final positions; do not attempt to move or reposition any part of the assembly after the bolts are tightened.

  12. Torque Tighten Bolts

    Using a torque wrench with a 15/16 inch socket, tighten all bolts to 50 to 60 ft. lbs. (67.8 - 81.3 Nm).

  13. Lubricate Cable Adapter and Receptacle Mating Surface

    Apply the supplied lubricant or ELASTIMOLD approved lubricant generously to the outside of the cable adapter, the area of the splice section, and the inside mating surface of the receptacle housing.

  14. Slide Receptacle Housing and Insert Venting Rod

    Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the nylon venting rod (supplied).

  15. Fully Seat Receptacle Housing with Assembly Tool

    Attach the 650ATY assembly tool as shown in the product documentation, ensuring the 'U' shaped yoke is over the splice section and the 'C' shaped yoke is over the receptacle housing. With the assembly tool in place, slowly raise the handle to slide the receptacle housing over the splice section. Remove the venting rod. WARNING: DO NOT place hand on threaded rod or guide shaft with the assembly tool in place if using the 600RRT tool.

  16. Perform Final Checks and Grounding

    Check all cable adapters to make sure they are located properly and remove all vinyl tape markers. Complete the installation of any ECS grounding device according to its specific instructions. Connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings, making a small loop and twisting tightly, taking care not to damage the eye. Connect this wire to ground.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.